Voltronic Power Solutions

Voltronic VICTOR-1U-6K-UPS

Discover the Victor 1U 6K UPS by Voltronic Power with 208-240VAC output and precise voltage regulation of ±1%.

Models Covered: VOLTRONIC-VICTOR-1U-6K-UPS

Manufacturer: Voltronic Power Technology Corp.

Application: The Victor 1U 6K UPS by Voltronic Power is engineered to deliver reliable power protection with a nominal voltage range of 208 to 240VAC. Its robust design ensures consistent performance, making it an ideal choice for critical applications. The Victor 1U 6K UPS is perfect for data centers, telecommunications, and industrial environments where stable power is crucial.

Technical Specifications

Technical Specifications
Parameter VOLTRONIC-VICTOR-1U-6K-UPS
Input
Nominal Voltage 208/220/230/240VAC
Voltage Range 110-300VAC ± 3% @ 50% load; 176-300VAC ± 3% @ 100% load
Frequency Range 46-54Hz; 56-64Hz
Power Factor ≥ 0.99 @ nominal voltage (100% load)
THDi ≤ 4% @ 100% load
Output
Output Voltage 208/220/230/240VAC
Voltage Regulation ± 1%
Frequency Range (Synchronized Range) 46-54 Hz or 56-64 Hz
Frequency Range (Batt. Mode) 50 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1max
Harmonic Distortion ≤ 2 % THD (Linear Load) / ≤ 4% THD (Non-linear Load)
Transfer Time 0 ms
Waveform (Batt. Mode) Pure Sinewave
Overload AC Mode 100% ≤ load ≤ 105% Warning only; 105%< load ≤ 125%: 1min; >125%: 1 sec
Efficiency
AC Mode 95% (max.)
Battery Mode 93% (max.)
Battery
Charging Current 1A, 2A, 4A (default), 6A
Charging Voltage 219 VDC ± 1%
Battery Connector 2 Poles (50A max.)
Indicators & Communication
LCD Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
Communication USB, Communication Slot
Emergency Power Off (EPO) YES
Physical
Dimension, D x W x H (mm) 520 x 438 x 44
Net Weight (kgs) 9.8
Operating Conditions
Humidity 0-95% RH @ 0-40°C (non-condensing)
Altitude 0-2000 meters without derating; 2000-3000 meters derating 1% every 100meters; >3000 meters: not working
Noise Level Less than 55dBA @ 1 Meter

Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.

Availability & grid compliance in Yemen

Market Yemen
Grid authority / regulator Public Electricity Corporation (PEC), Ministry of Electricity and Energy
Quotation currency YER
Support hours timezone Asia/Aden
Delivery & installation coverage Sana'a, Aden, Taiz, Al Hudaydah, Mukalla

Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Yemen that is Public Electricity Corporation (PEC), Ministry of Electricity and Energy. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.

Key Features & Technical Highlights

  • True double-conversion: True double-conversion
  • Microprocessor control optimizes reliability: Microprocessor control optimizes reliability
  • Input power factor correction: Input power factor correction
  • Output power factor 0.9: Output power factor 0.9
  • Wide input voltage (110V –: Wide input voltage (110V – 300V)
  • Converter mode available: Converter mode available
  • ECO mode for energy saving: ECO mode for energy saving
  • Generator compatible: Generator compatible
  • Smart SNMP and USB communication: Smart SNMP and USB communication
  • 10C high discharging rate on: 10C high discharging rate on Lithium-ion battery module, high efficiency with 1U compact size
  • Comprehensive display allows easy monitoring: Comprehensive display allows easy monitoring and access of UPS

Frequently Asked Questions

What are the main performance specifications of the Victor 1U 6K UPS?

The Victor 1U 6K UPS operates at a nominal voltage of 208/220/230/240VAC with a power factor of ≥ 0.99 at 100% load. It offers a frequency range of 46-54Hz or 56-64Hz and maintains a voltage regulation of ± 1%.

Is the Victor 1U 6K UPS compatible with different battery types or solar panels?

The Victor 1U 6K UPS is primarily designed for grid compatibility and does not directly support solar panels. It is compatible with standard UPS batteries.

What are the physical specifications of the Victor 1U 6K UPS?

The physical dimensions and weight of the Victor 1U 6K UPS are designed to fit standard 1U rack spaces. Specific dimensions and weight details are available in the product manual.

What are the installation requirements for the Victor 1U 6K UPS?

Installation requires a standard 1U rack space and appropriate electrical connections. Ensure proper ventilation and avoid exposure to extreme temperatures.

What warranty does the Victor 1U 6K UPS come with?

The Victor 1U 6K UPS comes with a standard warranty that covers manufacturing defects. Specific warranty terms can be found in the warranty documentation.

What certifications and standards does the Victor 1U 6K UPS meet?

The Victor 1U 6K UPS meets standard certifications for safety and performance, ensuring reliable operation in various environments.

What are the operating conditions for the Victor 1U 6K UPS?

The UPS is designed to operate efficiently in a temperature range of 0°C to 40°C and a humidity range of 0% to 95% non-condensing.

What are the key features and benefits of the Victor 1U 6K UPS?

Key features include zero transfer time, pure sinewave output in battery mode, and a high efficiency of up to 95% in AC mode, providing reliable power protection.