Also applies to:Axpert MAX II TWIN 8KWAxpert MAX II TWIN 11KWAxpert MAX II TWIN 12KWAxpert MAX II Duplex 8KWAxpert MAX II Duplex 11KWAxpert MAX II 8KWAxpert MAX II 11KWAxpert MAX 8K TWIN PV11K+33
What it means
Fan is locked when inverter is off
Cause: Fan fault.
Source: Axpert-MAXII-8K-TWIN-Off-grid-manual.pdf, p.47 · Axpert-MAXII-8K-TWIN-Off-grid-manual.pdf, p.55 · Axpert-MAXII-11K-TWIN-Off-grid-manual.pdf, p.47 · +47 more official manuals
Also applies to:InfiniSolar V II 2KWInfiniSolar V II 3KWInfiniSolar V II 5KWInfiniSolar V II 1.5KWInfiniSolar V II WP 2KWInfiniSolar V II WP 3KWInfiniSolar V II WP 5KWInfiniSolar V 1KW+4
What it means
Fan locked — Fault code 01 shown on the display with the fault icon on: Fan locked.
Cause: Fan fault.
Source: InfiniSolarVII_2KW-3KW-5KW_manual.pdf, p.26 · InfiniSolarVII_2KW-3KW-5KW_manual.pdf, p.28 · InfiniSolarVII_1.5KW_manual.pdf, p.27 · +5 more official manuals
Also applies to:InfiniSolar V II 2P 6KW
What it means
Fan is locked — Fault code 01 shown on the display with the fault icon on: Fan is locked..
Cause: Fan fault.
Source: InfiniSolar-VII-2P-6KW-manual-20201207.pdf, p.30 · InfiniSolar-VII-2P-6KW-manual-20201207.pdf, p.32
What it means
Bus voltage over — Fault code 01 shown on the display with the fault icon on: Bus voltage over.
Cause: Bus voltage over.
How to fix it
- 1Restart the unit.
- 2If the fault happens again, contact your installer or the repair centre.
Source: InfiniSolar-WP-LV-12KW-Premium-manual.pdf, p.52
Also applies to:InfiniSolar 15KWInfiniSolar Super 4KWInfiniSolar Plus 5KWInfiniSolar TX-PA 30KW
What it means
Bus voltage over — Fault code 01 shown on the display with the fault icon on: Bus voltage over.
Cause: Surge.
How to fix it
- 1Restart the inverter
- 2If the error message still remains, please contact your installer.
Source: InfiniSolar-10KW-manual-20191126.pdf, p.50 · InfiniSolar-15K-manual-20200313.pdf, p.51 · InfiniSolar-Super-4KW-manual.pdf, p.47 · +2 more official manuals
What it means
DC bus voltage exceeds the upper threshold — Fault code 01 shown on the display with the fault icon on: DC bus voltage exceeds the upper threshold.
Cause: DC bus voltage exceeds the upper threshold.
How to fix it
- 1Disconnect AC circuit breaker first.
- 2Then, disconnect DC circuit breaker.
- 3Until LCD screen completely shuts down, turn on DC breaker first.
- 4It will show "No Utility" in LCD screen.
- 5Then, turn on AC breaker.
- 6After 300 seconds, the system will automatically connect to the grid.
- 7If the error message still remains, please contact your installer.
- 8The internal temperature is higher than specified temperature.
- 9Leave inverter to cool down to room temperature.
- 10If the error message still remains, please contact your installer.
- 11Check if the open circuit voltage of PV modules is higher than 500VDC.
- 12If PV open circuit voltage is less than 500VDC and the error message remains, pelase contact your installer.
- 13Turn off the inverter.
- 14Then, restart the inverter.
- 15If the error message still remains, please contact your installer.
- 16The ground voltage is too high.
- 17Please disconnect AC breaker first and then DC breaker.
- 18Check if grounding is connected properly after LCD screen.
Source: InfiniSolarE-5.5KW-manual.pdf, p.43
Also applies to:InfiniSolar 2KWInfiniSolar 3KW
What it means
DC bus voltage exceeds the upper threshold — Fault code 01 shown on the display with the fault icon on: DC bus voltage exceeds the upper threshold.
Cause: DC bus voltage exceeds the upper threshold.
How to fix it
- 1Disconnect AC circuit breaker first. Then, disconnect DC circuit breaker
- 2Until LCD screen completely shuts down, turn on DC breaker first. It will show "No Utility" in LCD screen. Then, turn on AC breaker. After 300 seconds, the system will automatically connect to the grid
- 3If the error message still remains, please contact your installer.
Source: InfiniSolar-2KW3KW-manual.pdf, p.46
What it means
Input current is abnormal — Fault code 01 shown on the display with the fault icon on: Input current is abnormal..
Cause: Input current is abnormal.
How to fix it
- 1Restart the converter
- 2If the problem remains, please contact your installer.
Source: DC-converter-3KW-manual.pdf, p.20 · DC-converter-3KW-manual.pdf, p.21
Energy storage systemFault What it means
DC bus voltage exceeds the upper threshold — Fault code 01 shown on the display with the fault icon on: DC bus voltage exceeds the upper threshold..
Cause: DC bus voltage exceeds the upper threshold.
How to fix it
- 1Disconnect AC circuit breaker first.
- 2Then, disconnect DC circuit breaker.
- 3Until LCD screen completely shuts down, turn on DC breaker first.
- 4It will show "No Utility" in LCD screen.
- 5Then, turn on AC breaker.
- 6After 300 seconds, the system will automatically connect to the grid.
- 7If the error message still remains, please contact your installer.
Source: ESS510-manual.pdf, p.68
Also applies to:Galleon II 6KGalleon II 10KGiant Elite 1P/1P 6K-10KWinner Pro 6KVAWinner Pro 10KVA
What it means
Bus start failure — Fault code 01 shown on the display; the UPS has detected a fault condition: Bus start failure.
Cause: Bus start failure.
How to fix it
- 1Restart the unit.
- 2If the fault happens again, contact your installer or the repair centre.
Source: GalleonII-6-10K-Tower-RT-manual.pdf, p.29 · Giant-Elite-1P-1P_manual.pdf, p.26 · WinnerPro-6-10KVA_manual.pdf, p.23
Also applies to:Galleon III 1KGalleon III 2KGalleon III 3KWinner Pro 1KVA-3KVAWinner Pro+ 1KWinner Pro+ 2KWinner Pro+ 3KOtima II 800VA-3KVA+1
What it means
Bus start fail — Fault code 01 shown on the display; the UPS has detected a fault condition: Bus start fail.
Cause: Bus start fail.
How to fix it
- 1Restart the unit.
- 2If the fault happens again, contact your installer or the repair centre.
Source: Galleon-III-Tower-Rack-1-3K-manual.pdf, p.31 · Winner-Pro_manual.pdf, p.15 · WinnerProPlus-1-3K-Tower-Rack_manual.pdf, p.24 · +2 more official manuals
Also applies to:Galleon X9 6K RTGalleon X9 10K RT
What it means
Bus Start Fail — Fault code 01 shown on the display; the UPS has detected a fault condition: Bus Start Fail.
Cause: The internal converter failed, so the DC bus voltage could not be boosted correctly.
How to fix it
Contact the dealer to repair.
Source: Galleon-X9-6-10K-RT_manual.pdf, p.28
Also applies to:Giant Elite 3P/3P 10K-40KVA
What it means
Firmware incompatibility — Fault code 01 shown on the display; the UPS has detected a fault condition: Firmware incompatibility.
Cause: Firmware incompatibility.
How to fix it
- 1Restart the unit.
- 2If the fault happens again, contact your installer or the repair centre.
Source: Giant-Elite-3P3P-manual.pdf, p.41
Also applies to:SCC-MPPT 300WSCC-MPPT 600WSCC-MPPT 850W
What it means
Battery wires are not connected well, battery defect, or charge controller defect — Fault code F1 shown on the display with the fault icon on: Battery wires are not connected well, battery defect, or charge controller defect..
Cause: Battery wires are not connected well. Battery defect. Charge controller defect.
How to fix it
- 1Check if battery wires are properly connected.
- 2Replace battery.
- 3If the charge controller is defective, replace the unit.
Source: SCC-MPPT_manual.pdf, p.6