Voltronic Power Outdoor UPS

Voltronic Power UPS Datasheet — VOLTRONIC-OUTDOOR-UPS

Discover Voltronic Power's Outdoor UPS with 120 VAC nominal voltage and user-programmable voltage range for reliable power protection.

SKU: VOLTRONIC-OUTDOOR-UPS | Last Updated: 2026-03-27

⚡Electrical Specifications

Nominal Voltage120 VAC / 230/240 VAC
Acceptable Voltage Range88 ~152 VAC user programmable. Default: 100 ~ 130VAC / 176 ~ 300VAC user programmable. Default: 200 ~ 260VAC
Frequency Range50 Hz/60 Hz (Auto sensing)
Voltage Regulation (Batt. Mode)120 VAC ± 5% / 230/240 VAC ± 5%
Output Frequency50Hz/60Hz ± 0.1%
THD (Batt. Mode)<3% @ Full resistive load
AC Mode Efficiency95%
AVR Mode Efficiency90%
Battery Mode Efficiency90%
Transfer Time (Normal Mode max.)12ms
Transfer Time (Generator Mode max.)25ms
WaveformPure sinewave
Nominal DC Voltage48VDC
Low DC Warning Voltage46VDC ± 0.4VDC @ no load
Battery TypeAGM
Charging Current2A/4A/6A/8A/10A (Adjustable)
Bypass ModeGreen LED on
No OutputGreen LED off
Warning with OutputYellow LED on
Fault without OutputRed LED on
CommunicationRS-232/USB and optional SNMP
Dry Contact Rating3A @ 125VAC / 3A @ 250VAC
EM ComplianceClass A FCC/CISPR [EN50091-2: 1995]
Surge ProtectionIEEE/ANSI C.62.41 & 2KV, L-N
Battery ModeGreen LED flashing

🔧Mechanical Specifications

Dimension, D x W x H (mm)240 x 400 x 133
Net Weight (kg)13
Type of Mechanical ProtectionIP20

🌡️Environmental Specifications

Humidity5% to 95% Relative Humidity(Non-condensing)
Operating Temperature-40°C to 80°C / -40°C to 70°C
Noise Level< 48dB

📏Dimensions

Width400
Height133
Depth240
Weight13

✅Certifications

Class A FCC/CISPRIEEE/ANSI C.62.41