02Fault

Voltronic inverter error 02 (F2)

Over temperature

Also displayed as F2 on some models.

Faultthe inverter cuts its output and the red LED stays solid until the fault is cleared.

The exact meaning depends on your model:

Axpert MAX II TWIN

InverterFault

Also applies to:Axpert MAX II TWIN 8KWAxpert MAX II TWIN 11KWAxpert MAX II TWIN 12KWAxpert MAX II Duplex 8KWAxpert MAX II Duplex 11KWAxpert MAX II 8KWAxpert MAX II 11KWAxpert KING II TWIN 6KW+15

What it means

Over temperatureFault code 02 shown on the display with the fault icon on: Over temperature.

Cause: Internal temperature of inverter component is over 100°C.

How to fix it

Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source: Axpert-MAXII-8K-TWIN-Off-grid-manual.pdf, p.47 · Axpert-MAXII-8K-TWIN-Off-grid-manual.pdf, p.55 · Axpert-MAXII-11K-TWIN-Off-grid-manual.pdf, p.47 · +25 more official manuals

Axpert MAX TWIN

InverterFault

Also applies to:Axpert MAX 8K TWIN PV11KAxpert MAX E TWIN 11KWAxpert MAX E 11K DuplexAxpert MAX 3.6KWAxpert MAX 6.5KWAxpert MAX 7.2KWAxpert MKS III TWIN 6KWAxpert MKS II 5KVA+17

What it means

Over temperatureFault code 02 shown on the display with the fault icon on: Over temperature.

Cause: Internal temperature of inverter component is over 100°C.

How to fix it

Return to repair center.

Source: Axpert-MAX-8K-TWIN-Off-grid-manual-20220121.pdf, p.39 · Axpert-MAX-8K-TWIN-Off-grid-manual-20220121.pdf, p.46 · Axpert-MAX-E-TWIN-11K-Off-grid-manual-20220121.pdf, p.40 · +23 more official manuals

Axpert VM II

InverterFault

Also applies to:Axpert VM II 1.2KVAAxpert VM II 2.5KVAAxpert VM II Plus 3KAxpert VM II 3KVA PF1Axpert VM II 5KVA PF1

What it means

Over temperature or NTC is not connected wellFault code 02 shown on the display with the fault icon on: Over temperature or NTC is not connected well..

Cause: Internal temperature of inverter component is over 100°C.

How to fix it

Return to repair center.

Source: Axpert-VM-II-1.2KVA-2.5KVA_Plus-3K_manual.pdf, p.29 · Axpert-VM-II-1.2KVA-2.5KVA_Plus-3K_manual.pdf, p.33 · Axpert-VM-II-PF1-USB-dry-contact-100A_manual.pdf, p.28 · +1 more official manuals

What it means

BUS voltage underFault code 02 shown on the display with the fault icon on: BUS voltage under.

Cause: BUS voltage under.

How to fix it

  1. Restart the unit.
  2. If the fault happens again, contact your installer or the repair centre.

Source: InfiniSolar-WP-LV-12KW-Premium-manual.pdf, p.52

InfiniSolar 10KW

InverterFault

Also applies to:InfiniSolar 15KWInfiniSolar Super 4KWInfiniSolar Plus 5KWInfiniSolar TX-PA 30KW

What it means

BUS voltage underFault code 02 shown on the display with the fault icon on: BUS voltage under.

Cause: PV or battery disconnect suddenly.

How to fix it

1. Restart the inverter 2. If the error message still remains, please contact your installer.

Source: InfiniSolar-10KW-manual-20191126.pdf, p.50 · InfiniSolar-15K-manual-20200313.pdf, p.51 · InfiniSolar-Super-4KW-manual.pdf, p.47 · +2 more official manuals

InfiniSolar E 5.5KW

InverterFault

What it means

DC bus voltage falls below the lower thresholdFault code 02 shown on the display with the fault icon on: DC bus voltage falls below the lower threshold.

Cause: DC bus voltage falls below the lower threshold.

How to fix it

  1. Disconnect AC circuit breaker first.
  2. Then, disconnect DC circuit breaker.
  3. Until LCD screen completely shuts down, turn on DC breaker first.
  4. It will show "No Utility" in LCD screen.
  5. Then, turn on AC breaker.
  6. After 300 seconds, the system will automatically connect to the grid.
  7. If the error message still remains, please contact your installer.
  8. The internal temperature is higher than specified temperature.
  9. Leave inverter to cool down to room temperature.
  10. If the error message still remains, please contact your installer.
  11. Check if the open circuit voltage of PV modules is higher than 500VDC.
  12. If PV open circuit voltage is less than 500VDC and the error message remains, pelase contact your installer.
  13. Turn off the inverter.
  14. Then, restart the inverter.
  15. If the error message still remains, please contact your installer.
  16. The ground voltage is too high.
  17. Please disconnect AC breaker first and then DC breaker.
  18. Check if grounding is connected properly after LCD screen.

Source: InfiniSolarE-5.5KW-manual.pdf, p.43

InfiniSolar 2KW/3KW

InverterFault

Also applies to:InfiniSolar 2KWInfiniSolar 3KW

What it means

DC bus voltage falls below the lower thresholdFault code 02 shown on the display with the fault icon on: DC bus voltage falls below the lower threshold.

Cause: DC bus voltage falls below the lower threshold.

How to fix it

  1. Disconnect AC circuit breaker first. Then, disconnect DC circuit breaker
  2. Until LCD screen completely shuts down, turn on DC breaker first. It will show "No Utility" in LCD screen. Then, turn on AC breaker. After 300 seconds, the system will automatically connect to the grid
  3. If the error message still remains, please contact your installer.

Source: InfiniSolar-2KW3KW-manual.pdf, p.46

DC Converter 3KW

InverterFault

What it means

Battery current is abnormalFault code 02 shown on the display with the fault icon on: Battery current is abnormal..

Cause: Battery current is abnormal.

How to fix it

  1. Restart the converter
  2. If the problem remains, please contact your installer.

Source: DC-converter-3KW-manual.pdf, p.20 · DC-converter-3KW-manual.pdf, p.21

ESS510

Energy storage systemFault

What it means

DC bus voltage falls below the lower thresholdFault code 02 shown on the display with the fault icon on: DC bus voltage falls below the lower threshold..

Cause: DC bus voltage falls below the lower threshold.

How to fix it

  1. Disconnect AC circuit breaker first.
  2. Then, disconnect DC circuit breaker.
  3. Until LCD screen completely shuts down, turn on DC breaker first.
  4. It will show "No Utility" in LCD screen.
  5. Then, turn on AC breaker.
  6. After 300 seconds, the system will automatically connect to the grid.
  7. If the error message still remains, please contact your installer.

Source: ESS510-manual.pdf, p.68

Also applies to:Galleon II 6KGalleon II 10KGalleon III 1KGalleon III 2KGalleon III 3KGiant Elite 1P/1P 6K-10KWinner Pro 1KVA-3KVAWinner Pro 6KVA+6

What it means

Bus overFault code 02 shown on the display; the UPS has detected a fault condition: Bus over.

Cause: Bus over.

How to fix it

  1. Restart the unit.
  2. If the fault happens again, contact your installer or the repair centre.

Source: GalleonII-6-10K-Tower-RT-manual.pdf, p.29 · Galleon-III-Tower-Rack-1-3K-manual.pdf, p.31 · Giant-Elite-1P-1P_manual.pdf, p.26 · +5 more official manuals

What it means

Over temperatureFault code 02 shown on the display; the UPS has detected a fault condition: Over temperature.

Cause: Internal temperature of UPS component is over 100°C.

How to fix it

Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source: GalleonOne-5KL-48V-manual.pdf, p.22 · GalleonOne-5KL-48V-manual.pdf, p.28

Also applies to:Galleon X9 6K RTGalleon X9 10K RT

What it means

Bus OverFault code 02 shown on the display; the UPS has detected a fault condition: Bus Over.

Cause: 1) DC bus voltage is too high because of mains input or load transient current. 2) The internal converter failed.

How to fix it

  1. Shut down and restart the system to see if it happens again
  2. Contact the dealer to repair.

Source: Galleon-X9-6-10K-RT_manual.pdf, p.28

Also applies to:Giant Elite 3P/3P 10K-40KVA

What it means

NO Boot LoaderFault code 02 shown on the display; the UPS has detected a fault condition: NO Boot Loader.

Cause: NO Boot Loader.

How to fix it

  1. Restart the unit.
  2. If the fault happens again, contact your installer or the repair centre.

Source: Giant-Elite-3P3P-manual.pdf, p.41

SCC-MPPT Solar Charge Controller

Charge controllerFault

Also applies to:SCC-MPPT 300WSCC-MPPT 600WSCC-MPPT 850W

What it means

OverloadFault code F2 shown on the display with the fault icon on: Overload..

Cause: Overload.

How to fix it

Remove excess loads.

Source: SCC-MPPT_manual.pdf, p.6

Frequently asked questions

What does error 02 mean on a Voltronic inverter?
It depends on the model — 49 devices use code 02. On the Axpert MAX II TWIN it means: Over temperature. The card for each model on this page gives its exact meaning and fix.
Is error 02 a fault or a warning?
02 is a fault code: the inverter cuts its output and the red LED stays solid until it is cleared.
How do I clear or fix error 02?
Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. The exact steps for each affected model are listed on this page.

Related error codes

Compiled from official Voltronic user manuals. Always consult your device manual and a qualified technician before performing repairs.