Voltronic Power Galleon III 3P/3P 60KL

UPSModel VOLTRONIC-GALLEON-III-3P3P-60KL

Voltronic 60 kVA UPS Galleon III 3P/3P 60KL

Discover the Voltronic Power Galleon III 3P/3P 60KL Online UPS with 3 x 380/400/415 VAC output and ±1% voltage regulation.

  • Rated Output Power (VA): 60kVA
  • Rated Output Power (W): 60kW
  • Voltage: 3x 380-415 VAC (3P)
  • Voltage Range: 190-520 VAC (3P)
  • Power Factor: >= 0.99

Choose the Rated Output Power (VA)

What sets the VOLTRONIC-GALLEON-III-3P3P-60KL apart from the other 2 models in the family: Rated Output Power (VA) 60kVA VA; Rated Output Power (W) 60kW W; Battery Type 12V/9Ah; Charging Current (max.) 1A-18A(Adjustable); Charging Voltage 213-650V(N=16-20); Long-run Model Net Weight (kgs) 74; Weight (kg) N/A kg; Noise Level Less than 70 dB @ 1 Meter.

AED 75,000incl. VAT

In stock

  • Delivered within 3 business days, door to door, to every market we serve.
  • Dispatched the same business day for an order placed before 21:00 (Dubai time), or the next business day after.
  • Delivery charge: free
  • 2-year warranty

Voltronic 60 kVA UPS Galleon III 3P/3P 60KL features

  • True double-conversion

  • DSP technology guarantees high performance

  • Output power factor 1.0

  • Active power factor correction in

    Active power factor correction in all phases

  • 50Hz/60Hz frequency converter mode

  • ECO mode operation for energy

    ECO mode operation for energy saving (ECO)

  • Emergency power off function (EPO)

  • Generator compatible

  • SNMP+USB+RS-232 multiple communications

  • 3-stage extendable charging design for

    3-stage extendable charging design for optimized battery performance

  • Adjustable battery numbers for long-run

    Adjustable battery numbers for long-run model

  • Maintenance bypass available

  • Optional parallel operation

  • Optional isolation transformer offers full

    Optional isolation transformer offers full isolation and complete common mode noise rejection

About the Voltronic 60 kVA UPS Galleon III 3P/3P 60KL

The Voltronic 60 kVA UPS Galleon III 3P/3P 60KL is a Three Phase Online UPS with a rated power of 60 kW, making it a dependable choice for protecting critical loads from power interruptions. It accepts an operating voltage range of 190-520 VAC (3-phase) @ 50% load. Its output waveform is Pure Sine wave. The unit measures 815 x 300 x 1000 and weighs 74. It is rated to operate across 0-40°C, with a humidity tolerance of < 95% and non-condensing. The Voltronic 60 kVA UPS Galleon III 3P/3P 60KL is backed by a 2-year manufacturer warranty from Voltronic Power. Its published specifications also list Rated Output Power (VA) of 60kVA, Frequency Range (Batt. Mode) of 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz and Current Crest Ratio of 3:1 (max.).

Specifications last updated 23 July 2026

Voltronic 60 kVA UPS Galleon III 3P/3P 60KL full specifications

Electrical(22)

Rated Output Power (VA)60kVA
Rated Output Power (W)60kW
Nominal Voltage3 x 380/400/415 VAC (3Ph+N)
Voltage Range190-520 VAC (3-phase) @ 50% load; 305-478 VAC (3-phase) @ 100% load
Frequency Range46-54 Hz or 56-64 Hz
Power Factor≥ 0.99 @ 100% Load
Output Voltage3 x 380/400/415 VAC (3Ph+N)
AC Voltage Regulation± 1%
Frequency Range (Batt. Mode)50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio3:1 (max.)
Harmonic Distortion≤ 2% THD (Linear Load) ; ≤ 5% THD (Non-linear Load)
Transfer Time0 ms
Waveform (Batt. Mode)Pure Sine wave
AC Mode95.5%
ECO Mode98.5%
Battery Type12V/9Ah
Numbers(16+16)pcs x 2 strings
Charging Current (max.)1A-18A(Adjustable)
Charging Voltage213-650V(N=16-20)
Smart RS-232 / USBSupports Windows® Family, Linux and MAC
Optional SNMPPower management from SNMP manager and web browser
Battery Mode94.5%

Mechanical(5)

Dimension, DxWxH (mm)815 x 300 x 1000
Weight (kg)N/A
Long-run Model Dimension, DxWxH (mm)815 x 300 x 1000
Long-run Model Net Weight (kgs)74
Weight74 kg

Environmental(3)

Operation Temperature0-40°C
Humidity< 95% and non-condensing
Noise LevelLess than 70 dB @ 1 Meter

Downloads & support

Frequently Asked Questions

What is the rated power of the Voltronic 60 kVA UPS Galleon III 3P/3P 60KL?

The Voltronic 60 kVA UPS Galleon III 3P/3P 60KL has a rated power of 60 kW.

What voltage does the Voltronic 60 kVA UPS Galleon III 3P/3P 60KL operate on?

The Voltronic 60 kVA UPS Galleon III 3P/3P 60KL has a nominal voltage of 3 x 380/400/415 VAC (3Ph+N) and an operating voltage range of 190-520 VAC (3-phase) @ 50% load.

What are the physical dimensions and weight of the Voltronic 60 kVA UPS Galleon III 3P/3P 60KL?

The Voltronic 60 kVA UPS Galleon III 3P/3P 60KL measures 815 x 300 x 1000 and weighs 74.

What is the operating temperature range of the Voltronic 60 kVA UPS Galleon III 3P/3P 60KL?

The Voltronic 60 kVA UPS Galleon III 3P/3P 60KL operates across 0-40°C and a humidity range of < 95% and non-condensing.

What is the maximum charge current of the Voltronic 60 kVA UPS Galleon III 3P/3P 60KL?

The Voltronic 60 kVA UPS Galleon III 3P/3P 60KL has a maximum charge current of 1A-18A(Adjustable).

What output waveform does the Voltronic 60 kVA UPS Galleon III 3P/3P 60KL produce?

The Voltronic 60 kVA UPS Galleon III 3P/3P 60KL produces a Pure Sine wave output waveform.

How does the Voltronic 60 kVA UPS Galleon III 3P/3P 60KL regulate voltage?

The Voltronic 60 kVA UPS Galleon III 3P/3P 60KL provides a voltage regulation of ± 1%.

How loud is the Voltronic 60 kVA UPS Galleon III 3P/3P 60KL during operation?

The Voltronic 60 kVA UPS Galleon III 3P/3P 60KL has a noise level of Less than 70 dB @ 1 Meter during operation.

What is the power quality of the Voltronic 60 kVA UPS Galleon III 3P/3P 60KL?

The Voltronic 60 kVA UPS Galleon III 3P/3P 60KL has a power factor of ≥ 0.99 @ 100% Load and a harmonic distortion of ≤ 2% THD (Linear Load).

What warranty coverage is available for the Voltronic 60 kVA UPS Galleon III 3P/3P 60KL?

The Voltronic 60 kVA UPS Galleon III 3P/3P 60KL is backed by a 2-year manufacturer warranty from Voltronic Power.

Customer reviews