Voltronic Power Three-Phase Online UPS PLUS-POWER-E-15U-60 / VOLTRONIC-PLUS-POWER-E-15U-90

+Power E 15U-60 by Voltronic Power: Online UPS with 3 x 380VAC/400VAC/415VAC, 50/60Hz auto sensing, and precise voltage regulation.

Models Covered: VOLTRONIC-PLUS-POWER-E-15U-60, VOLTRONIC-PLUS-POWER-E-15U-90

Manufacturer: Voltronic Power Technology Corp.

Application: The Voltronic 60 kVA UPS +Power E 15U-60 is a Three Phase Online UPS with a rated power of 60 kW, making it a dependable choice for protecting critical loads from power interruptions. It accepts an operating voltage range of 305 - 478 VAC at 70% - 100% load. It operates at an efficiency of Up to 94.5%. The unit measures 1000 x 515 x 763 and weighs 182. It is rated to operate across 0 - 40°C, with a humidity tolerance of 0 - 95% non-condensing. The Voltronic 60 kVA UPS +Power E 15U-60 is certified to IEC/EN 60950-1, IEC/EN 62040-1 and IEC/EN 62040-2 Category C3 and is backed by a 2-year manufacturer warranty from Voltronic Power. Its published specifications also list Rated Output Power (VA) of 60kVA, Power Module of 20KVA/20KW (PM-20HV) and Max Power Modules of 3.

Models and prices

Technical Specifications

Technical Specifications
ParameterVOLTRONIC-PLUS-POWER-E-15U-60VOLTRONIC-PLUS-POWER-E-15U-90
Additional Specifications
Rated Output Power (VA)60kVA90kVA
Rated Output Power (W)60kW90kW
Power Module20KVA/20KW (PM-20HV)30KVA/30KW (PM-30HV)
Electrical Data
Max Power Modules3
Output
Nominal Voltage3 x 380VAC/400VAC/415VAC (3Ph+N)
Voltage Regulation (Steady state)≤ ± 1% Typical (balanced load)
Frequency Range (Synchronized)46Hz - 54Hz or 56Hz - 64Hz
Overload Capability1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
Harmonic Distortion≤ 2% THD (Linear load); ≤ 4% THD (Non-linear load)
EfficiencyUp to 94.5%
Input
Voltage Range305 - 478 VAC at 70% - 100% load; 208 - 478 VAC for <70% load
Nominal Frequency50/60Hz (Auto sensing)
Frequency Range40Hz - 70Hz
Power Factor> 0.99 at 100% load, > 0.98 at 50% load
Harmonic Distortion (THDi)< 3% @ 100% load
Battery Charging
Maximum Voltage+/- 240V (12V x 40 Pcs)
Minimum Voltage+/- 192V (12V x 32 Pcs)
Float Charging Voltage2.25V/Cell
Boost Charging Voltage2.35V/Cell
Maximum Charging Current6A (User-adjustable)8A (User-adjustable)
Temperature CompensationYes
Communication
Smart RS-232 / USBSupports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC
Optional SNMPPower management from SNMP manager and web browser
Certifications
SafetyIEC/EN 60950-1; IEC/EN 62040-1
EMCIEC/EN 62040-2 Category C3
Physical
Cabinet Dimension (D x W x H) mm1000 x 515 x 763
Net Weight (kg)182183.5
Mechanical Data
Weight182183.5
Operating Conditions
Operating Temperature0 - 40°C
Relative Humidity0 - 95% non-condensing
Altitude<1000m for Nominal power
IP ProtectionIP 20

Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.

Availability & grid compliance in the UAE

MarketUAE
Grid authority / regulatorDEWA, ADDC, SEWA
Quotation currencyAED
Support hours timezoneAsia/Dubai
Main citiesDubai, Abu Dhabi, Sharjah, Ajman, Ras Al Khaimah

Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in the UAE that rests with the local authorities (DEWA, ADDC, SEWA). Confirm the grid code, import requirements and any local certification with them, or with us, before you order.

For prices, see Voltronic Inverters: Prices in UAE. Store pickup — collect your order from our store in Dubai or Riyadh.

Key Features & Technical Highlights

  • High efficiency online double conversion: High efficiency online double conversion technology
  • Output power factor 1
  • Modular design lowers MTTR
  • Adjustable battery numbers
  • Adjustable charging current
  • Built-in maintenance bypass switch for: Built-in maintenance bypass switch for easy maintenance without interruption
  • Graphic 5.7” LCD design for: Graphic 5.7” LCD design for easy configuration
  • Support 1+1 cabinets parallel

Frequently Asked Questions

What is the rated power of the Voltronic 60 kVA UPS +Power E 15U-60?

The Voltronic 60 kVA UPS +Power E 15U-60 has a rated power of 60 kW.

What voltage does the Voltronic 60 kVA UPS +Power E 15U-60 operate on?

The Voltronic 60 kVA UPS +Power E 15U-60 has a nominal voltage of 3 x 380 VAC/400 VAC/415 VAC (3Ph+N) and an operating voltage range of 305 - 478 VAC at 70% - 100% load.

What are the physical dimensions and weight of the Voltronic 60 kVA UPS +Power E 15U-60?

The Voltronic 60 kVA UPS +Power E 15U-60 measures 1000 x 515 x 763 and weighs 182.

What is the operating temperature range of the Voltronic 60 kVA UPS +Power E 15U-60?

The Voltronic 60 kVA UPS +Power E 15U-60 operates across 0 - 40°C and a humidity range of 0 - 95% non-condensing.

What is the efficiency of the Voltronic 60 kVA UPS +Power E 15U-60?

The Voltronic 60 kVA UPS +Power E 15U-60 has an efficiency of Up to 94.5%.

What is the maximum charge current of the Voltronic 60 kVA UPS +Power E 15U-60?

The Voltronic 60 kVA UPS +Power E 15U-60 has a maximum charge current of 6A (User-adjustable).

How does the Voltronic 60 kVA UPS +Power E 15U-60 regulate voltage?

The Voltronic 60 kVA UPS +Power E 15U-60 provides a voltage regulation of ≤ ± 1% Typical (balanced load).

What ingress protection rating does the Voltronic 60 kVA UPS +Power E 15U-60 carry?

The Voltronic 60 kVA UPS +Power E 15U-60 carries an ingress protection rating of IP 20.

What is the power quality of the Voltronic 60 kVA UPS +Power E 15U-60?

The Voltronic 60 kVA UPS +Power E 15U-60 has a power factor of > 0.99 at 100% load, > 0.98 at 50% load and a harmonic distortion of < 3% @ 100% load.

What certifications does the Voltronic 60 kVA UPS +Power E 15U-60 have?

The Voltronic 60 kVA UPS +Power E 15U-60 is certified to IEC/EN 60950-1, IEC/EN 62040-1 and IEC/EN 62040-2 Category C3, meeting recognised international standards for safety and performance.