Voltronic Fortress 3phase UPS
The Fortress 3phase UPS from Voltronic Power is engineered to deliver robust and reliable power protection for critical applications. With a nominal voltage of 3 x 380/400/415 VAC and auto-sensing frequency, it ensures seamless operation across various environments.
Technical Specifications
| Parameter | 60K | 80K | 100K | 120K | 180K | 200K | 240K | 300K |
|---|---|---|---|---|---|---|---|---|
| Input | ||||||||
| Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) | |||||||
| Voltage Range | 110-300 VAC @ 50% load; 184-276 VAC @100% load | 110-300 VAC @ 50% load; 184-276 VAC @100% load | 110-300 VAC @ 50% load; 184-276 VAC @100% load | 110-300 VAC @ 50% load; 184-276 VAC @100% load | 110-300 VAC @ 50% load; 184-276 VAC @100% load | 110-300 VAC @ 50% load; 184-276 VAC @100% load | 110-300 VAC @ 50% load; 184-276 VAC @100% load | 110-300 VAC @ 50% load; 184-276 VAC @100% load |
| Nominal Frequency | 50/60Hz (Auto sensing) | |||||||
| Frequency Range | 40Hz ~ 70Hz | |||||||
| Power Factor | >= 0.99 @ 100% load | |||||||
| Harmonic Distortion (THDi) | <5% @ 100% load | |||||||
| Output | ||||||||
| Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) | |||||||
| Voltage Regulation (Steady state) | ≤ ± 1% Typical (balanced load) | |||||||
| Nominal Frequency | 50/60Hz | |||||||
| Frequency Range (Synchronized range) | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |||||||
| Overload Capability | ≤ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms | |||||||
| Harmonic Distortion | ≤ 2% THD (Linear Load); ≤ 4% THD (Non-linear Load) | |||||||
| Efficiency | ||||||||
| AC Mode | 95% | 96% | 95.5% | 95.5% | 95.5% | 95.5% | 95.5% | 95.5% |
| ECO Mode | 98% | 99% | 98.5% | 98.5% | 98.5% | 98.5% | 98.5% | 98.5% |
| Battery Mode | 94% | 95.5% | 94.5% | 94.5% | 94.5% | 94.5% | 94.5% | 94.5% |
| Bypass | ||||||||
| Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) | |||||||
| Voltage Range | -30% ~ +20% | |||||||
| Frequency Range | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |||||||
| Overload Capability | ≤ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms | |||||||
| Battery Charging | ||||||||
| Nominal Voltage | +/- 192V ~ +/- 240V (Selectable) | |||||||
| Maximum Voltage | +/- 240V (12V x 40 Pcs) | |||||||
| Minimum Voltage | +/- 192V (12V x 32 Pcs) | |||||||
| Floating Charge Voltage | 2.28V / Cell (2.25 ~ 2.33 Selectable) | |||||||
| Boost Charging Voltage | 2.35V/Cell | |||||||
| Temperature Compensation | Yes | |||||||
| Maximum Charging Current | 18A (Adjustable) | 18A (Adjustable) | 24A (Adjustable) | 36A (Adjustable) | 54A (Adjustable) | 54A (Adjustable) | 72A (Adjustable) | 90A (Adjustable) |
| Physical | ||||||||
| IP Class | IP20, optional IP31 | |||||||
| Dimension, D x W x H (mm) | 1000x320x800 | 1000x430x1200 | 1000x430x1200 | 1000x430x1200 | 1000x600x1200 | 1000x600x1200 | 1100x600x1475 | 1100x600x1475 |
| Net Weight (Kgs) | 94 | 125 | 169 | 169 | 249 | 249 | 360 | 396 |
| Operating Conditions | ||||||||
| Operating Temperature | 0-40°C | |||||||
| Operating Humidity | < 95% and non-condensing | |||||||
| Altitude | <1000m for Nominal power | |||||||
| Communication | ||||||||
| Management | Supports Windows® Family, Linux and MAC | |||||||
| Optional SNMP | Power management from SNMP manager and web browser | |||||||
| Certifications | ||||||||
| Safety | IEC/EN 62040-1 | |||||||
| EMC | IEC/EN 62040-2 Category C3 | |||||||
Note: Specifications are based on the official Voltronic Power datasheet. Values may be subject to change; always verify against the latest manufacturer documentation.
Key Features
Backfeed detection built-in
Single power module on/off control through LCD panel
Pluggable power module design with front access
Parallel operation up to 4 units with common battery
Dual-mains inputs
Built-in 4 switches including Mains input, bypass input, output and maintenance bypass switch
Flexible battery configuration and adjustable charging current
Optional extra communication is available
Applications & Use Cases
Typical Applications
- Data centers
- Hospitals and medical facilities
- Banks and financial institutions
- Telecommunications
- Factories and industrial facilities
Regional Installation Notes (United Arab Emirates)
Climate Suitability: Suitable for United Arab Emirates's hot climate with reliable performance at high temperatures.
- Ensure adequate ventilation
- Protection from direct sunlight
- Regular maintenance recommended
Frequently Asked Questions
What are the main performance specifications of the Fortress 3phase UPS?
The Fortress 3phase UPS offers high efficiency with 95% in AC mode, 98% in ECO mode, and 94% in battery mode. It supports a nominal voltage of 3 x 380/400/415 VAC (3Ph+N) and a power factor of >= 0.99 at full load.
Is the Fortress 3phase UPS compatible with different battery types or solar panels?
The Fortress 3phase UPS is designed to be compatible with various battery types. However, it does not directly support solar panels without additional equipment.
What are the physical specifications of the Fortress 3phase UPS?
The specific dimensions and weight of the Fortress 3phase UPS are not provided in the key specifications. Please refer to the product manual or contact Voltronic Power for detailed physical specifications.
What are the installation requirements for the Fortress 3phase UPS?
Installation of the Fortress 3phase UPS requires a stable environment with proper ventilation. It should be installed by a qualified technician to ensure compliance with electrical standards.
What is the warranty period for the Fortress 3phase UPS?
The Fortress 3phase UPS typically comes with a standard warranty period. Please check with Voltronic Power or your supplier for specific warranty terms and conditions.
What certifications and standards does the Fortress 3phase UPS comply with?
The Fortress 3phase UPS complies with IEC/EN 62040-1 and IEC/EN 62040-2 Category C3 standards, ensuring safety and performance reliability.
What are the operating conditions for the Fortress 3phase UPS?
The Fortress 3phase UPS is designed to operate efficiently within a wide frequency range of 40Hz to 70Hz. It should be used in environments with controlled temperature and humidity levels.
What are the key features and benefits of the Fortress 3phase UPS?
Key features of the Fortress 3phase UPS include high efficiency, robust voltage regulation, and excellent overload capability. These features ensure reliable power supply and protection for critical systems.