Voltronic Power Galleon III 3P/3P 60KL

Voltronic Power UPS Datasheet — VOLTRONIC-GALLEON-III-3P3P-60KL

Discover the Voltronic Power Galleon III 3P/3P 60KL Online UPS with 3 x 380/400/415 VAC output and ±1% voltage regulation.

SKU: VOLTRONIC-GALLEON-III-3P3P-60KL | Last Updated: 2026-07-23

⚡Electrical Specifications

Rated Output Power (VA)60kVA
Rated Output Power (W)60kW
Nominal Voltage3 x 380/400/415 VAC (3Ph+N)
Voltage Range190-520 VAC (3-phase) @ 50% load; 305-478 VAC (3-phase) @ 100% load
Frequency Range46-54 Hz or 56-64 Hz
Power Factor≥ 0.99 @ 100% Load
Output Voltage3 x 380/400/415 VAC (3Ph+N)
AC Voltage Regulation± 1%
Frequency Range (Batt. Mode)50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio3:1 (max.)
Harmonic Distortion≤ 2% THD (Linear Load) ; ≤ 5% THD (Non-linear Load)
Transfer Time0 ms
Waveform (Batt. Mode)Pure Sine wave
AC Mode95.5%
ECO Mode98.5%
Battery Type12V/9Ah
Numbers(16+16)pcs x 2 strings
Charging Current (max.)1A-18A(Adjustable)
Charging Voltage213-650V(N=16-20)
Smart RS-232 / USBSupports Windows® Family, Linux and MAC
Optional SNMPPower management from SNMP manager and web browser
Battery Mode94.5%

🔧Mechanical Specifications

Dimension, DxWxH (mm)815 x 300 x 1000
Weight (kg)N/A
Long-run Model Dimension, DxWxH (mm)815 x 300 x 1000
Long-run Model Net Weight (kgs)74
Weight74 kg

🌡️Environmental Specifications

Operation Temperature0-40°C
Humidity< 95% and non-condensing
Noise LevelLess than 70 dB @ 1 Meter

📏Dimensions

Width300
Height1000
Depth815
Weight55 / 56 / 74