Voltronic Power Three-Phase Online UPS GALLEON-III-33-31-11-10KL-20KL-RT
Discover the Voltronic Power Galleon III 33/31/11 10KL-20KL RT UPS with 3-phase 380/400/415VAC and precise voltage regulation for reliable power.
Models and prices
- VOLTRONIC-GALLEON-III-33-31-11-10KL-20KL-RTAED 30,000incl. VAT
Technical Specifications
| Parameter | VOLTRONIC-GALLEON-III-33-31-11-10KL-20KL-RT |
|---|---|
| Input | |
| Nominal Voltage | 3 x 380/400/415VAC (3Ph+N) or 220/230/240VAC (1Ph+N) |
| Voltage Range | 190-520 VAC (3-phase) @ 50% load; 305-478 VAC (3-phase) @ 100% load |
| Frequency Range | 46-54 Hz or 56-64 Hz |
| Power Factor | >= 0.99 @ 100% load |
| Output | |
| Output Voltage | 3 x 380/400/415VAC (3Ph+N) or 220/230/240VAC (1Ph+N) |
| AC Voltage Regulation (Batt. Mode) | ± 1% |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≤ 2 % THD (Linear Load) ; ≤ 5 % THD (Non-linear Load) |
| Transfer Time | 0 ms |
| Waveform (Batt. Mode) | Pure Sine Wave |
| Electrical Data | |
| AC Mode | 95.5% / 96% / 96% |
| Battery Mode | 94.5% / 95.5% / 95.5% |
| Numbers | ±8 ~ ±10 (adjustable) / ±16 ~ ±20 (adjustable) / ±10 ~ ±20 (adjustable) |
| Charging Voltage (max.) | +/ -13.65V DC x N (N=8~10) / +/ -13.65V x N (N=16~20) / +/ -13.65V x N (N=10~20) |
| Efficiency | |
| ECO Mode | 98.5% |
| Battery | |
| Battery Type | Depending on application |
| Charging Current (max.) | 1A ~ 18A (adjustable) |
| Communication | |
| Smart RS-232/USB | Supports Windows® Family, Linux and MAC |
| Optional SNMP | Power management from SNMP manager and web browser |
| Mechanical Data | |
| Dimension, D X W X H (mm) | 620 x 438 x 88 [2U] / 620 x 438 x 130.6 [3U] / 620 x 438 x 130.6 [3U] |
| Net Weight (kgs) | 16 / 22.2 / 23.1 |
| Additional Specifications | |
| Weight | 16 / 22.2 / 23.1 |
| Operating Conditions | |
| Operation Temperature | 0-40°C |
| Operation Humidity | <95% and non-condensing |
| Noise Level | Less than 62dB @ 1 Meter / Less than 65dB @ 1 Meter / Less than 65dB @ 1 Meter |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in the UAE
| Market | UAE |
|---|---|
| Grid authority / regulator | DEWA, ADDC, SEWA |
| Quotation currency | AED |
| Support hours timezone | Asia/Dubai |
| Main cities | Dubai, Abu Dhabi, Sharjah, Ajman, Ras Al Khaimah |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in the UAE that rests with the local authorities (DEWA, ADDC, SEWA). Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- True double-conversion
- Rack/Tower design
- Flexible system configuration as 3-in/3-out,: Flexible system configuration as 3-in/3-out, 3-in/1-out or 1-in/1-out
- DSP technology guarantees high performance
- Output power factor 1
- Active power factor correction in: Active power factor correction in all phases
- 50Hz/60Hz frequency converter mode
- ECO mode operation for energy: ECO mode operation for energy saving (ECO)
- Emergency power off function (EPO)
- Dual AC inputs
- Generator compatible
- Adjustable battery numbers
Frequently Asked Questions
What voltage does the Voltronic UPS Galleon III 33/31/11 10KL-20KL RT operate on?
The Voltronic UPS Galleon III 33/31/11 10KL-20KL RT has a nominal voltage of 3 x 380/400/415 VAC (3Ph+N) or 220/230/240 VAC (1Ph+N) and an operating voltage range of 190-520 VAC (3-phase) @ 50% load.
What are the physical dimensions and weight of the Voltronic UPS Galleon III 33/31/11 10KL-20KL RT?
The Voltronic UPS Galleon III 33/31/11 10KL-20KL RT measures 620 x 438 x 88 [2U] / 620 x 438 x 130.6 [3U] / 620 x 438 x 130.6 [3U] and weighs 16 / 22.2 / 23.1.
What is the operating temperature range of the Voltronic UPS Galleon III 33/31/11 10KL-20KL RT?
The Voltronic UPS Galleon III 33/31/11 10KL-20KL RT operates across 0-40°C and a humidity range of <95% and non-condensing.
What is the maximum charge current of the Voltronic UPS Galleon III 33/31/11 10KL-20KL RT?
The Voltronic UPS Galleon III 33/31/11 10KL-20KL RT has a maximum charge current of 1A ~ 18A (adjustable).
What output waveform does the Voltronic UPS Galleon III 33/31/11 10KL-20KL RT produce?
The Voltronic UPS Galleon III 33/31/11 10KL-20KL RT produces a Pure Sine Wave output waveform.
How does the Voltronic UPS Galleon III 33/31/11 10KL-20KL RT regulate voltage?
The Voltronic UPS Galleon III 33/31/11 10KL-20KL RT provides a voltage regulation of ± 1%.
How loud is the Voltronic UPS Galleon III 33/31/11 10KL-20KL RT during operation?
The Voltronic UPS Galleon III 33/31/11 10KL-20KL RT has a noise level of Less than 62dB @ 1 Meter / Less than 65dB @ 1 Meter / Less than 65dB @ 1 Meter during operation.
What is the power quality of the Voltronic UPS Galleon III 33/31/11 10KL-20KL RT?
The Voltronic UPS Galleon III 33/31/11 10KL-20KL RT has a power factor of >= 0.99 @ 100% load and a harmonic distortion of ≤ 2 % THD (Linear Load).
What warranty coverage is available for the Voltronic UPS Galleon III 33/31/11 10KL-20KL RT?
The Voltronic UPS Galleon III 33/31/11 10KL-20KL RT is backed by a 2-year manufacturer warranty from Voltronic Power.