Voltronic Power Galleon III 3P/3P 30K~60K Rack

Voltronic Power UPS Datasheet — VOLTRONIC-GALLEON-III-30K-60K

Discover the Voltronic Power Galleon III 3P/3P 30K~60K Rack with 3x 380/400/415 VAC nominal voltage and precise AC voltage regulation.

SKU: VOLTRONIC-GALLEON-III-30K-60K | Last Updated: 2026-03-27

⚡Electrical Specifications

Nominal Voltage3x 380/400/415 VAC (3Ph+N)
Voltage Range190-520 VAC (3-phase) @ 50% load, 305-478 VAC (3-phase) @ 100% load
Frequency46-54 Hz or 56-64 Hz
Power Factor≥ 0.99 @ 100% load
Output Voltage3x 380/400/415 VAC (3Ph+N)
AC Voltage Regulation (Batt. Mode)± 1%
Frequency Range (Synchronized Range)46-54 Hz or 56-64 Hz
Frequency Range (Batt. Mode)50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio3:1 (max.)
Harmonic Distortion≤ 2 % THD (Linear Load); ≤ 5 % THD (Non-linear Load)
Transfer Time AC mode to Battery mode0 ms
Transfer Time Inverter to Bypass0 ms
Waveform (Batt. Mode)Pure Sinewave
Overload100-110% for 60 min, 110-125% for 10 min, 125%-150% for 1 min; >150% immediately
AC Mode95.5%
ECO Mode98.5%
Battery TypeDepending on the applications
Battery Numbers±16 ~20 (Adjustable)
Charging Current (max.)1A~12A (Adjustable) / 1A~12A (Adjustable) / 1A~18A (Adjustable)
Charging Voltage+/-(13.65V x N (N=16~20))
Smart RS-232/USBSupports Windows® family, Linux and MAC
Optional SNMPPower management from SNMP manager and web browser
Battery Mode94.5%

🔧Mechanical Specifications

Dimension, D x W x H (mm)680 x 438 x 133 [3U] / 680 x 438 x 133 [3U] / 797 x 438 x 176 [4U]
Net Weight (Kgs)32 / 34 / 45
Weight32 / 34 / 45

🌡️Environmental Specifications

Operating Temperature0-40°C
Operating Humidity< 95 % and non-condensing
Noise LevelLess than 65dB @ 1 Meter / Less than 65dB @ 1 Meter / Less than 70dB @ 1 Meter

📏Dimensions

Width438
Height133
Depth680
Weight32 / 34 / 45