Voltronic Power +Power 30U-120HV / +Power 30U-180HV / +Power 30U-90HV / +Power 42U-120HV / +Power 42U-200-20KHV / +Power 42U-210HV
Discover Voltronic Power's +Power 30U-120HV with 3 x 380VAC/400VAC/415VAC, ideal for stable power solutions.
Technical Specifications
| Parameter | +Power 30U-120HV | +Power 30U-180HV | +Power 30U-90HV | +Power 42U-120HV | +Power 42U-200-20KHV | +Power 42U-210HV |
|---|---|---|---|---|---|---|
| Output | ||||||
| Nominal Voltage | 3 x 380VAC/400VAC/415VAC (3PH+N) | |||||
| Voltage Regulation (Steady state) | ≤ ± 1% Typical (balanced load); ≤ ± 2% Typical (imbalanced load) | |||||
| Frequency Range (Synchronized) | 46Hz – 54Hz or 56Hz – 64Hz | |||||
| Overload Capability | 1 hour for 110%, 10 mins for 125%, 1 min for 150%, 200ms for >150% | |||||
| Harmonic Distortion | ≤ 2% THD (Linear Load); ≤ 4% THD (Non-linear Load) | |||||
| Efficiency | Up to 94.5% | |||||
| Input | ||||||
| Voltage Range | 305 - 478 VAC @ 100% load; 208 - 478VAC @ 70% load | |||||
| Nominal Frequency | 50/60Hz (Auto Sensing) | |||||
| Frequency Range | 40Hz – 70Hz | |||||
| Power Factor | > 0.99 @ 100% Load, >0.98 @ 50% Load | |||||
| Harmonic Distortion (THDi) | < 3% @ 100% load | |||||
| Battery Charging | ||||||
| Maximum Voltage | +/- 240V (12V x 40 pcs) | |||||
| Minimum Voltage | +/- 192V (12V x 32 pcs) | |||||
| Float Charging Voltage | 2.25V / Cell | |||||
| Boost Charging Voltage | 2.35V / Cell | |||||
| Maximum Charging Current (Per Power Module) | 6A for 20KW power module | 6A for 20KW power module | 8A for 30KW power module | 6A for 20KW power module | 6A for 20KW power module | 6A for 20KW power module |
| Temperature Compensation | Yes | |||||
| Communication | ||||||
| Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC | |||||
| Optional SNMP | Power management from SNMP manager and web browser | |||||
| Certifications | ||||||
| Safety | IEC/EN 60950-1; IEC/EN 62040-1 | |||||
| EMC | IEC/EN 62040-2 Category C3 | |||||
| Physical | ||||||
| Cabinet Dimension (D x W x H) mm | 1100 x 600 x 1475 | 1100 x 600 x 1475 | 1100 x 600 x 1475 | 1100 x 600 x 2010 | 1100 x 600 x 1475 | 1100 x 600 x 2010 |
| Net Weight (kg) | 335 or 333 | 437.5 or 434.5 | 675 | 932 | 611 | 549 |
| Mechanical Data | ||||||
| Weight | 335 or 333 | 437.5 or 434.5 | 675 | 932 | 611 | 549 |
| Operating Conditions | ||||||
| Operating Temperature | 0 – 40°C | |||||
| Relative Humidity | 0 – 95% non-condensing | |||||
| Altitude | <1000m for Nominal power | |||||
| IP Protection | IP 20 | |||||
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Sudan
| Market | Sudan |
| Grid authority / regulator | Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum |
| Quotation currency | SDG |
| Support hours timezone | Africa/Khartoum |
| Delivery & installation coverage | Khartoum, Omdurman, Port Sudan, Kassala, Nyala |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Sudan that is Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- High efficiency online double conversion: High efficiency online double conversion technology
- Unity output power factor: Unity output power factor
- Modular design lowers MTTR: Modular design lowers MTTR
- N+1 or N+X parallel redundancy: N+1 or N+X parallel redundancy for power guarantee
- Ease of installation and maintenance: Ease of installation and maintenance
- Flexible battery configuration adapts different: Flexible battery configuration adapts different applications
- Highly reliable operation with redundant: Highly reliable operation with redundant power supply in STS
- User-adjustable charging current: User-adjustable charging current
- High overload capability: High overload capability
- Graphic 5.7” LCD design for: Graphic 5.7” LCD design for easy management
- Optional 10" touch LCD panel: Optional 10" touch LCD panel
Frequently Asked Questions
What are the main performance specifications of the +Power Modular UPS?
The +Power Modular UPS offers a high efficiency of up to 94.5% and supports a nominal voltage of 3 x 380VAC/400VAC/415VAC (3PH+N). It maintains a power factor greater than 0.99 at full load and harmonic distortion of less than 3% at 100% load.
Is the +Power Modular UPS compatible with different battery types and solar panels?
Yes, the UPS is compatible with a nominal battery voltage of +/- 216V, consisting of 12V x 36 pcs, and can support a maximum voltage of +/- 240V with 12V x 40 pcs. It can be integrated with solar panels and the grid for enhanced power solutions.
What are the physical specifications of the +Power Modular UPS?
The physical dimensions and weight of the +Power Modular UPS can vary based on the specific configuration and modules used. Please refer to the detailed product manual for precise measurements and weight.
What are the installation requirements for the +Power Modular UPS?
Installation requires a stable environment with appropriate ventilation. The UPS should be installed by a certified technician to ensure compliance with safety standards and optimal performance.
What warranty is offered with the +Power Modular UPS?
Voltronic Power offers a standard warranty period for the +Power Modular UPS, which typically covers parts and labor. Specific warranty terms can vary, so it's advisable to consult the purchase agreement or contact customer support for detailed information.
What certifications and standards does the +Power Modular UPS adhere to?
The +Power Modular UPS is certified under IEC/EN 60950-1, IEC/EN 62040-1, and IEC/EN 62040-2 Category C3, ensuring compliance with international safety and performance standards.
What are the operating conditions for the +Power Modular UPS?
The UPS is designed to operate efficiently in a temperature range that supports optimal performance. It is important to maintain humidity levels within recommended limits to ensure reliability and longevity.
What are the key features and benefits of the +Power Modular UPS?
Key features include high efficiency, robust overload capability, and low harmonic distortion. These benefits ensure reliable power supply, reduced energy costs, and enhanced protection for connected equipment.