Voltronic Power Three-Phase Online UPS GALLEON-III-3P3P-30K/40K/60KL
Discover the Voltronic Power Galleon III 3P/3P 30K Online UPS with 3 x 380/400/415 VAC output and ±1% voltage regulation.
Models and prices
- VOLTRONIC-GALLEON-III-3P3P-30KAED 75,000incl. VAT
- VOLTRONIC-GALLEON-III-3P3P-40KAED 75,000incl. VAT
- VOLTRONIC-GALLEON-III-3P3P-60KLAED 75,000incl. VAT
Technical Specifications
| Parameter | VOLTRONIC-GALLEON-III-3P3P-30K | VOLTRONIC-GALLEON-III-3P3P-40K | VOLTRONIC-GALLEON-III-3P3P-60KL |
|---|---|---|---|
| Additional Specifications | |||
| Rated Output Power (VA) | 30kVA | 40kVA | 60kVA |
| Rated Output Power (W) | 30kW | 40kW | 60kW |
| Input | |||
| Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) | ||
| Voltage Range | 190-520 VAC (3-phase) @ 50% load; 305-478 VAC (3-phase) @ 100% load | ||
| Frequency Range | 46-54 Hz or 56-64 Hz | ||
| Power Factor | ≥ 0.99 @ 100% Load | ||
| Output | |||
| Output Voltage | 3 x 380/400/415 VAC (3Ph+N) | ||
| AC Voltage Regulation | ± 1% | ||
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | ||
| Current Crest Ratio | 3:1 (max.) | ||
| Harmonic Distortion | ≤ 2% THD (Linear Load) ; ≤ 5% THD (Non-linear Load) | ||
| Transfer Time | 0 ms | ||
| Waveform (Batt. Mode) | Pure Sine wave | ||
| Efficiency | |||
| AC Mode | 95.5% | ||
| ECO Mode | 98.5% | ||
| Battery Mode | 94.5% | ||
| Electrical Data | |||
| Battery Type | 12V/7Ah | 12V/9Ah | 12V/9Ah |
| Charging Current (max.) | 2A (Default) | 1A-12A(Adjustable) | 1A-18A(Adjustable) |
| Charging Voltage | 218 VDC | 213-650V(N=16-20) | 213-650V(N=16-20) |
| Battery | |||
| Numbers | (16+16)pcs x 2 strings | ||
| Communication | |||
| Smart RS-232 / USB | Supports Windows® Family, Linux and MAC | ||
| Optional SNMP | Power management from SNMP manager and web browser | ||
| Physical | |||
| Dimension, DxWxH (mm) | 815 x 300 x 1000 | ||
| Long-run Model Dimension, DxWxH (mm) | 815 x 300 x 1000 | ||
| Mechanical Data | |||
| Net Weight (kgs) | 207 | 233 | — |
| Long-run Model Net Weight (kgs) | 55 | 56 | 74 |
| Weight | 207 kg | 233 kg | 74 kg |
| Operating Conditions | |||
| Operation Temperature | 0-40°C | ||
| Humidity | < 95% and non-condensing | ||
| Noise Level | Less than 65 dB @ 1 Meter | Less than 70 dB @ 1 Meter | Less than 70 dB @ 1 Meter |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in the UAE
| Market | UAE |
|---|---|
| Grid authority / regulator | DEWA, ADDC, SEWA |
| Quotation currency | AED |
| Support hours timezone | Asia/Dubai |
| Main cities | Dubai, Abu Dhabi, Sharjah, Ajman, Ras Al Khaimah |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in the UAE that rests with the local authorities (DEWA, ADDC, SEWA). Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- True double-conversion
- DSP technology guarantees high performance
- Output power factor 1.0
- Active power factor correction in: Active power factor correction in all phases
- 50Hz/60Hz frequency converter mode
- ECO mode operation for energy: ECO mode operation for energy saving (ECO)
- Emergency power off function (EPO)
- Generator compatible
- SNMP+USB+RS-232 multiple communications
- 3-stage extendable charging design for: 3-stage extendable charging design for optimized battery performance
- Adjustable battery numbers for long-run: Adjustable battery numbers for long-run model
- Maintenance bypass available
Frequently Asked Questions
What is the rated power of the Voltronic 30 kVA UPS Galleon III 3P/3P 30K?
The Voltronic 30 kVA UPS Galleon III 3P/3P 30K has a rated power of 30 kW.
What voltage does the Voltronic 30 kVA UPS Galleon III 3P/3P 30K operate on?
The Voltronic 30 kVA UPS Galleon III 3P/3P 30K has a nominal voltage of 3 x 380/400/415 VAC (3Ph+N) and an operating voltage range of 190-520 VAC (3-phase) @ 50% load.
What are the physical dimensions and weight of the Voltronic 30 kVA UPS Galleon III 3P/3P 30K?
The Voltronic 30 kVA UPS Galleon III 3P/3P 30K measures 815 x 300 x 1000 and weighs 207.
What is the operating temperature range of the Voltronic 30 kVA UPS Galleon III 3P/3P 30K?
The Voltronic 30 kVA UPS Galleon III 3P/3P 30K operates across 0-40°C and a humidity range of < 95% and non-condensing.
What is the maximum charge current of the Voltronic 30 kVA UPS Galleon III 3P/3P 30K?
The Voltronic 30 kVA UPS Galleon III 3P/3P 30K has a maximum charge current of 2A (Default).
What output waveform does the Voltronic 30 kVA UPS Galleon III 3P/3P 30K produce?
The Voltronic 30 kVA UPS Galleon III 3P/3P 30K produces a Pure Sine wave output waveform.
How does the Voltronic 30 kVA UPS Galleon III 3P/3P 30K regulate voltage?
The Voltronic 30 kVA UPS Galleon III 3P/3P 30K provides a voltage regulation of ± 1%.
How loud is the Voltronic 30 kVA UPS Galleon III 3P/3P 30K during operation?
The Voltronic 30 kVA UPS Galleon III 3P/3P 30K has a noise level of Less than 65 dB @ 1 Meter during operation.
What is the power quality of the Voltronic 30 kVA UPS Galleon III 3P/3P 30K?
The Voltronic 30 kVA UPS Galleon III 3P/3P 30K has a power factor of ≥ 0.99 @ 100% Load and a harmonic distortion of ≤ 2% THD (Linear Load).
What warranty coverage is available for the Voltronic 30 kVA UPS Galleon III 3P/3P 30K?
The Voltronic 30 kVA UPS Galleon III 3P/3P 30K is backed by a 2-year manufacturer warranty from Voltronic Power.