| Protection | BMS |
|---|---|
| Standard Charge Method | 0.2C CC (Constant Current) charge to FC, CV (Constant Voltage) charge till charge current decline to <0.05C |
| Inner Resistance | <20ΜΩ |
| Communication | RS485 (RJ45), extension port (RJ11) |
| Certifications | UN38.3, IEC 62619, EN 61000-6-3 EN 61000-6-1, UKCA |
| Capacity (Wh) | 5120 Wh |
| Nominal Voltage | 51.2 VDC |
| Typical Capacity(Ah) | 100 Ah |
| Full Charge Voltage (FC) | 56 V ± 0.1 V |
| Full Discharge Voltage (FD) | 42 V |
| Max. Continuous Discharge Current | 150 A |
| Max. Peak Discharge Current | 192 A at 1min |
| Max. Charge Voltage | 56 V ± 0.1 V |
| Max. Charge Current | 100 A (Default 30A) |
| Dimension (D x W x H) mm | 185 x 540 x 420 |
|---|---|
| Dimension with stand feet | 185 x 540 x 530 |
| Net Weight (kg) | 48 |
| Operation Temperature | Charge: 0°C~50°C Discharge: 0°C~50°C |
|---|---|
| Storage Temperature | -20ºC ~ 60 °C 20°C±5°C is the recommended storage temperature |








Essential UPS battery maintenance tips. Temperature control, testing schedules, replacement indicators, and how to extend battery life in hot climates.
Read: How to Maintain UPS Batteries for Maximum Lifespan →Compare lithium-ion (LiFePO4) and lead-acid (VRLA) UPS batteries. Lifespan, cost, weight, heat tolerance, and total cost of ownership analysis.
Read: Lead-Acid vs Lithium-Ion UPS Batteries: Cost, Lifespan & TCO Compared →5120 Wh (100 Ah). That is the figure to divide your evening load into; how long it actually lasts depends on what you switch on, so send us the appliance list and we will work it through against this number rather than quote you an hour count.
The LIO II-4810 works with a 51.2 VDC bank. It charges at up to 100 A (Default 30A), and that current — not the bank's capacity — is what the cabling and the fuse between bank and unit have to be sized for.
Up to 150 A continuous. An inverter pulling more than that on a motor start will trip the pack's protection rather than damage it, so match the inverter to this figure.