W3FWarning

Voltronic device error W3F

Para Protect

Warninga protection warning — the unit keeps running, but deal with the cause before it escalates.

Also applies to:Galleon X9 6K RTGalleon X9 10K RT

What it means

Para ProtectWarning code 3F flashing on the display: Para Protect.

Cause: Parallel cable is still not connected well when restart after the parallel system is fault because of parallel communication failure. (When this warning appeared, the UPS could not start up because it is system protection for parallel system).

How to fix it

  1. If the system is still needed to be operated in parallel mode, please connect the parallel cable well. And, choose "Para Unlock" in control menu to remove the warning. Then, the UPS could start up
  2. If the UPSs in the system are separated to single UPS, please disconnect the output to other UPSs and choose "Para Unlock" in control menu to remove the warning. Then, the UPS could start up. NOTE: Be careful to check the UPS operation mode (parallel or single) and the connections. If the parallel cable is not connected in the parallel mode, the UPS may be damaged.

Source: Galleon-X9-6-10K-RT_manual.pdf, p.28

Frequently asked questions

What does error W3F mean on a Voltronic device?
W3F means: Para Protect. Parallel cable is still not connected well when restart after the parallel system is fault because of parallel communication failure. (When this warning appeared, the UPS could not start up because it is system protection for parallel system).
Is error W3F a fault or a warning?
W3F is a warning: the unit keeps running. Fix the underlying condition before it escalates.
How do I clear or fix error W3F?
1) If the system is still needed to be operated in parallel mode, please connect the parallel cable well. And, choose "Para Unlock" in control menu to remove the warning.