Voltronic Power UPS Datasheet — VOLTRONIC-VICTOR-1U-6K-UPS
Discover the Victor 1U 6K UPS by Voltronic Power with 208-240VAC output and precise voltage regulation of ±1%.
SKU: VOLTRONIC-VICTOR-1U-6K-UPS | Last Updated: 2026-03-27
⚡Electrical Specifications
| Nominal Voltage | 208/220/230/240VAC |
| Voltage Range | 110-300VAC ± 3% @ 50% load; 176-300VAC ± 3% @ 100% load |
| Frequency Range | 46-54Hz; 56-64Hz |
| Power Factor | ≥ 0.99 @ nominal voltage (100% load) |
| THDi | ≤ 4% @ 100% load |
| Output Voltage | 208/220/230/240VAC |
| Voltage Regulation | ± 1% |
| Frequency Range (Synchronized Range) | 46-54 Hz or 56-64 Hz |
| Frequency Range (Batt. Mode) | 50 Hz or 60Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1max |
| Harmonic Distortion | ≤ 2 % THD (Linear Load) / ≤ 4% THD (Non-linear Load) |
| Transfer Time | 0 ms |
| Waveform (Batt. Mode) | Pure Sinewave |
| Overload | AC Mode 100% ≤ load ≤ 105% Warning only; 105%< load ≤ 125%: 1min; >125%: 1 sec |
| AC Mode | 95% (max.) |
| Charging Current | 1A, 2A, 4A (default), 6A |
| Charging Voltage | 219 VDC ± 1% |
| Battery Connector | 2 Poles (50A max.) |
| LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
| Communication | USB, Communication Slot |
| Battery Mode | 93% (max.) |
| Emergency Power Off (EPO) | YES |
🔧Mechanical Specifications
| Dimension, D x W x H (mm) | 520 x 438 x 44 |
| Net Weight (kgs) | 9.8 |
🌡️Environmental Specifications
| Humidity | 0-95% RH @ 0-40°C (non-condensing) |
| Altitude | 0-2000 meters without derating; 2000-3000 meters derating 1% every 100meters; >3000 meters: not working |
| Noise Level | Less than 55dBA @ 1 Meter |
📏Dimensions
Width438
Height44
Depth520
Weight9.8