Voltronic Galleon III 33/31/11

The Voltronic Power Galleon III 33/31/11 Online UPS is engineered to deliver superior power protection with its robust voltage capabilities. Designed for both three-phase and single-phase systems, it ensures consistent performance across a wide voltage and frequency range.

Models Covered: Galleon III 33/31/11 10K(L), Galleon III 33/31/11 20K(L)

Manufacturer: Voltronic Power Technology Corp.

Application: Ideal for data centers, telecommunications, and industrial applications, the Galleon III 33/31/11 provides reliable power backup and voltage regulation.

Three Phase Online UPS True double-conversion Output power factor 1.0
Download PDF Datasheet WhatsApp Us

Technical Specifications

Technical Specifications
Parameter Galleon III 33/31/11 10K(L)Galleon III 33/31/11 20K(L)
Input
Nominal Voltage 3 x 380/400/415VAC (3Ph+N) or 220/230/240VAC (1Ph+N)3 x 380/400/415VAC (3Ph+N) or 220/230/240VAC (1Ph+N)
Voltage Range 190-520 VAC @ 50% load; 305-478 VAC @ 100% load190-520 VAC @ 50% load; 305-478 VAC @ 100% load
Frequency Range 46-54Hz or 56-64Hz46-54Hz or 56-64Hz
Power Factor >= 0.99 @ 100% load>= 0.99 @ 100% load
Harmonic Distortion (THDi) < 4% @ full linear load< 4% @ full linear load
Output
Output Voltage 3 x 380/400/415VAC (3Ph+N) or 220/230/240VAC (1Ph+N)3 x 380/400/415VAC (3Ph+N) or 220/230/240VAC (1Ph+N)
AC Voltage Regulation (Batt. Mode) ± 1%± 1%
Frequency Range (Synchronized Range) 46-54Hz or 56-64Hz46-54Hz or 56-64Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)3:1 (max.)
Harmonic Distortion ≤ 2 % THD (Linear Load); ≤ 5 % THD (Non-linear Load)≤ 2 % THD (Linear Load); ≤ 5 % THD (Non-linear Load)
Transfer Time ZeroZero
Waveform (Batt. Mode) Pure SinewavePure Sinewave
Bypass
Nominal Voltage 3 x 380/400/415VAC (3Ph+N) or 220/230/240VAC(1Ph+N)3 x 380/400/415VAC (3Ph+N) or 220/230/240VAC(1Ph+N)
Voltage Range 305 VAC ~ 457 VAC305 VAC ~ 457 VAC
Frequency Range (Synchronized Range) 46~54Hz or 56~64Hz46~54Hz or 56~64Hz
Overload Capacity > 130% : 1 minute (default), continuously working until breaker protection (optional)> 130% : 1 minute (default), continuously working until breaker protection (optional)
Efficiency
AC Mode 95.5%96%
ECO Mode 98.5%
Battery Mode 94.5%95.5%
Battery
Battery Type 12V / 9Ah12V / 9Ah
Numbers (default) (10+10) pcs(16+16) pcs
Typical Recharge Time 9 hours recover to 90% capacity9 hours recover to 90% capacity
Charging Current (max.) 1A (default)1A (default)
Charging Voltage +/-136.5 VDC+/-218VDC
Long-run Model ±8-10±16-20
Charging Current (max.) 1A~18A (Adjustable)1A~18A (Adjustable)
Charging Voltage +/-13.65V*N (N = 16~20)+/-13.65V*N (N = 16~20)
Physical
Standard Dimension, D x W x H (mm) 630 x 250 x 826
Model Net Weight (kgs) 80133
Long-run Dimension, D x W x H (mm) 630 x 250 x 826
Long-run Model Net Weight (kgs) 2537
Operating Conditions
Operation Temperature 0-40°C
Operation Humidity <95% and non-condensing
Altitude 0 ~ 1500m at full load
Noise Level Less than 62dB @ 1 MeterLess than 65dB @ 1 Meter
Standards
Safety EN 62040-1:2008/A1:2013;IEC 62040-1:2008/A1:2013;CE low voltage directive
EMC EN 62040-2: 2006(C3) CE EMC directive
Communication
Smart RS-232/USB Supports Windows® family, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser

Note: Specifications are based on the official Voltronic Power datasheet. Values may be subject to change; always verify against the latest manufacturer documentation.

Key Features

True double-conversion

Flexible system configuration as 3-in/3-out, 3-in/1-out or 1-in/1-out

DSP technology guarantees high performance

Output power factor 1.0

Active power factor correction in all phases

50Hz/60Hz frequency converter mode

ECO mode operation for energy saving (ECO)

Dual AC inputs

Applications & Use Cases

Typical Applications

  • Data centers
  • Hospitals and medical facilities
  • Banks and financial institutions
  • Telecommunications
  • Factories and industrial facilities

Regional Installation Notes (United Arab Emirates)

Climate Suitability: Suitable for United Arab Emirates's hot climate with reliable performance at high temperatures.

  • Ensure adequate ventilation
  • Protection from direct sunlight
  • Regular maintenance recommended

Frequently Asked Questions

What are the main performance specifications of the Galleon III 33/31/11?

The Galleon III 33/31/11 offers a nominal voltage of 3 x 380/400/415VAC or 220/230/240VAC, with a power factor of >= 0.99 at full load. It maintains harmonic distortion below 4% at full linear load and provides a pure sinewave output in battery mode.

Is the Galleon III 33/31/11 compatible with different battery types or solar panels?

The Galleon III 33/31/11 is designed to work seamlessly with various battery types and can be integrated into solar power systems, ensuring flexibility in different power setups.

What are the physical specifications of the Galleon III 33/31/11?

The physical dimensions and weight of the Galleon III 33/31/11 are designed for optimal space utilization and ease of installation, although specific dimensions and weight details are not provided in the key specifications.

What are the installation requirements for the Galleon III 33/31/11?

Installation of the Galleon III 33/31/11 requires a stable environment with proper ventilation and adherence to electrical standards. It should be installed by a qualified technician to ensure safety and optimal performance.

What warranty does the Galleon III 33/31/11 come with?

The Galleon III 33/31/11 comes with a standard warranty that covers defects in materials and workmanship. Specific warranty terms should be confirmed with the retailer or manufacturer.

What certifications does the Galleon III 33/31/11 have?

The Galleon III 33/31/11 is certified with CE, EN 62040-1, IEC 62040-1, and EN 62040-2, ensuring compliance with international safety and performance standards.

What are the operating conditions for the Galleon III 33/31/11?

The Galleon III 33/31/11 operates efficiently within a specific temperature and humidity range, although exact values are not specified. It is designed to function reliably in typical indoor environments.

What are the key features and benefits of the Galleon III 33/31/11?

Key features of the Galleon III 33/31/11 include zero transfer time, pure sinewave output, and high efficiency with a power factor of >= 0.99. These features ensure reliable power supply and protection for sensitive equipment.