Onduleur UPS triphasé Arena 2U/3U Voltronic Power — Fiche technique VOLTRONIC-ARENA-2U-3U
Découvrez l'onduleur Arena 2U/3U de Voltronic Power avec une plage de tension triphasée de 190-520 VAC et une régulation précise.
SKU: VOLTRONIC-ARENA-2U-3U | Dernière Mise à Jour: 2026-03-27
⚡Spécifications Électriques
| Tension nominale | 3 x 360VAC/380VAC/400VAC/415VAC (3Ph+N+PE) / 3 x 360VAC/380VAC/400VAC/415VAC (3Ph+N+PE) / 208VAC/220VAC/230VAC/240VAC (1Ph+N+PE) / 100/200, 110/220, 120/208, 120/240, 127/220 VAC (2Ph+N+PE) / 3 x 360VAC/380VAC/400VAC/415VAC (3Ph+N+PE) / 3 x 360VAC/380VAC/400VAC/415VAC (3Ph+N+PE) / 208VAC/220VAC/230VAC/240VAC (1Ph+N+PE) / 100/200, 110/220, 120/208, 120/240, 127/220 VAC (2Ph+N+PE) / 3 x 173VAC/190VAC/200VAC/208VAC/220VAC (3Ph+N+PE) |
| Plage de tension | 190-520 VAC (3-phase) @ 50% load, 305-478 VAC (3-phase) @ 100% load / 190-520 VAC (3-phase) @ 50% load, 305-478 VAC (3-phase) @ 100% load / 110-300 VAC @ 50% load, 176-276 VAC @ 100% load / 88-155 VAC (L-N), 152-269 VAC (L-L) / 190-520 VAC (3-phase) @ 50% load, 305-478 VAC (3-phase) @ 100% load / 190-520 VAC (3-phase) @ 50% load, 305-478 VAC (3-phase) @ 100% load / 110-300 VAC @ 50% load, 176-276 VAC @ 100% load / 88-155 VAC (L-N), 152-269 VAC (L-L) / 88-155 VAC (L-N), 152-269 VAC (L-L) |
| Plage de fréquence | 40 Hz ~ 70 Hz |
| Facteur de puissance | >= 0.99 @ 100% load |
| Distorsion harmonique de courant (THDi) | < 4% @ full linear load |
| Tension de sortie | 360VAC/380VAC/400VAC/415VAC (3Ph+N) / 208*220/230/240VAC(L+N) / 208*220/230/240VAC(L+N) / 100/200,110/220,120/208,120/240,127/220VAC(2Ph+N) / 360VAC/380VAC/400VAC/415VAC (3Ph+N) / 208*220/230/240VAC(L+N) / 208*220/230/240VAC(L+N) / 100/200,110/220,120/208,120/240,127/220VAC(2Ph+N) / 173VAC/190VAC/200VAC/208VAC/220VAC(3Ph+N) |
| Régulation de la tension AC (mode batterie) | ± 1% |
| Plage de fréquence (plage de synchronisation) | 46~54Hz or 56~64Hz |
| Plage de fréquence (mode batterie) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Facteur de crête du courant | 3:1 (max.) |
| Distorsion harmonique | ≤ 2% THD (Linear Load) ; ≤ 3% THD (Non-linear Load) |
| Temps de transfert | 0 ms |
| Forme d'onde (mode batterie) | Pure Sinewave |
| Mode AC | 94% / 94% / 93.5% / 91% / 94% / 94% / 93.5% / 91% / 92% |
| Mode ECO | 97% / 97% / 97% / 97% / 97% / 97% / 97% / 97% / 97% |
| Mode batterie à pleine charge | 93% / 92.5% / 92% / 91% / 93% / 92.5% / 92% / 91% / 92% |
| Mode batterie en pointe | 93.5% / 93% / 92.5% / 91.5% / 93.5% / 93% / 92.5% / 91.5% / 92% |
| Tension de batterie | ± 12V / 9 Ah |
| Nombre de batteries | 12 pcs x 2 / 12 pcs x 2 / 12 pcs x 2 / 6 pcs x 2 / 16~20 pcs (adjustable) x 2 / 16~20 pcs (adjustable) x 2 / 16~20 pcs (adjustable) x 2 / 8~10pcs (adjustable) x 2 / 8~10pcs (adjustable) x 2 |
| Tension de charge | ± 164V / ± 164V / ± 164V / ± 82V / ± 218V / ± 218V / ± 218V / ± 109V / ± 109V |
| Temps de recharge typique | 9 hours recover to 90% capacity |
| Courant de charge | ± 4A |
| Afficheur LCD/LED | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
| RS-232/USB intelligent | Supports Windows® Family, Linux and MAC |
| SNMP en option | Power management from SNMP manager and web browser |
🔧Spécifications Mécaniques
| Dimensions (mm) | 678 x 418 x 88 [2U] / 678 x 418 x 88 [2U] / 678 x 418 x 88 [2U] / 678 x 418 x 88 [2U] / 678 x 418 x 129 [3U] / 678 x 418 x 129 [3U] / 678 x 418 x 129 [3U] / 678 x 418 x 129 [3U] / 678 x 418 x 129 [3U] |
| Poids net (kgs) | 17 / 17 / 17 / 14 / 20.5 / 20.5 / 20.5 / 17.6 / 21 |
| Poids | 17 / 17 / 17 / 14 / 20.5 / 20.5 / 20.5 / 17.6 / 21 |
🌡️Spécifications Environnementales
| Humidité de fonctionnement | 0-95 % RH @ 0- 40°C (non-condensing) |
| Niveau sonore | Less than 55dB @ 1 Meter / Less than 55dB @ 1 Meter / Less than 55dB @ 1 Meter / Less than 58dB @ 1 Meter / Less than 55dB @ 1 Meter / Less than 55dB @ 1 Meter / Less than 55dB @ 1 Meter / Less than 58dB @ 1 Meter / Less than 58dB @ 1 Meter |
📏Dimensions
Largeur418
Hauteur88
Profondeur678
Poids17 / 17 / 17 / 14 / 20.5 / 20.5 / 20.5 / 17.6 / 21