01Fault

Voltronic inverter error 01 (F1)

Fan is locked when inverter is off

Also displayed as F1 on some models.

Faultthe inverter cuts its output and the red LED stays solid until the fault is cleared.

The exact meaning depends on your model:

Axpert MAX II TWIN

InverterFault

Also applies to:Axpert MAX II TWIN 8KWAxpert MAX II TWIN 11KWAxpert MAX II TWIN 12KWAxpert MAX II Duplex 8KWAxpert MAX II Duplex 11KWAxpert MAX II 8KWAxpert MAX II 11KWAxpert MAX 8K TWIN PV11K+33

What it means

Fan is locked when inverter is off

Cause: Fan fault.

How to fix it

Replace the fan.

Source: Axpert-MAXII-8K-TWIN-Off-grid-manual.pdf, p.47 · Axpert-MAXII-8K-TWIN-Off-grid-manual.pdf, p.55 · Axpert-MAXII-11K-TWIN-Off-grid-manual.pdf, p.47 · +47 more official manuals

InfiniSolar V II

InverterFault

Also applies to:InfiniSolar V II 2KWInfiniSolar V II 3KWInfiniSolar V II 5KWInfiniSolar V II 1.5KWInfiniSolar V II WP 2KWInfiniSolar V II WP 3KWInfiniSolar V II WP 5KWInfiniSolar V 1KW+4

What it means

Fan lockedFault code 01 shown on the display with the fault icon on: Fan locked.

Cause: Fan fault.

How to fix it

Replace the fan.

Source: InfiniSolarVII_2KW-3KW-5KW_manual.pdf, p.26 · InfiniSolarVII_2KW-3KW-5KW_manual.pdf, p.28 · InfiniSolarVII_1.5KW_manual.pdf, p.27 · +5 more official manuals

Also applies to:InfiniSolar V II 2P 6KW

What it means

Fan is lockedFault code 01 shown on the display with the fault icon on: Fan is locked..

Cause: Fan fault.

How to fix it

Replace the fan.

Source: InfiniSolar-VII-2P-6KW-manual-20201207.pdf, p.30 · InfiniSolar-VII-2P-6KW-manual-20201207.pdf, p.32

What it means

Bus voltage overFault code 01 shown on the display with the fault icon on: Bus voltage over.

Cause: Bus voltage over.

How to fix it

  1. Restart the unit.
  2. If the fault happens again, contact your installer or the repair centre.

Source: InfiniSolar-WP-LV-12KW-Premium-manual.pdf, p.52

InfiniSolar 10KW

InverterFault

Also applies to:InfiniSolar 15KWInfiniSolar Super 4KWInfiniSolar Plus 5KWInfiniSolar TX-PA 30KW

What it means

Bus voltage overFault code 01 shown on the display with the fault icon on: Bus voltage over.

Cause: Surge.

How to fix it

  1. Restart the inverter
  2. If the error message still remains, please contact your installer.

Source: InfiniSolar-10KW-manual-20191126.pdf, p.50 · InfiniSolar-15K-manual-20200313.pdf, p.51 · InfiniSolar-Super-4KW-manual.pdf, p.47 · +2 more official manuals

InfiniSolar E 5.5KW

InverterFault

What it means

DC bus voltage exceeds the upper thresholdFault code 01 shown on the display with the fault icon on: DC bus voltage exceeds the upper threshold.

Cause: DC bus voltage exceeds the upper threshold.

How to fix it

  1. Disconnect AC circuit breaker first.
  2. Then, disconnect DC circuit breaker.
  3. Until LCD screen completely shuts down, turn on DC breaker first.
  4. It will show "No Utility" in LCD screen.
  5. Then, turn on AC breaker.
  6. After 300 seconds, the system will automatically connect to the grid.
  7. If the error message still remains, please contact your installer.
  8. The internal temperature is higher than specified temperature.
  9. Leave inverter to cool down to room temperature.
  10. If the error message still remains, please contact your installer.
  11. Check if the open circuit voltage of PV modules is higher than 500VDC.
  12. If PV open circuit voltage is less than 500VDC and the error message remains, pelase contact your installer.
  13. Turn off the inverter.
  14. Then, restart the inverter.
  15. If the error message still remains, please contact your installer.
  16. The ground voltage is too high.
  17. Please disconnect AC breaker first and then DC breaker.
  18. Check if grounding is connected properly after LCD screen.

Source: InfiniSolarE-5.5KW-manual.pdf, p.43

InfiniSolar 2KW/3KW

InverterFault

Also applies to:InfiniSolar 2KWInfiniSolar 3KW

What it means

DC bus voltage exceeds the upper thresholdFault code 01 shown on the display with the fault icon on: DC bus voltage exceeds the upper threshold.

Cause: DC bus voltage exceeds the upper threshold.

How to fix it

  1. Disconnect AC circuit breaker first. Then, disconnect DC circuit breaker
  2. Until LCD screen completely shuts down, turn on DC breaker first. It will show "No Utility" in LCD screen. Then, turn on AC breaker. After 300 seconds, the system will automatically connect to the grid
  3. If the error message still remains, please contact your installer.

Source: InfiniSolar-2KW3KW-manual.pdf, p.46

DC Converter 3KW

InverterFault

What it means

Input current is abnormalFault code 01 shown on the display with the fault icon on: Input current is abnormal..

Cause: Input current is abnormal.

How to fix it

  1. Restart the converter
  2. If the problem remains, please contact your installer.

Source: DC-converter-3KW-manual.pdf, p.20 · DC-converter-3KW-manual.pdf, p.21

ESS510

Energy storage systemFault

What it means

DC bus voltage exceeds the upper thresholdFault code 01 shown on the display with the fault icon on: DC bus voltage exceeds the upper threshold..

Cause: DC bus voltage exceeds the upper threshold.

How to fix it

  1. Disconnect AC circuit breaker first.
  2. Then, disconnect DC circuit breaker.
  3. Until LCD screen completely shuts down, turn on DC breaker first.
  4. It will show "No Utility" in LCD screen.
  5. Then, turn on AC breaker.
  6. After 300 seconds, the system will automatically connect to the grid.
  7. If the error message still remains, please contact your installer.

Source: ESS510-manual.pdf, p.68

Also applies to:Galleon II 6KGalleon II 10KGiant Elite 1P/1P 6K-10KWinner Pro 6KVAWinner Pro 10KVA

What it means

Bus start failureFault code 01 shown on the display; the UPS has detected a fault condition: Bus start failure.

Cause: Bus start failure.

How to fix it

  1. Restart the unit.
  2. If the fault happens again, contact your installer or the repair centre.

Source: GalleonII-6-10K-Tower-RT-manual.pdf, p.29 · Giant-Elite-1P-1P_manual.pdf, p.26 · WinnerPro-6-10KVA_manual.pdf, p.23

Also applies to:Galleon III 1KGalleon III 2KGalleon III 3KWinner Pro 1KVA-3KVAWinner Pro+ 1KWinner Pro+ 2KWinner Pro+ 3KOtima II 800VA-3KVA+1

What it means

Bus start failFault code 01 shown on the display; the UPS has detected a fault condition: Bus start fail.

Cause: Bus start fail.

How to fix it

  1. Restart the unit.
  2. If the fault happens again, contact your installer or the repair centre.

Source: Galleon-III-Tower-Rack-1-3K-manual.pdf, p.31 · Winner-Pro_manual.pdf, p.15 · WinnerProPlus-1-3K-Tower-Rack_manual.pdf, p.24 · +2 more official manuals

Also applies to:Galleon X9 6K RTGalleon X9 10K RT

What it means

Bus Start FailFault code 01 shown on the display; the UPS has detected a fault condition: Bus Start Fail.

Cause: The internal converter failed, so the DC bus voltage could not be boosted correctly.

How to fix it

Contact the dealer to repair.

Source: Galleon-X9-6-10K-RT_manual.pdf, p.28

Also applies to:Giant Elite 3P/3P 10K-40KVA

What it means

Firmware incompatibilityFault code 01 shown on the display; the UPS has detected a fault condition: Firmware incompatibility.

Cause: Firmware incompatibility.

How to fix it

  1. Restart the unit.
  2. If the fault happens again, contact your installer or the repair centre.

Source: Giant-Elite-3P3P-manual.pdf, p.41

SCC-MPPT Solar Charge Controller

Charge controllerFault

Also applies to:SCC-MPPT 300WSCC-MPPT 600WSCC-MPPT 850W

What it means

Battery wires are not connected well, battery defect, or charge controller defectFault code F1 shown on the display with the fault icon on: Battery wires are not connected well, battery defect, or charge controller defect..

Cause: Battery wires are not connected well. Battery defect. Charge controller defect.

How to fix it

  1. Check if battery wires are properly connected.
  2. Replace battery.
  3. If the charge controller is defective, replace the unit.

Source: SCC-MPPT_manual.pdf, p.6

Frequently asked questions

What does error 01 mean on a Voltronic inverter?
It depends on the model — 49 devices use code 01. On the Axpert MAX II TWIN it means: Fan is locked when inverter is off. The card for each model on this page gives its exact meaning and fix.
Is error 01 a fault or a warning?
01 is a fault code: the inverter cuts its output and the red LED stays solid until it is cleared.
How do I clear or fix error 01?
Replace the fan. The exact steps for each affected model are listed on this page.

Related error codes

Compiled from official Voltronic user manuals. Always consult your device manual and a qualified technician before performing repairs.