Voltronic Power Compact 1U

Voltronic Power UPS Datasheet — VOLTRONIC-COMPACT-1U

Discover Voltronic Power's Compact 1U UPS with voltage options of 110/120 or 220/230/240 VAC and precise voltage regulation of ±1%.

SKU: VOLTRONIC-COMPACT-1U | Last Updated: 2026-03-27

⚡Electrical Specifications

Voltage110/120 VAC or 220/230/240 VAC / 220/230/240 VAC / 110/120 VAC or 220/230/240 VAC / 220/230/240 VAC / 220/230/240 VAC / 220/230/240 VAC
Voltage Range55-150 VAC or 110-300 VAC @ 50% load, 80-150 VAC or 160-300 VAC @ 100% load / 110-300 VAC @ 50% load, 160-300 VAC @ 100% load / 55-150 VAC or 110-300 VAC @ 50% load, 80-150 VAC or 160-300 VAC @ 100% load / 110-300 VAC @ 50% load, 160-300 VAC @ 100% load / 110-300 VAC @ 50% load, 160-300 VAC @ 100% load / 110-300 VAC @ 50% load, 160-300 VAC @ 100% load
Frequency Range40Hz ~ 70Hz
Power Factor>= 0.99 @ nominal voltage (100% load)
Output Voltage110/120 VAC or 220/230/240 VAC / 220/230/240 VAC / 110/120 VAC or 220/230/240 VAC / 220/230/240 VAC / 220/230/240 VAC / 220/230/240 VAC
Voltage Regulation± 1%
Frequency Range (Synchronized Range)57 ~ 63 Hz or 47 ~ 53 Hz
Frequency Range (Batt. Mode)60 Hz or 50 Hz ± 0.3 Hz
Current Crest Ratio5:1 (110/120 VAC), 3:1 (220/230/240 VAC) / 3:1 / 5:1 (110/120 VAC), 3:1 (220/230/240 VAC) / 3:1 / 3:1 / 3:1
Harmonic Distortion≤ 3% THD (Linear Load); ≤ 5% THD (Non-linear Load)
Transfer Time0 ms
Time (Inverter to Bypass)4 ms (Typical)
Waveform (Batt. Mode)Pure Sinewave
AC Mode86% / 90% / 92% / 93% / 94% / 94%
ECO Mode96% / 96% / 96% / 96% / 96% / 96%
Battery Mode83% / 90% / 90% / 91% / 91% / 91%
Battery TypeLithium-ion battery / Sealed Lead-acid battery / Lithium-ion battery or Sealed Lead-acid battery / Lithium-ion battery / Lithium-ion battery / Lithium-ion battery
Battery Voltage25.6 VDC / 24 VDC / 48 VDC / 38.4 VDC / 48VDC / 48VDC
Battery Spec & Numbers25.6V/8Ah x 1 / 6V/9Ah x 4 / Depending on external battery capacity / 38.4 V/6Ah x 1 / 48V/5Ah x 1 (additional battery pack expandable) / Depending on external battery capacity
Typical Recharge Time6 hours recover to 90% capacity / 9 hours recover to 90% capacity / 4 hours recover to 90% capacity / 3.5 hours recover to 90% capacity / 2 hours recover to 90% capacity / 2 hours recover to 90% capacity
Charging Current1A / 1.5A / 1.5A / 2.5A/5A/7.5A (adjustable via BMS) / 2.5A/5A/7.5A (adjustable via BMS) / 2.5A/5A/7.5A (adjustable via BMS)
LEDAC mode, Battery mode and fault indicators
AlarmBattery Mode: Sounding every 4 seconds / Low Battery: Sounding every second / Overload: Sounding twice every second / Fault: Continuously sounding / Fault: Continuously sounding / Fault: Continuously sounding
USB or RS-232Supports Windows® Family, Linux and MAC
Optional SNMPPower management from SNMP manager and web browser
Dry ContactSignal for AC Power Normal, Battery OK and Fault Alarm

🔧Mechanical Specifications

Dimension (DxWxH)(mm)477 x 438 x 44 / 300 x 438 x 44 / 509 x 438 x 44 / 583 x 438 x 44 / 580 x 438 x 44 / 580 x 438 x 44
Net Weight (kgs)12.4 / 12.6 / 12.6 / 12.4 / 18 / 12.4
Weight12.4 / 12.6 / 12.6 / 12.4 / 18 / 12.4

🌡️Environmental Specifications

Humidity20-90 % RH @ 0- 50°C (non-condensing)
Noise LevelLess than 50dBA @ 1 Meter

📏Dimensions

Width438
Height44
Depth477