Voltronic GALLEON-III-33-31-11-10K-20K
Discover the Voltronic Power Galleon III 33/31/11 10K-20K Online UPS with 3 x 380/400/415VAC voltage, ensuring reliable power protection.
Technical Specifications
| Parameter | VOLTRONIC-GALLEON-III-33-31-11-10K-20K |
|---|---|
| Bypass | |
| Nominal Voltage | 3 x 380/400/415VAC (3Ph+N) or 220/230/240VAC (1Ph+N) / 3 x 380/400/415VAC (3Ph+N) or 220/230/240VAC (1Ph+N) |
| Overload Capacity | > 130% : 1 minute (default), continuously working until breaker protection (optional) / > 130% : 1 minute (default), continuously working until breaker protection (optional) |
| Input | |
| Voltage Range | 190-520 VAC @ 50% load; 305-478 VAC @ 100% load / 190-520 VAC @ 50% load; 305-478 VAC @ 100% load |
| Frequency Range | 46-54Hz or 56-64Hz / 46-54Hz or 56-64Hz |
| Power Factor | >= 0.99 @ 100% load / >= 0.99 @ 100% load |
| Harmonic Distortion (THDi) | < 4% @ full linear load / < 4% @ full linear load |
| Output | |
| Output Voltage | 3 x 380/400/415VAC (3Ph+N) or 220/230/240VAC (1Ph+N) / 3 x 380/400/415VAC (3Ph+N) or 220/230/240VAC (1Ph+N) |
| AC Voltage Regulation (Batt. Mode) | ± 1% / ± 1% |
| Frequency Range (Synchronized Range) | 46-54Hz or 56-64Hz / 46-54Hz or 56-64Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz / 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) / 3:1 (max.) |
| Harmonic Distortion | ≤ 2 % THD (Linear Load); ≤ 5 % THD (Non-linear Load) / ≤ 2 % THD (Linear Load); ≤ 5 % THD (Non-linear Load) |
| Transfer Time | 0 / 0 ms |
| Waveform (Batt. Mode) | Pure Sinewave / Pure Sinewave |
| Electrical Data | |
| AC Mode | 95.5% / 96% |
| Numbers (default) | (10+10) pcs / (16+16) pcs |
| Long-run Model | ±8-10 / ±16-20 |
| Efficiency | |
| ECO Mode | 98.5% |
| Battery | |
| Battery Type | 12V / 9Ah / 12V / 9Ah |
| Typical Recharge Time | 9 hours recover to 90% capacity / 9 hours recover to 90% capacity |
| Battery Data | |
| Charging Current (max.) | 1A (default) / 1A (default) |
| Charging Voltage | +/-136.5 VDC / +/-218VDC |
| Standards | |
| Safety | EN 62040-1:2008/A1:2013;IEC 62040-1:2008/A1:2013;CE low voltage directive |
| EMC | EN 62040-2: 2006(C3) CE EMC directive |
| Communication | |
| Smart RS-232/USB | Supports Windows® family, Linux and MAC |
| Optional SNMP | Power management from SNMP manager and web browser |
| Physical | |
| Standard Dimension, D x W x H (mm) | 630 x 250 x 826 |
| Long-run Dimension, D x W x H (mm) | 630 x 250 x 826 |
| Mechanical Data | |
| Model Net Weight (kgs) | 80 / 133 |
| Long-run Model Net Weight (kgs) | 25 / 37 |
| Additional Specifications | |
| Weight | 80 / 133 kg |
| Operating Conditions | |
| Operation Temperature | 0-40°C |
| Operation Humidity | <95% and non-condensing |
| Altitude | 0 ~ 1500m at full load |
| Noise Level | Less than 62dB @ 1 Meter / Less than 65dB @ 1 Meter |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Sudan
| Market | Sudan |
| Grid authority / regulator | Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum |
| Quotation currency | SDG |
| Support hours timezone | Africa/Khartoum |
| Delivery & installation coverage | Khartoum, Omdurman, Port Sudan, Kassala, Nyala |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Sudan that is Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- True double-conversion: True double-conversion
- Flexible system configuration as 3-in/3-out,: Flexible system configuration as 3-in/3-out, 3-in/1-out or 1-in/1-out
- DSP technology guarantees high performance: DSP technology guarantees high performance
- Output power factor 1.0: Output power factor 1.0
- Active power factor correction in: Active power factor correction in all phases
- 50Hz/60Hz frequency converter mode: 50Hz/60Hz frequency converter mode
- ECO mode operation for energy: ECO mode operation for energy saving (ECO)
- Dual AC inputs: Dual AC inputs
- Emergency power off function (EPO): Emergency power off function (EPO)
- Generator compatible: Generator compatible
- Adjustable battery numbers for long-run: Adjustable battery numbers for long-run model
- Parallel operation up to 4: Parallel operation up to 4 units with common battery
Frequently Asked Questions
What are the main performance specifications of the Galleon III 33/31/11?
The Galleon III 33/31/11 offers a nominal voltage of 3 x 380/400/415VAC or 220/230/240VAC, with a power factor of >= 0.99 at full load. It maintains harmonic distortion below 4% at full linear load and provides a pure sinewave output in battery mode.
Is the Galleon III 33/31/11 compatible with different battery types or solar panels?
The Galleon III 33/31/11 is designed to work seamlessly with various battery types and can be integrated into solar power systems, ensuring flexibility in different power setups.
What are the physical specifications of the Galleon III 33/31/11?
The physical dimensions and weight of the Galleon III 33/31/11 are designed for optimal space utilization and ease of installation, although specific dimensions and weight details are not provided in the key specifications.
What are the installation requirements for the Galleon III 33/31/11?
Installation of the Galleon III 33/31/11 requires a stable environment with proper ventilation and adherence to electrical standards. It should be installed by a qualified technician to ensure safety and optimal performance.
What warranty does the Galleon III 33/31/11 come with?
The Galleon III 33/31/11 comes with a standard warranty that covers defects in materials and workmanship. Specific warranty terms should be confirmed with the retailer or manufacturer.
What certifications does the Galleon III 33/31/11 have?
The Galleon III 33/31/11 is certified with CE, EN 62040-1, IEC 62040-1, and EN 62040-2, ensuring compliance with international safety and performance standards.
What are the operating conditions for the Galleon III 33/31/11?
The Galleon III 33/31/11 operates efficiently within a specific temperature and humidity range, although exact values are not specified. It is designed to function reliably in typical indoor environments.
What are the key features and benefits of the Galleon III 33/31/11?
Key features of the Galleon III 33/31/11 include zero transfer time, pure sinewave output, and high efficiency with a power factor of >= 0.99. These features ensure reliable power supply and protection for sensitive equipment.