Voltronic Power Solutions

Voltronic AXPERT-MAX-II-TWIN-11/VOLTRONIC-AXPERT-MAX-II-TWIN-12/VOLTRONIC-AXPERT-MAX-II-TWIN-8/AXPERT-MAX-II-TWIN-8K

The Axpert MAX II TWIN 11K is an off-grid solar inverter rated Axpert MAX II TWIN 11K.

Models Covered: AXPERT-MAX-II-TWIN-11K, AXPERT-MAX-II-TWIN-12K, VOLTRONIC-AXPERT-MAX-II-TWIN-11K, VOLTRONIC-AXPERT-MAX-II-TWIN-12K, VOLTRONIC-AXPERT-MAX-II-TWIN-8K, AXPERT-MAX-II-TWIN-8K

Manufacturer: Voltronic Power

Application: The Axpert MAX II TWIN 11K is an off-grid solar inverter rated Axpert MAX II TWIN 11K. Every figure on this page is read from the manufacturer's manual for the Axpert MAX II TWIN series.

Technical Specifications

Technical Specifications
Parameter AXPERT-MAX-II-TWIN-11KAXPERT-MAX-II-TWIN-12KVOLTRONIC-AXPERT-MAX-II-TWIN-11KVOLTRONIC-AXPERT-MAX-II-TWIN-12KVOLTRONIC-AXPERT-MAX-II-TWIN-8KAXPERT-MAX-II-TWIN-8K
Additional Specifications
Parallel Capability YES, 6 units
Selectable Voltage Range 170-280 VAC (For Personal Computers)
AC Voltage Regulation (Batt. Mode) 230VAC ± 5%
Efficiency (Peak) 93%
Maxmum Solar Charge Current 150A200A150A
High Loss Frequency 65±1Hz
High Loss Return Frequency 63±1Hz
High Loss Return Voltage 270Vac±7V
High Loss Voltage 280Vac±7V
Low Loss Frequency 40±1Hz
Low Loss Return Frequency 42±1Hz
Low Loss Return Voltage 180Vac±7V (UPS); 100Vac±7V (Appliances)
Low Loss Voltage 170Vac±7V (UPS) 90Vac±7V (Appliances)
Max AC Input Voltage 300Vac
Max. PV Array Open Circuit Voltage 500Vdc
Nominal Input Frequency 50Hz/60Hz (Auto detection)
Output Short Circuit Protection Line mode: Circuit Breaker (70A) Battery mode: Electronic Circuits
PV Array MPPT Voltage Range 90Vdc 450Vdc
Start-up Voltage 80V +/- 5Vdc
Low DC Cut-off Voltage 44Vdc
Nominal DC Input Voltage 48Vdc
Cold Start Voltage 46.0Vdc
Floating Charging Voltage 54Vdc
Input Voltage Waveform Sinusoidal (utility or generator) Nominal
Output Charge Time to
Overload Protection Surge
Safety Certification CE
Parallel Kit YES
Parallel communication CAN
Output Power For 8KW model, when
Operating Temperature -10°C to 50°C
Charging Current 150A UPS
Efficiency (Line Mode) >95% (Rated R load, battery full charged)
Max AC Input Current 60A
Nominal Input Voltage 230Vac
Max parallel numbers 6
DC Offset ≤100mV
Peak Efficiency 93%
Efficiency >95% ( Rated R load Line Mode
Output Frequency 60Hz or 50Hz Peak
Output Voltage Regulation 230Vac± 5%
Operating Temperature Range -10°C to 50°C
Circulation Current under No Load Condition Max 2A
Transfer time in parallel mode Max 50ms
Max 2nd Output Current 40A
Max Output Current for 2nd output 40A
Physical
Communication Interface USB/RS232/RS485/WiFi/Dry-contact
Dimension, D x W x H (mm) 158.4 x 503.6 x 530.8
Net Weight (kgs) 20
Certifications
Compliance Safety IEC 62109, IEC 61683, EN/IEC 61000-6-2, 61000-6-4, 61000-3-11, 61000-3-12
AC Output
Rated Power 11000VA/11000W12000VA/12000W11000W Max. PV Array Open Circuit12000VA/12000W8000W Max. PV Array Open Circuit8000VA/8000W
Surge Power 22000VA24000VA22000VA24000VA16000VA16000VA
Waveform Pure sine wave
Transfer Time 10ms typical (UPS);10 ms (For Personal Computers) ; 20 ms (For Home Appliances)10ms typical (UPS);
Solar Charger & AC Charger
Maximum PV Array Power 13000W (6500W x 2)18000W (Max. 12000W per tracker)13000W (6500W x 2)18000W (Max. 12000W per tracker)11000W (5500W x 2)11000W (5500W x 2)
Maximum AC Charge Current 150A200A150A200A120A120A
Maximum Charge Current 150A200A150A200A150A150A
Solar Charger Type MPPT
MPPT Range @ Operating Voltage 90 – 450 VDC
Maximum PV Array Open Circuit Voltage 500 VDC
Maximum PV Input Current 40A/27A (MAX 60A)40A/27A (MAX 60A)27A x 2 (MAX 40A)
Maximum Solar Charge Current 150A200A150A
Operating Conditions
Humidity 5% to 95%5% to 95%5% to 95%5% to 95% Relative Humidity (Non-condensing)5% to 95%5% to 95%
Storage Temperature -15°C to 60°C-15°C to 60°C-15°C~ 60°C-15°C to 60°C-15°C~ 60°C-15°C to 60°C
Electrical / AC Output Data
Max. Charging Current 150A120A
Max. Input Current 27A x 2(MAX 40A)27A x 2 (MAX 40A)
High DC Cut-off Voltage 63Vdc66Vdc
High DC Recovery Voltage 61Vdc64Vdc
DC Voltage DC Offset ≦100mV Power Limitation 55VdcDC Offset ≦100mV Power Limitation 50Vdc
Rated Output Power 11000W8000W
Battery
Overcharge Protection 63Vdc Charging Algorithm 3-Step Charging Curve Time63 VDC66Vdc Charging Algorithm 3-Step Charging Curve Time66 VDC
Battery Voltage 48 VDC
Floating Charge Voltage 54 VDC

Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.

Availability & grid compliance in Sudan

Market Sudan
Grid authority / regulator Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum
Quotation currency SDG
Support hours timezone Africa/Khartoum
Delivery & installation coverage Khartoum, Omdurman, Port Sudan, Kassala, Nyala

Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Sudan that is Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.

Key Features & Technical Highlights

  • Increased PV power: Increased PV power
  • Touchable button with 5" color: Touchable button with 5" color LCD
  • Status indication with RGB lights: Status indication with RGB lights
  • Dual outputs for smart load: Dual outputs for smart load management
  • Upgrade maximum PV current to: Upgrade maximum PV current to 60A for 12K model
  • Built-in WiFi with APP for: Built-in WiFi with APP for mobile monitoring and OTA firmware upgrade
  • Supports USB On-the-Go function: Supports USB On-the-Go function
  • Built-in BMS communication port: Built-in BMS communication port
  • Built-in meter calibration for optimized: Built-in meter calibration for optimized system operation
  • Battery independent design: Battery independent design
  • Built-in anti-dust kit: Built-in anti-dust kit
  • Built-in DC output for DC: Built-in DC output for DC fan, LED bulb, router and so on

Frequently Asked Questions

What are the main performance specifications of the Axpert MAX II TWIN?

The Axpert MAX II TWIN has a rated power of 11000VA/11000W with a peak efficiency of 93%. It provides a pure sine wave output with an AC voltage regulation of 230VAC ± 5% in battery mode.

Is the Axpert MAX II TWIN compatible with different battery types and solar panels?

Yes, the inverter is compatible with a 48 VDC battery system and supports MPPT solar chargers with a maximum PV array power of 11000W, making it suitable for various solar panel configurations.

What are the physical specifications of the Axpert MAX II TWIN?

The physical dimensions and weight of the Axpert MAX II TWIN are not specified here, but it is designed to be robust and suitable for residential and commercial installations. Please refer to the product manual for detailed dimensions and weight.

What are the installation requirements for the Axpert MAX II TWIN?

Installation should be performed by a qualified technician. Ensure that the inverter is installed in a well-ventilated area, away from direct sunlight and moisture, and that all electrical connections comply with local regulations.

What warranty does Voltronic Power offer for the Axpert MAX II TWIN?

Voltronic Power typically offers a standard warranty for its products, but specific warranty terms for the Axpert MAX II TWIN should be confirmed with the retailer or distributor.

What certifications does the Axpert MAX II TWIN have?

The Axpert MAX II TWIN is certified under IEC 62109, IEC 61683, EN/IEC 61000-6-2, 61000-6-4, 61000-3-11, and 61000-3-12, ensuring compliance with international safety and performance standards.

What are the operating conditions for the Axpert MAX II TWIN?

The inverter is designed to operate efficiently within a specific temperature and humidity range. For optimal performance, ensure the environment is within the recommended conditions as specified in the product manual.

What are the key features and benefits of the Axpert MAX II TWIN?

Key features include a high surge power of 22000VA, fast transfer time of 10 ms for PCs, and 20 ms for home appliances, along with MPPT solar charging capabilities, making it ideal for both residential and commercial use.