Voltronic Power Outdoor UPS

Voltronic Outdoor UPS

Discover Voltronic Power's Outdoor UPS with 120 VAC nominal voltage and user-programmable voltage range for reliable power protection.

  • Nominal Voltage: 120/230/240 VAC
  • Voltage Range: 88-300 VAC
  • Frequency Range: 50/60 Hz (Auto sensing)
AED 1,800incl. VAT

In stock

Voltronic Outdoor UPS features

Provide continuous power to critical

Provide continuous power to critical loads during blackout in rugged environment

Wide operating temperature range from

Wide operating temperature range from -40°C to 80°C suits for outdoor applications

Built-in boost and buck AVR

Built-in boost and buck AVR to regulate input voltage

Selectable transfer time for normal

Selectable transfer time for normal or generator modes

Provide RS-232, USB and SNMP

Provide RS-232, USB and SNMP intelligent port

Circuit breaker protection on AC

Circuit breaker protection on AC input, AC output and external battery input

User-adjustable charging current

Adjustable input threshold voltage

Provide programmable signals for dry

Provide programmable signals for dry contacts

Battery compensation optimizes battery lifecycle

About the Voltronic Outdoor UPS

Voltronic Power's Outdoor UPS is engineered to provide robust and reliable power protection in outdoor environments. With a nominal voltage of 120 VAC and a user-programmable voltage range of 88 to 152 VAC, this UPS ensures your equipment stays powered even in fluctuating conditions. Ideal for outdoor installations, this UPS is perfect for telecommunications, security systems, and remote monitoring equipment, ensuring uninterrupted power supply.

Specifications last updated 27 March 2026

Voltronic Outdoor UPS full specifications

Electrical

Nominal Voltage120 VAC / 230/240 VAC
Acceptable Voltage Range88 ~152 VAC user programmable. Default: 100 ~ 130VAC / 176 ~ 300VAC user programmable. Default: 200 ~ 260VAC
Frequency Range50 Hz/60 Hz (Auto sensing)
Voltage Regulation (Batt. Mode)120 VAC ± 5% / 230/240 VAC ± 5%
Output Frequency50Hz/60Hz ± 0.1%
THD (Batt. Mode)<3% @ Full resistive load
AC Mode Efficiency95%
AVR Mode Efficiency90%
Battery Mode Efficiency90%
Transfer Time (Normal Mode max.)12ms
Transfer Time (Generator Mode max.)25ms
WaveformPure sinewave
Nominal DC Voltage48VDC
Low DC Warning Voltage46VDC ± 0.4VDC @ no load
Battery TypeAGM
Charging Current2A/4A/6A/8A/10A (Adjustable)
Bypass ModeGreen LED on
No OutputGreen LED off
Warning with OutputYellow LED on
Fault without OutputRed LED on
CommunicationRS-232/USB and optional SNMP
Dry Contact Rating3A @ 125VAC / 3A @ 250VAC
EM ComplianceClass A FCC/CISPR [EN50091-2: 1995]
Surge ProtectionIEEE/ANSI C.62.41 & 2KV, L-N
Battery ModeGreen LED flashing

Mechanical

Dimension, D x W x H (mm)240 x 400 x 133
Net Weight (kg)13
Type of Mechanical ProtectionIP20

Environmental

Humidity5% to 95% Relative Humidity(Non-condensing)
Operating Temperature-40°C to 80°C / -40°C to 70°C
Noise Level< 48dB

Certifications

  • Class A FCC/CISPR
  • IEEE/ANSI C.62.41