⚡Electrical Specifications
| Nominal Voltage | 120 VAC / 230/240 VAC |
| Acceptable Voltage Range | 88 ~152 VAC user programmable. Default: 100 ~ 130VAC / 176 ~ 300VAC user programmable. Default: 200 ~ 260VAC |
| Frequency Range | 50 Hz/60 Hz (Auto sensing) |
| Voltage Regulation (Batt. Mode) | 120 VAC ± 5% / 230/240 VAC ± 5% |
| Output Frequency | 50Hz/60Hz ± 0.1% |
| THD (Batt. Mode) | <3% @ Full resistive load |
| AC Mode Efficiency | 95% |
| AVR Mode Efficiency | 90% |
| Battery Mode Efficiency | 90% |
| Transfer Time (Normal Mode max.) | 12ms |
| Transfer Time (Generator Mode max.) | 25ms |
| Waveform | Pure sinewave |
| Nominal DC Voltage | 48VDC |
| Low DC Warning Voltage | 46VDC ± 0.4VDC @ no load |
| Battery Type | AGM |
| Charging Current | 2A/4A/6A/8A/10A (Adjustable) |
| Bypass Mode | Green LED on |
| No Output | Green LED off |
| Warning with Output | Yellow LED on |
| Fault without Output | Red LED on |
| Communication | RS-232/USB and optional SNMP |
| Dry Contact Rating | 3A @ 125VAC / 3A @ 250VAC |
| EM Compliance | Class A FCC/CISPR [EN50091-2: 1995] |
| Surge Protection | IEEE/ANSI C.62.41 & 2KV, L-N |
| Battery Mode | Green LED flashing |
🔧Mechanical Specifications
| Dimension, D x W x H (mm) | 240 x 400 x 133 |
| Net Weight (kg) | 13 |
| Type of Mechanical Protection | IP20 |
🌡️Environmental Specifications
| Humidity | 5% to 95% Relative Humidity(Non-condensing) |
| Operating Temperature | -40°C to 80°C / -40°C to 70°C |
| Noise Level | < 48dB |