Technical Specifications
| Parameter | Fortress 3/3 100K | Fortress 3/3 120K | Fortress 3/3 180K | Fortress 3/3 200K | Fortress 3/3 240K | Fortress 3/3 300K | Fortress 3/3 60K | Fortress 3/3 80K |
|---|---|---|---|---|---|---|---|---|
| Output | ||||||||
| Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) | |||||||
| Voltage Regulation (Steady state) | ≤ ± 2% Typical (unbalanced load) | ≤ ± 2% Typical (unbalanced load) | ≤ ± 2% Typical (unbalanced load) | ≤ ± 2% Typical (unbalanced load) | ≤ ± 2% Typical (unbalanced load) | ≤ ± 2% Typical (unbalanced load) | ≤ ± 1% Typical (balanced load) | ≤ ± 2% Typical (unbalanced load) |
| Frequency Range (Synchronized range) | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |||||||
| Overload Capability | ≤ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms | |||||||
| Harmonic Distortion | ≤ 2% THD (Linear Load); ≤ 4% THD (Non-linear Load) | |||||||
| Input | ||||||||
| Voltage Range | 110-300 VAC @ 50% load; 184-276 VAC @100% load | |||||||
| Nominal Frequency | 50/60Hz (Auto sensing) | |||||||
| Frequency Range | 40Hz ~ 70Hz | |||||||
| Power Factor | >= 0.99 @ 100% load | |||||||
| Harmonic Distortion (THDi) | <5% @ 100% load | |||||||
| Efficiency | ||||||||
| AC Mode | 95.5% | 95.5% | 95.5% | 95.5% | 95.5% | 95.5% | 95% | 96% |
| ECO Mode | 98.5% | 98.5% | 98.5% | 98.5% | 98.5% | 98.5% | 98% | 99% |
| Battery Mode | 94.5% | |||||||
| Battery Charging | ||||||||
| Maximum Voltage | +/- 240V (12V x 40 Pcs) | |||||||
| Minimum Voltage | +/- 192V (12V x 32 Pcs) | |||||||
| Floating Charge Voltage | 2.28V / Cell (2.25 ~ 2.33 Selectable) | |||||||
| Boost Charging Voltage | 2.35V/Cell | |||||||
| Maximum Charging Current | 24A (Adjustable) | 36A (Adjustable) | 54A (Adjustable) | 54A (Adjustable) | 72A (Adjustable) | 90A (Adjustable) | 18A (Adjustable) | 18A (Adjustable) |
| Temperature Compensation | Yes | |||||||
| Communication | ||||||||
| Management | Supports Windows® Family, Linux and MAC | |||||||
| Optional SNMP | Power management from SNMP manager and web browser | |||||||
| Certifications | ||||||||
| Safety | IEC/EN 62040-1 | |||||||
| EMC | IEC/EN 62040-2 Category C3 | |||||||
| Physical | ||||||||
| IP Class | IP20, optional IP31 | |||||||
| Dimension, D x W x H (mm) | 1000x430x1200 | 1000x430x1200 | 1000x600x1200 | 1000x600x1200 | 1100x600x1475 | 1100x600x1475 | 1000x320x800 | 1000x430x1200 |
| Net Weight (Kgs) | 169 | 169 | 249 | 249 | 360 | 396 | 94 | 125 |
| Mechanical Data | ||||||||
| Weight | 169 | 169 | 249 | 249 | 360 | 396 | 94 | 125 |
| Operating Conditions | ||||||||
| Operating Temperature | 0-40°C | |||||||
| Operating Humidity | < 95% and non-condensing | |||||||
| Altitude | <1000m for Nominal power | |||||||
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Sudan
| Market | Sudan |
| Grid authority / regulator | Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum |
| Quotation currency | SDG |
| Support hours timezone | Africa/Khartoum |
| Delivery & installation coverage | Khartoum, Omdurman, Port Sudan, Kassala, Nyala |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Sudan that is Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- Backfeed detection built-in: Backfeed detection built-in
- Single power module on/off control: Single power module on/off control through LCD panel
- Pluggable power module design with: Pluggable power module design with front access
- Parallel operation up to 4: Parallel operation up to 4 units with common battery
- Dual-mains inputs: Dual-mains inputs
- Built-in 4 switches including Mains: Built-in 4 switches including Mains input, bypass input, output and maintenance bypass switch
- Flexible battery configuration and adjustable: Flexible battery configuration and adjustable charging current
- Optional extra communication is available: Optional extra communication is available
- Emergency power off function (EPO): Emergency power off function (EPO)
- Generator compatible: Generator compatible
- 50Hz/60Hz frequency converter mode: 50Hz/60Hz frequency converter mode
- Compatible to Lithium-ion battery: Compatible to Lithium-ion battery
Frequently Asked Questions
What are the main performance specifications of the Fortress 3phase UPS?
The Fortress 3phase UPS offers high efficiency with 95% in AC mode, 98% in ECO mode, and 94% in battery mode. It supports a nominal voltage of 3 x 380/400/415 VAC (3Ph+N) and a power factor of >= 0.99 at full load.
Is the Fortress 3phase UPS compatible with different battery types or solar panels?
The Fortress 3phase UPS is designed to be compatible with various battery types. However, it does not directly support solar panels without additional equipment.
What are the physical specifications of the Fortress 3phase UPS?
The specific dimensions and weight of the Fortress 3phase UPS are not provided in the key specifications. Please refer to the product manual or contact Voltronic Power for detailed physical specifications.
What are the installation requirements for the Fortress 3phase UPS?
Installation of the Fortress 3phase UPS requires a stable environment with proper ventilation. It should be installed by a qualified technician to ensure compliance with electrical standards.
What is the warranty period for the Fortress 3phase UPS?
The Fortress 3phase UPS typically comes with a standard warranty period. Please check with Voltronic Power or your supplier for specific warranty terms and conditions.
What certifications and standards does the Fortress 3phase UPS comply with?
The Fortress 3phase UPS complies with IEC/EN 62040-1 and IEC/EN 62040-2 Category C3 standards, ensuring safety and performance reliability.
What are the operating conditions for the Fortress 3phase UPS?
The Fortress 3phase UPS is designed to operate efficiently within a wide frequency range of 40Hz to 70Hz. It should be used in environments with controlled temperature and humidity levels.
What are the key features and benefits of the Fortress 3phase UPS?