Voltronic Power APlus 42U-300

Voltronic Power UPS Datasheet — VOLTRONIC-APLUS-42U-300

Discover Voltronic Power's APlus 42U-300 UPS with 3 x 380/400/415 VAC, -30%~+20% voltage range, and auto-sensing 50/60Hz frequency.

SKU: VOLTRONIC-APLUS-42U-300 | Last Updated: 2026-07-23

⚡Electrical Specifications

Rated Output Power (VA)300kVA
Rated Output Power (W)300kW
Power Module60KVA/60KW (PM-60)
Max Power Modules5
Nominal Voltage3 x 380/400/415 VAC (3P+N)
Voltage Range-30% ~ +20%
Nominal Frequency50/60Hz (Auto Sensing)
Frequency Range40Hz ~ 70Hz
Power Factor> 0.99 @ 100% Load, >0.98 @ 50% Load
Harmonic Distortion (THDi)<3% @ 100% load
Voltage Regulation(Steady state)≤± 1% Typical (balanced load) ; ≤± 2% Typical (unbalanced load)
Frequency Range(Synchronized)46Hz ~ 54Hz or 56Hz ~ 64Hz
Overload Capability1 hour for ≤ 110%, 10 mins for 111% ~ 125%, 1 min for 126%~150% and 200ms for >150%
Harmonic Distortion≤2% THD (Linear Load) ; ≤4% THD (Non-linear Load)
Efficiency96%
Maximum Voltage+/- 240V (12V x 40 Pcs)
Minimum Voltage+/- 192V (12V x 32 Pcs)
Floating Charge Voltage2.28V / Cell (2.25 ~ 2.33 Selectable)
Boost Charge Voltage2.35V/Cell
Maximum Charging Current (Per Power Module)18A (Adjustable)
Smart RS-232 / USBSupports Windows® Family, Linux and MAC
Optional SNMPPower management from SNMP manager and web browser
SafetyIEC/EN 62040-1
EMCIEC/EN 62040-2 Category C3

🔧Mechanical Specifications

Cabinet Dimension (D x W x H) mm1100x600x2010
Net Weight (Kg)516
Weight516

🌡️Environmental Specifications

Operating Temperature0 ~ 40°C
Relative Humidity0 ~ 95% non-condensing
Altitude<1000m for Nominal power
IP ProtectionIP 20
Temperature CompensationYes

📏Dimensions

Width600
Height1475
Depth1100
Weight516

✅Certifications

IEC/EN 62040-1IEC/EN 62040-2 Category C3