Fault code 01 shown on the display with the fault icon on: Fan is locked when inverter is off..
CauseFan fault.
Recommended fixReplace the fan.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
This is the complete fault table for the Voltronic Axpert VM III Inverter family — 25 codes shared by 3 model numbers, transcribed from the official manual. On Voltronic units, a fault code means the unit has cut its output and the red LED stays solid; a warning flashes the red LED while the unit keeps running.
Last checked against the official manuals on July 27, 2026.
Fault code 01 shown on the display with the fault icon on: Fan is locked when inverter is off..
CauseFan fault.
Recommended fixReplace the fan.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 02 shown on the display with the fault icon on: Over temperature.
CauseInternal temperature of inverter component is over 100°C.
Recommended fixReturn to repair center.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 03 shown on the display with the fault icon on: Battery voltage is too high.
CauseBattery is over-charged.
Recommended fixReturn to repair center.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 04 shown on the display with the fault icon on: Battery voltage is too low.
CauseBattery voltage is too low.
Recommended fixRestart the unit. If the fault happens again, contact your installer or the repair centre.
Source:Axpert-VM-III_manual-20200904.pdf· page 41
Fault code 05 shown on the display with the fault icon on: Output short circuited or over temperature is detected by internal converter components..
CauseOutput short circuited.
Recommended fixCheck if wiring is connected well and remove abnormal load.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 06 shown on the display with the fault icon on: Output voltage is too high..
CauseOutput abnormal (Inverter voltage below than 190Vac or is higher than 260Vac).
Recommended fix1. Reduce the connected load. 2. Return to repair center.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 07 shown on the display with the fault icon on: Overload time out.
CauseOverload error. The inverter is overload 110% and time is up.
Recommended fixReduce the connected load by switching off some equipment.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 08 shown on the display with the fault icon on: Bus voltage is too high.
CauseInternal components failed.
Recommended fixReturn to repair center.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 09 shown on the display with the fault icon on: Bus soft start failed.
CauseInternal components failed.
Recommended fixReturn to repair center.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 51 shown on the display with the fault icon on: Over current or surge.
CauseOver current or surge.
Recommended fixRestart the unit, if the error happens again, please return to repair center.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 52 shown on the display with the fault icon on: Bus voltage is too low.
CauseBus voltage is too low.
Recommended fixReduce the number of PV modules in series.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 53 shown on the display with the fault icon on: Inverter soft start failed.
CauseInternal components failed.
Recommended fixReturn to repair center.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 55 shown on the display with the fault icon on: Over DC voltage in AC output.
CauseOutput voltage is unbalanced.
Recommended fixReduce the number of PV modules in series.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 57 shown on the display with the fault icon on: Current sensor failed.
CauseInternal components failed.
Recommended fixReturn to repair center.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 58 shown on the display with the fault icon on: Output voltage is too low.
CauseOutput abnormal (Inverter voltage below than 190Vac or is higher than 260Vac).
Recommended fix1. Reduce the connected load. 2. Return to repair center.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Fault code 59 shown on the display with the fault icon on: PV voltage is over limitation.
CausePV input voltage is beyond the specification.
Recommended fixReduce the number of PV modules in series.
Source:Axpert-VM-III_manual-20200904.pdf· page 41Axpert-VM-III_manual-20200904.pdf· page 45
Warning code 01 flashing on the display: Fan is locked when inverter is on.. Audible alarm: beep three times every second.
CauseFan is locked when inverter is on.
Recommended fixReplace the fan.
Source:Axpert-VM-III_manual-20200904.pdf· page 41
Warning code 02 flashing on the display: Over temperature.
CauseOver temperature.
Recommended fixReturn to repair center.
Source:Axpert-VM-III_manual-20200904.pdf· page 41
Warning code 03 flashing on the display: Battery is over-charged. Audible alarm: beep once every second.
CauseBattery is over-charged.
Recommended fixReturn to repair center.
Source:Axpert-VM-III_manual-20200904.pdf· page 41
Warning code 04 flashing on the display: Low battery. Audible alarm: beep once every second.
CauseLow battery.
Recommended fixThe unit keeps operating. Clear the condition shown and the warning resets automatically; if it persists, contact your installer or the repair centre.
Source:Axpert-VM-III_manual-20200904.pdf· page 41
Warning code 07 flashing on the display: Overload. Audible alarm: beep once every 0.5 second.
CauseOverload.
Recommended fixReduce the connected load by switching off some equipment.
Source:Axpert-VM-III_manual-20200904.pdf· page 41
Warning code 10 flashing on the display: Output power derating. Audible alarm: beep twice every 3 seconds.
CauseOutput power derating.
Recommended fixThe unit keeps operating. Clear the condition shown and the warning resets automatically; if it persists, contact your installer or the repair centre.
Source:Axpert-VM-III_manual-20200904.pdf· page 41
Warning code 15 flashing on the display: PV energy is low.. Audible alarm: beep twice every 3 seconds.
CausePV energy is low.
Recommended fixThe unit keeps operating. Clear the condition shown and the warning resets automatically; if it persists, contact your installer or the repair centre.
Source:Axpert-VM-III_manual-20200904.pdf· page 41
Warning code 16 flashing on the display: High AC input (>280VAC) during BUS soft start.
CauseHigh AC input (>280VAC) during BUS soft start.
Recommended fixThe unit keeps operating. Clear the condition shown and the warning resets automatically; if it persists, contact your installer or the repair centre.
Source:Axpert-VM-III_manual-20200904.pdf· page 41
Warning code 32 flashing on the display: Communication failure between inverter and remote display panel.
CauseCommunication failure between inverter and remote display panel.
Recommended fixThe unit keeps operating. Clear the condition shown and the warning resets automatically; if it persists, contact your installer or the repair centre.
Source:Axpert-VM-III_manual-20200904.pdf· page 41
Send us the code on your screen and a Voltronic technician will reply with the exact steps for your unit. Support is free for life — a first diagnosis never needs a callout.
Compiled from official Voltronic user manuals. Always consult your device manual and a qualified technician before performing repairs.