Voltronic Power UPS OTIMA-II-TOWER

Discover Voltronic Power's Otima II Tower UPS with voltage options of 110-240 VAC and precise regulation for reliable power backup.

Models Covered: VOLTRONIC-OTIMA-II-TOWER

Manufacturer: Voltronic Power Technology Corp.

Application: The Voltronic UPS Otima II Tower is a Line Interactive UPS with a voltage regulation of ±1.5 % (Before battery alarm), making it a dependable choice for protecting critical loads from power interruptions. It accepts an operating voltage range of 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 162-290 VAC. Its output waveform is Pure Sinewave. The unit measures 397 x 145 x 220 / 455 x 145 x 220 / 421 x 190 x 318 / 421 x 190 x 318 / 421 x 190 x 318 / 421 x 190 x 318 / 421 x 190 x 318 and weighs 11.7 / 12.1 / 17.2 / 19.7 / 26.6 / 29 / 34.5. The Voltronic UPS Otima II Tower is backed by a 2-year manufacturer warranty from Voltronic Power. Its published specifications also list Frequency Range (Batt. Mode) of 50 Hz or 60 Hz ± 1 Hz, Current Crest Ratio of 3:1 and ECO Mode of 97%.

Models and prices

Technical Specifications

Technical Specifications
ParameterVOLTRONIC-OTIMA-II-TOWER
Electrical Data
Voltage110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 208/220/230/240 VAC
Acceptable Voltage Range81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 162-290 VAC
Output Voltage110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 208/220/230/240 VAC
Battery Mode>= 88%, up to 90% @ nominal battery voltage
Battery Type and Quantity12 V/7 Ah x 2 / 12 V/9 Ah x 2 / 12 V/7 Ah x 2 / 12 V/9 Ah x 4 / 12 V/9 Ah x 4 / 12 V/9 Ah x 6 / 12 V/10 Ah x 6
Input
Frequency Range60/50 Hz (Auto sensing)
Output
Voltage Regulation (Batt. Mode)±1.5 % (Before battery alarm)
Frequency Range (Batt. Mode)50 Hz or 60 Hz ± 1 Hz
Current Crest Ratio3:1
Harmonic Distortion2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm)
Transfer TimeTypical 2-6 ms, 10ms max.
Waveform (Batt. Mode)Pure Sinewave
Efficiency
ECO Mode97%
Buck & Boost Mode95%
Battery
Charging Current (max.)1.5A
Charging Voltage27.4 VDC ± 1% / 54.8 VDC ± 1% / 82.1 VDC ± 1% / 82.1 VDC ± 1% / 82.1 VDC ± 1% / 82.1 VDC ± 1% / 82.1 VDC ± 1%
Typical Recharge Time4 hours recover to 90% capacity
Communication
Smart RS-232/USBSupports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC
Optional SNMPPower management from SNMP manager and web browser
Physical Specifications
Dimension, DxWxH(mm)397 x 145 x 220 / 455 x 145 x 220 / 421 x 190 x 318 / 421 x 190 x 318 / 421 x 190 x 318 / 421 x 190 x 318 / 421 x 190 x 318
Mechanical Data
Net Weight (kgs)11.7 / 12.1 / 17.2 / 19.7 / 26.6 / 29 / 34.5
Additional Specifications
Weight11.7 / 12.1 / 17.2 / 19.7 / 26.6 / 29 / 34.5
Protection Features
Full ProtectionOverload, discharge, and overcharge protection
Operating Conditions
Humidity0-90 % RH @ 0- 40°C (Non-condensing)
Noise LevelLess than 45dB
Altitude0~3000m, 10% de-rating for over 1000m

Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.

Availability & grid compliance in the UAE

MarketUAE
Grid authority / regulatorDEWA, ADDC, SEWA
Quotation currencyAED
Support hours timezoneAsia/Dubai
Main citiesDubai, Abu Dhabi, Sharjah, Ajman, Ras Al Khaimah

Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in the UAE that rests with the local authorities (DEWA, ADDC, SEWA). Confirm the grid code, import requirements and any local certification with them, or with us, before you order.

For prices, see Voltronic Inverters: Prices in UAE. Store pickup — collect your order from our store in Dubai or Riyadh.

Key Features & Technical Highlights

  • Pure sine wave
  • Output power factor 0.9
  • Programmable power management outlets
  • ECO (Efficiency Corrective Optimizer) operation: ECO (Efficiency Corrective Optimizer) operation for energy saving
  • Very high efficiency in battery: Very high efficiency in battery mode
  • Boost and Buck AVR for: Boost and Buck AVR for voltage stabilization
  • Multiple communications available
  • 3-stage smart battery charging control
  • Optional HID Power Device USB: Optional HID Power Device USB Port

Frequently Asked Questions

What voltage does the Voltronic UPS Otima II Tower operate on?

The Voltronic UPS Otima II Tower has a nominal voltage of 110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 110/115/120/127 VAC or 208/220/230/240 VAC / 208/220/230/240 VAC and an operating voltage range of 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 81-152 VAC or 162-290 VAC / 162-290 VAC.

What are the physical dimensions and weight of the Voltronic UPS Otima II Tower?

The Voltronic UPS Otima II Tower measures 397 x 145 x 220 / 455 x 145 x 220 / 421 x 190 x 318 / 421 x 190 x 318 / 421 x 190 x 318 / 421 x 190 x 318 / 421 x 190 x 318 and weighs 11.7 / 12.1 / 17.2 / 19.7 / 26.6 / 29 / 34.5.

What is the maximum charge current of the Voltronic UPS Otima II Tower?

The Voltronic UPS Otima II Tower has a maximum charge current of 1.5A.

What transfer time and output waveform does the Voltronic UPS Otima II Tower provide?

The Voltronic UPS Otima II Tower has a transfer time of Typical 2-6 ms, 10ms max. and an output waveform of Pure Sinewave.

How does the Voltronic UPS Otima II Tower regulate voltage?

The Voltronic UPS Otima II Tower provides a voltage regulation of ±1.5 % (Before battery alarm).

How loud is the Voltronic UPS Otima II Tower during operation?

The Voltronic UPS Otima II Tower has a noise level of Less than 45dB during operation.

What is the power quality of the Voltronic UPS Otima II Tower?

The Voltronic UPS Otima II Tower has a harmonic distortion of 2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm).

What warranty coverage is available for the Voltronic UPS Otima II Tower?

The Voltronic UPS Otima II Tower is backed by a 2-year manufacturer warranty from Voltronic Power.