Fault code 01 shown on the display; the UPS has detected a fault condition: Fan is locked when inverter is off..
CauseFan fault.
Recommended fixReplace the fan.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
This is the complete fault table for the Voltronic Galleon One 5KL 48V ups — all 36 codes from the official manual on one page. On this Voltronic device, a fault code means the unit has entered protection and stopped normal operation; a warning leaves it running. The exact indication (LED pattern or display code) is listed per code below.
Last checked against the official manuals on July 27, 2026.
Fault code 01 shown on the display; the UPS has detected a fault condition: Fan is locked when inverter is off..
CauseFan fault.
Recommended fixReplace the fan.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 02 shown on the display; the UPS has detected a fault condition: Over temperature.
CauseInternal temperature of UPS component is over 100°C.
Recommended fixCheck whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 03 shown on the display; the UPS has detected a fault condition: Battery voltage is too high.
CauseBattery is over-charged.
Recommended fixReturn to repair center.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 04 shown on the display; the UPS has detected a fault condition: Battery voltage is too low.
CauseBattery voltage is too low.
Recommended fixRestart the unit. If the fault happens again, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 22
Fault code 05 shown on the display; the UPS has detected a fault condition: Output short circuited or over temperature is detected by internal converter components..
CauseOutput short circuited.
Recommended fixCheck if wiring is connected well and remove abnormal load.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 06 shown on the display; the UPS has detected a fault condition: Output voltage is too high..
CauseOutput abnormal (Inverter voltage below than 190Vac or is higher than 260Vac).
Recommended fix1. Reduce the connected load. 2. Return to repair center.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 07 shown on the display; the UPS has detected a fault condition: Overload time out.
CauseOverload error. The UPS is overload 110% and time is up.
Recommended fixReduce the connected load by switching off some equipment.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 08 shown on the display; the UPS has detected a fault condition: Bus voltage is too high.
CauseInternal components failed.
Recommended fixReturn to repair center.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 09 shown on the display; the UPS has detected a fault condition: Bus soft start failed.
CauseInternal components failed.
Recommended fixReturn to repair center.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 50 shown on the display; the UPS has detected a fault condition: PFC over current.
CausePFC over current or surge.
Recommended fixRestart the unit, if the error happens again, please return to repair center.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 51 shown on the display; the UPS has detected a fault condition: OP over current.
CauseOP over current or surge.
Recommended fixIf the battery is connected well, please return to repair center.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 52 shown on the display; the UPS has detected a fault condition: Bus voltage is too low.
CauseBus voltage is too low.
Recommended fixIf the battery is connected well, please return to repair center.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 53 shown on the display; the UPS has detected a fault condition: Inverter soft start failed.
CauseInternal components failed.
Recommended fixReturn to repair center.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 55 shown on the display; the UPS has detected a fault condition: Over DC voltage in AC output.
CauseOutput voltage is unbalanced.
Recommended fixIf the battery is connected well, please return to repair center.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 56 shown on the display; the UPS has detected a fault condition: Battery is not connected.
CauseBattery is not connected well or fuse is burnt.
Recommended fixIf the battery is connected well, please return to repair center.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 57 shown on the display; the UPS has detected a fault condition: Current sensor failed.
CauseInternal components failed.
Recommended fixReturn to repair center.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 58 shown on the display; the UPS has detected a fault condition: Output voltage is too low.
CauseOutput abnormal (Inverter voltage below than 190Vac or is higher than 260Vac).
Recommended fix1. Reduce the connected load. 2. Return to repair center.
Source:GalleonOne-5KL-48V-manual.pdf· page 22GalleonOne-5KL-48V-manual.pdf· page 28
Fault code 60 shown on the display; the UPS has detected a fault condition: Power feedback protection.
CausePower feedback protection.
Recommended fixRestart the unit. If the fault happens again, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 41
Fault code 71 shown on the display; the UPS has detected a fault condition: Firmware version inconsistent.
CauseFirmware version inconsistent.
Recommended fixRestart the unit. If the fault happens again, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 41
Fault code 72 shown on the display; the UPS has detected a fault condition: Current sharing fault.
CauseCurrent sharing fault.
Recommended fixRestart the unit. If the fault happens again, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 41
Fault code 80 shown on the display; the UPS has detected a fault condition: CAN fault.
CauseCAN fault.
Recommended fixRestart the unit. If the fault happens again, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 41
Fault code 81 shown on the display; the UPS has detected a fault condition: Host loss.
CauseHost loss.
Recommended fixRestart the unit. If the fault happens again, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 41
Fault code 82 shown on the display; the UPS has detected a fault condition: Synchronization loss.
CauseSynchronization loss.
Recommended fixRestart the unit. If the fault happens again, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 41
Fault code 83 shown on the display; the UPS has detected a fault condition: Battery voltage detected different.
CauseBattery voltage detected different.
Recommended fixRestart the unit. If the fault happens again, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 41
Fault code 84 shown on the display; the UPS has detected a fault condition: AC input voltage and frequency detected different.
CauseAC input voltage and frequency detected different.
Recommended fixRestart the unit. If the fault happens again, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 41
Fault code 85 shown on the display; the UPS has detected a fault condition: AC output current unbalance.
CauseAC output current unbalance.
Recommended fixRestart the unit. If the fault happens again, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 41
Fault code 86 shown on the display; the UPS has detected a fault condition: AC output mode setting is different.
CauseAC output mode setting is different.
Recommended fixRestart the unit. If the fault happens again, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 41
Warning code 01 flashing on the display: Fan is locked when UPS is on.. Audible alarm: beep three times every second.
CauseFan is locked when UPS is on.
Recommended fixReplace the fan.
Source:GalleonOne-5KL-48V-manual.pdf· page 22
Warning code 02 flashing on the display: Over temperature.
CauseOver temperature.
Recommended fixCheck whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Source:GalleonOne-5KL-48V-manual.pdf· page 22
Warning code 03 flashing on the display: Battery is over-charged. Audible alarm: beep once every second.
CauseBattery is over-charged.
Recommended fixReturn to repair center.
Source:GalleonOne-5KL-48V-manual.pdf· page 22
Warning code 04 flashing on the display: Low battery. Audible alarm: beep once every second.
CauseLow battery.
Recommended fixThe unit keeps operating. Clear the condition shown and the warning resets automatically; if it persists, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 22
Warning code 07 flashing on the display: Overload. Audible alarm: beep once every 0.5 second.
CauseOverload.
Recommended fixReduce the connected load by switching off some equipment.
Source:GalleonOne-5KL-48V-manual.pdf· page 22
Warning code 10 flashing on the display: Output power derating. Audible alarm: beep twice every 3 seconds.
CauseOutput power derating.
Recommended fixThe unit keeps operating. Clear the condition shown and the warning resets automatically; if it persists, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 22
Warning code 12 flashing on the display: EPO activated.
CauseEPO activated.
Recommended fixThe unit keeps operating. Clear the condition shown and the warning resets automatically; if it persists, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 22
Warning code 13 flashing on the display: Manual Bypass activated.
CauseManual Bypass activated.
Recommended fixThe unit keeps operating. Clear the condition shown and the warning resets automatically; if it persists, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 22
Warning code 17 flashing on the display: Phase Lock failed.
CausePhase Lock failed.
Recommended fixThe unit keeps operating. Clear the condition shown and the warning resets automatically; if it persists, contact your installer or the repair centre.
Source:GalleonOne-5KL-48V-manual.pdf· page 22
Send us the code on your screen and a Voltronic technician will reply with the exact steps for your unit. Support is free for life — a first diagnosis never needs a callout.
Compiled from official Voltronic user manuals. Always consult your device manual and a qualified technician before performing repairs.