Voltronic Power Off-Grid Solar Inverters AXPERT-MAX-TWIN-8/E-TWIN-11/TWIN-12K

Discover the Axpert MAX TWIN 8K inverter by Voltronic Power with 230VAC regulation, 16000VA surge power, and 95% efficiency.

Models Covered: VOLTRONIC-AXPERT-MAX-TWIN-8K, VOLTRONIC-AXPERT-MAX-E-TWIN-11K, VOLTRONIC-AXPERT-MAX-TWIN-12K

Manufacturer: Voltronic Power Technology Corp.

Application: The Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K is an Off-Grid Inverter with a rated power of 8000W, making it a dependable choice for off-grid, hybrid and backup power installations. It accepts an operating voltage range of 90 VDC 450 VDC. It operates at an efficiency of 93%. Its output waveform is Pure sine wave. The unit measures 147.4 x 432.5 x 553.6 and weighs 18.4. It is rated to operate across -10°C to 50°C, with a humidity tolerance of 5% to 95% Relative Humidity(Non-condensing). Monitoring and control are available over USB/RS232/RS485/WiFi/Dry-contact. The Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K is certified to IEC 62109, IEC 61683, EN/IEC 61000-6-2, 61000-6-4, 61000-3-11 and 61000-3-12 and is backed by a 2-year manufacturer warranty from Voltronic Power. Its published specifications also list Circulation Current under No Load Condition of Max 2A, DC Offset of ≤100mV and Floating Charging Voltage of 54Vdc.

Models and prices

Technical Specifications

Technical Specifications
ParameterVOLTRONIC-AXPERT-MAX-TWIN-8KVOLTRONIC-AXPERT-MAX-E-TWIN-11KVOLTRONIC-AXPERT-MAX-TWIN-12K
Additional Specifications
Circulation Current under No Load ConditionMax 2A
DC Offset≤100mV
Floating Charging Voltage54Vdc
Low DC Cut-off Voltage44Vdc
Max. Charging Current120A
Max. Input Current27A x 2 (MAX 40A)
Max. PV Array Open Circuit Voltage500Vdc
Nominal DC Input Voltage48Vdc
PV Array MPPT Voltage Range90Vdc 450Vdc
Parallel KitYES
Parallel communicationCAN
Peak Efficiency93%
Transfer time in parallel modeMax 50ms
Max parallel numbers6
Parallel CapabilityYES, 6 units
Selectable Voltage Range170-280 VAC (For Personal Computers)
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
High Loss Return Voltage270Vac±7V
High Loss Voltage280Vac±7V
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
Low Loss Voltage170Vac±7V (UPS) 90Vac±7V (Appliances)
Max AC Input Current60A
Max AC Input Voltage300Vac
Max Output Current for 2nd output40A
Nominal Input Frequency50Hz/60Hz (Auto detection)
Nominal Input Voltage230Vac
Output Short Circuit ProtectionLine mode: Circuit Breaker (70A) Battery mode: Electronic Circuits
Charging Current150A UPS
Input Voltage WaveformSinusoidal (utility or generator) Nominal
Overload ProtectionSurge
Safety CertificationCE
Power Unbalance Ratio<5% 100% Load
DC VoltageDC Offset ≦100mV Power Limitation 55Vdc
Efficiency>95% ( Rated R load Line Mode
Output Frequency60Hz or 50Hz Peak
Output Voltage Regulation230Vac± 5%
Operating Temperature Range-10°C to 50°C
Electrical / AC Output Data
High DC Cut-off Voltage66Vdc63Vdc66Vdc
High DC Recovery Voltage64Vdc61Vdc64Vdc
Rated Output Power8000W11000W12000W
Rated Power8000W11000W Max. PV Array Open Circuit12000W
Start-up Voltage80V +/- 5Vdc80V +/- 5Vdc Power Limitation PV Current MPPT temperature 75° 80°80V +/- 5Vdc
AC Output
AC Voltage Regulation (Batt. Mode)230VAC ± 5%
Surge Power16000VA22000VA24000VA
Efficiency (Peak)93%
Transfer Time10 ms (For Personal Computers), 20 ms (For Home Appliances)10ms typical (UPS);10 ms (For Personal Computers), 20 ms (For Home Appliances)
WaveformPure sine wave
Optional DC Voltage12 VDC ± 5%, 100W
Battery
Battery Voltage48 VDC
Floating Charge Voltage54 VDC
Overcharge Protection66 VDC63Vdc Charging Algorithm 3-Step Charging Curve Time63 VDC
Solar Charger & AC Charger
Solar Charger TypeMPPT
Maximum PV Array Power11000W (5500W x 2)13000W (6500W x 2)18000W (Max. 12000W per tracker)
MPPT Range @ Operating Voltage90 – 450 VDC
Maximum PV Array Open Circuit Voltage500 VDC
Maximum PV Input Current27A x 2 (MAX 40A)40A/27A (MAX 60A)40A/27A (MAX 60A)
Maximum Solar Charge Current120A150A200A
Maximum AC Charge Current120A150A200A
Maximum Charge Current120A150A200A
Standard
Compliance SafetyIEC 62109, IEC 61683, EN/IEC 61000-6-2, 61000-6-4, 61000-3-11, 61000-3-12
Physical
Dimension, D x W x H (mm)147.4 x 432.5 x 553.6
Net Weight (kgs)18.418.420
Communication InterfaceUSB/RS232/RS485/WiFi/Dry-contact
Operating Environment
Humidity5% to 95% Relative Humidity(Non-condensing)5% to 95%5% to 95% Relative Humidity(Non-condensing)
Operating Temperature-10°C to 50°C
Storage Temperature-15°C to 60°C-15°C~ 60°C-15°C to 60°C
Electrical Data
Battery56.4Vdc

Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.

Availability & grid compliance in the UAE

MarketUAE
Grid authority / regulatorDEWA, ADDC, SEWA
Quotation currencyAED
Support hours timezoneAsia/Dubai
Main citiesDubai, Abu Dhabi, Sharjah, Ajman, Ras Al Khaimah

Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in the UAE that rests with the local authorities (DEWA, ADDC, SEWA). Confirm the grid code, import requirements and any local certification with them, or with us, before you order.

For prices, see Voltronic Inverters: Prices in UAE. Store pickup — collect your order from our store in Dubai or Riyadh.

Key Features & Technical Highlights

  • Status indication with RGB lights
  • Dual outputs for smart load: Dual outputs for smart load management
  • Built-in WiFi with APP for: Built-in WiFi with APP for mobile monitoring and OTA firmware
  • Supports USB On-the-Go function
  • Built-in BMS communication port
  • Built-in meter calibration for optimized: Built-in meter calibration for optimized system operation
  • Battery independent design
  • Built-in anti-dust kit
  • Optional DC output for DC: Optional DC output for DC fan, LED bulb, router and so on
  • Parallel operation with 6 units

Frequently Asked Questions

What is the rated power of the Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K?

The Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K has a rated power of 8000W and a surge capability of 16000 VA.

What voltage does the Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K operate on?

The Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K has a nominal voltage of 48 VDC and an operating voltage range of 90 VDC 450 VDC.

What are the physical dimensions and weight of the Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K?

The Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K measures 147.4 x 432.5 x 553.6 and weighs 18.4.

What is the operating temperature range of the Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K?

The Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K operates across -10°C to 50°C and a humidity range of 5% to 95% Relative Humidity(Non-condensing).

What is the efficiency of the Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K?

The Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K has an efficiency of 93%.

What solar input can the Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K handle?

The Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K supports a maximum PV array power of 11000W (5500W x 2), a maximum solar charge current of 120A and a maximum PV array open-circuit voltage of 500 VDC.

What transfer time and output waveform does the Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K provide?

The Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K has a transfer time of Max 50ms and an output waveform of Pure sine wave.

How does the Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K regulate voltage?

The Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K provides a voltage regulation of 230 VAC ± 5%.

What communication options does the Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K offer?

The Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K offers USB/RS232/RS485/WiFi/Dry-contact connectivity for monitoring and control.

Can multiple Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K units run in parallel?

Yes — the Voltronic 8 kW Off-Grid Solar Inverter Axpert MAX TWIN 8K supports parallel operation (YES).