Voltronic Power UPS Datasheet — VOLTRONIC-SOLAR-UPS-5KW
Discover Voltronic Power's Solar UPS 5KW with 230 VAC voltage, auto-sensing frequency, and precise voltage regulation for reliable power.
SKU: VOLTRONIC-SOLAR-UPS-5KW | Last Updated: 2026-03-27
⚡Electrical Specifications
| Voltage | 230 VAC |
| Voltage Range | 110-280 VAC |
| Frequency Range | 50 Hz/60 Hz (Auto sensing) ± 4Hz |
| Power Factor | > 0.98 @ Nominal Voltage (100% Load) |
| THDi | < 10% |
| AC Voltage Regulation (Batt. Mode) | 230VAC ± 5% |
| Frequency Range (Synchronized Range) | 46-54 Hz or 56-64 Hz |
| Frequency Range (Batt. Mode) | 50 Hz |
| Harmonic Distortion | ≤ 3% THD (Linear Load) ; ≤ 5 % THD (Non-linear Load) |
| Transfer Time | 0 ms |
| Waveform | Pure Sinewave |
| Line Mode | 93.0% |
| ECO Mode | 99.0% |
| Battery Mode | 90.0% |
| Battery Voltage | 48 VDC |
| Floating Charge Voltage | 54 VDC |
| Overcharge Protection | 66 VDC |
| Solar Charger Type | MPPT |
| Maximum PV Array Power | 4000 W |
| MPPT Range @ Operating Voltage | 60 ~ 115 VDC |
| Maximum PV Array Open Circuit Voltage | 145 VDC |
| Maximum Solar Charge Current | 80 A |
| Maximum AC Charge Current | 60 A |
| Communication Interface | RS232 & USB |
🔧Mechanical Specifications
| Dimension, D x W x H(mm) | 465 x 190 x 336 |
| Net Weight (kgs) | 16 |
🌡️Environmental Specifications
| Humidity | 5% to 95% Relative Humidity(Non-condensing) |
| Operating Temperature | -10°C to 50°C |
| Storage Temperature | -15°C to 60°C |
📏Dimensions
Width190
Height336
Depth465
Weight16