Voltronic Power Fortress 3/3 120K
Voltronic Power

Fortress 3/3 120K

Découvrez l'onduleur triphasé Fortress de Voltronic Power avec 3 x 380/400/415 VAC et fréquence 50/60Hz auto-sensible pour une protection fiable.

  • Nominal Voltage: 3x 380/400/415 VAC
  • Voltage Range: 110-300 VAC @ 50% load; 184-276 VAC @100% load
  • Frequency: 50/60Hz (Auto sensing)
95,000 AEDTTC
Spécifications Complètes

Caractéristiques

Backfeed detection built-in

Single power module on/off control

Single power module on/off control through LCD panel

Pluggable power module design with

Pluggable power module design with front access

Parallel operation up to 4

Parallel operation up to 4 units with common battery

Dual-mains inputs

Built-in 4 switches including Mains

Built-in 4 switches including Mains input, bypass input, output and maintenance bypass switch

Flexible battery configuration and adjustable

Flexible battery configuration and adjustable charging current

Optional extra communication is available

Emergency power off function (EPO)

Generator compatible

50Hz/60Hz frequency converter mode

Compatible to Lithium-ion battery

Aperçu

L'onduleur triphasé Fortress de Voltronic Power est conçu pour offrir une protection d'alimentation robuste et fiable pour les applications critiques. Avec une tension nominale de 3 x 380/400/415 VAC et une fréquence auto-sensible, il assure un fonctionnement sans faille dans divers environnements. Idéal pour les centres de données, les installations industrielles et les télécommunications, l'onduleur triphasé Fortress offre une régulation de puissance constante et une protection contre les fluctuations de tension.

Spécifications complètes

Caractéristiques électriques

Nominal Tension3 x 380/400/415 VAC (3Ph+N)
Tension Plage110-300 VAC @ 50% load; 184-276 VAC @100% load
Nominal Fréquence50/60Hz (Auto sensing)
Fréquence Plage40Hz ~ 70Hz
Puissance>= 0.99 @ 100% load
Harmonic Distortion (THDi)<5% @ 100% load
Tension (Steady state)≤ ± 2% Typical (unbalanced load)
Fréquence Plage46Hz ~ 54Hz or 56Hz ~ 64Hz
Overload Capability≤ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms
Harmonic Distortion≤ 2% THD (Linear Load); ≤ 4% THD (Non-linear Load)
AC Mode95.5%
ECO Mode98.5%
Batterie94.5%
Tension+/- 240V (12V x 40 Pcs)
Tension+/- 192V (12V x 32 Pcs)
Charge Tension2.28V / Cell (2.25 ~ 2.33 Selectable)
Tension2.35V/Cell
TempératureYes
Courant36A (Adjustable)
ManagementSupports Windows® Family, Linux and MAC
Optional SNMPPower management from SNMP manager and web browser
SafetyIEC/EN 62040-1
EMCIEC/EN 62040-2 Category C3

Caractéristiques mécaniques

IP ClassIP20, optional IP31
Dimensions (mm)1000x430x1200
Poids (Kgs)169
Poids169

Caractéristiques environnementales

Fonctionnement Température0-40°C
Fonctionnement Humidité< 95% and non-condensing
Altitude<1000m for Nominal power

Certifications

  • IEC/EN 62040-1
  • IEC/EN 62040-2 Category C3

Produits Connexes