41Fault

Voltronic device error 41

Inv S Short

Faultthe unit enters fault protection and stops normal operation until the fault is cleared — how it is shown (LED pattern or display code) depends on the model.

The exact meaning depends on your model:

What it means

Inv S ShortFault code 41 shown on the display with the fault icon on: Inv S Short.

Cause: Output short circuited.

How to fix it

  1. Check if wiring is connected well and remove abnormal load
  2. If the error message still remains, please contact your installer.

Source: InfiniSolar-TX-PA_manual.pdf, p.51

Also applies to:Galleon II 6KGalleon II 10KGalleon III 1KGalleon III 2KGalleon III 3KGiant Elite 1P/1P 6K-10KWinner Pro 1KVA-3KVAWinner Pro 6KVA+6

What it means

Over temperatureFault code 41 shown on the display; the UPS has detected a fault condition: Over temperature.

Cause: Over temperature.

How to fix it

  1. Restart the unit.
  2. If the fault happens again, contact your installer or the repair centre.

Source: GalleonII-6-10K-Tower-RT-manual.pdf, p.29 · Galleon-III-Tower-Rack-1-3K-manual.pdf, p.31 · Giant-Elite-1P-1P_manual.pdf, p.26 · +5 more official manuals

Also applies to:Galleon X9 6K RTGalleon X9 10K RT

What it means

Over TempFault code 41 shown on the display; the UPS has detected a fault condition: Over Temp.

Cause: The internal temperature is too high and reach the fault level (shutdown): 1) Maybe the environment is hot. 2) Maybe the fan is blocked or failed. 3) Maybe ventilation is blocked by the wall or other goods. 4) Load is too heavy.

How to fix it

  1. Make sure the ambient temperature not over 40oC
  2. Make sure the fan is OK
  3. Make sure ventilation is well
  4. Remove some loads if possible.

Source: Galleon-X9-6-10K-RT_manual.pdf, p.29

Frequently asked questions

What does error 41 mean on a Voltronic device?
It depends on the model — 10 devices use code 41. On the InfiniSolar TX-PA 30KW it means: Inv S Short. The card for each model on this page gives its exact meaning and fix.
Is error 41 a fault or a warning?
41 is a fault code: the unit enters protection and stops normal operation until it is cleared.
How do I clear or fix error 41?
1. Check if wiring is connected well and remove abnormal load. The exact steps for each affected model are listed on this page.