Voltronic Power Giant II 3P/3P

Voltronic Power UPS Datasheet — VOLTRONIC-GIANT-II-3P-3P

Discover the Voltronic Power Giant II 3P/3P UPS with 6 pulse rectifier and 380VAC/400VAC/415VAC nominal voltage for reliable power solutions.

SKU: VOLTRONIC-GIANT-II-3P-3P | Last Updated: 2026-03-27

⚡Electrical Specifications

Rectifier Type6 pulse / 6 pulse / 6 pulse / 6 pulse / 6 pulse / 6 pulse / 12 pulse / 12 pulse / 12 pulse / 12 pulse
Nominal Voltage380VAC/400VAC/415VAC
Acceptable Voltage Range304VAC – 456VAC
Frequency50Hz ± 10%
TVSS40kA (optional)
Input Voltage Range285VAC – 475VAC
Battery Voltage384 VDC (adjustable)
Cold StartYes
Power Factor0.9, customized up to 1.0
Nominal Output Voltage380VAC/400VAC/415VAC
Output Voltage Regulation±1%
Overload Capability110% continuous running; 125% for 10 min; >150% for 1 min
Dry Contacts5 outputs and 4 inputs
Optional SNMPPower management from SNMP manager and web browser
SafetyIEC62040-1:2017
Modbus RS-232/RS-485Supports Windows® family, Linux and MAC

🔧Mechanical Specifications

IP ProtectionIP31 (default), IP42 (optional)
Dimensions (DxWxH) mm656 x 405 x 817 / 656 x 405 x 941 / 818 x 432 x 1159 / 971 x 554 x 1290 / 971 x 635 x 1326 / 1051 x 705 x 1646 / 1051 x 705 x 1646 / 1051 x 705 x 1646 / 1051 x 705 x 1646 / 1051 x 705 x 1646
Net Weight (Kgs)120 / 145 / 193 / 278 / 365 / 471 / 573 / 650 / 735 / 790
Weight120 / 145 / 193 / 278 / 365 / 471 / 573 / 650 / 735 / 790

🌡️Environmental Specifications

Operating Temperature0 – 50°C
Storage Temperature-25°C – 55°C
Humidity0–95% (non-condensing)
Altitude1000m

📏Dimensions

Width405
Height817
Depth656
Weight120 / 145 / 193 / 278 / 365 / 471 / 573 / 650 / 735 / 790

✅Certifications

IEC62040-1:2017