Voltronic Galleon III
The Galleon III by Voltronic Power is a state-of-the-art UPS designed to deliver reliable power protection with a nominal voltage range of 208 to 240 VAC. It ensures precise voltage regulation and frequency stability, making it an ideal choice for sensitive electronic equipment.
Technical Specifications
| Parameter | Galleon III 6K(L) | Galleon III 10K(L) |
|---|---|---|
| Input | ||
| Nominal Voltage | 208/220/230/240 VAC | 208/220/230/240 VAC |
| Voltage Range | 110~300VAC ± 3% at 60% load; 176~300VAC ± 3% at 100% load | 110~300VAC ± 3% at 60% load; 176~300VAC ± 3% at 100% load |
| Frequency Range | 46~54 Hz or 56~64 Hz | 46~54 Hz or 56~64 Hz |
| Power Factor | ≥ 0.99 @ full load | ≥ 0.99 @ full load |
| THDi | < 4% @100% R load | < 4% @100% R load |
| Output | ||
| Output Voltage | 208/220/230/240 VAC | 208/220/230/240 VAC |
| AC Voltage Regulation (Batt. Mode) | ± 1% | ± 1% |
| Frequency Range (Synchronized Range) | 46~54 Hz or 56~64 Hz | 46~54 Hz or 56~64 Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) | 3:1 (max.) |
| Harmonic Distortion | ≤ 1 % THD (Linear Load) ; ≤ 4 % THD (Non-linear Load) | ≤ 1 % THD (Linear Load) ; ≤ 4 % THD (Non-linear Load) |
| Transfer Time | Zero | Zero |
| Waveform (Batt. Mode) | Pure Sinewave | Pure Sinewave |
| Overload | 100-110% for 60 min, 110-125% for 10 min, 125%-150% 1min, >150% immediately switch to bypass | 100-110% for 60 min, 110-125% for 10 min, 125%-150% 1min, >150% immediately switch to bypass |
| Efficiency | ||
| AC Mode | 95% | 95% |
| Battery Mode | 92% | 92% |
| Battery | ||
| Battery Type | 12 V / 7 Ah | 12 V / 9 Ah |
| Numbers | 16 | 20 |
| Typical Recharge Time | 7 hours recover to 90% capacity | 9 hours recover to 90% capacity |
| Charging Current (max.) | 1 A ± 10% (Default) | 1 A ± 10% (Default) |
| Charging Voltage | 218.4 VDC ± 1% | 240 VDC ± 1% |
| Battery Type | Sealed, lead-acid battery | Sealed, lead-acid battery |
| Physical | ||
| Dimension, D×W×H (mm) | 369 × 190 × 688 | 442 × 190 × 688 |
| Net Weight (kgs) | 55 | 74 |
| Operating Conditions | ||
| Operating Humidity | <95 % RH @ 0- 40°C (Non-condensing) | <95 % RH @ 0- 40°C (Non-condensing) |
| Noise Level | Less than 55dB @1Meter | Less than 55dB @1Meter |
| Communication | ||
| Standard RS-232/USB | Supports Windows® Family, Linux and MAC | Supports Windows® Family, Linux and MAC |
| Optional SNMP | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser |
Note: Specifications are based on the official Voltronic Power datasheet. Values may be subject to change; always verify against the latest manufacturer documentation.
Key Features
Advanced DSP control technology
Ultra-wide voltage input range
High power density with optimized structural design
Self-diagnostics and hidden fault detection
Green Power Bidirectional Protection
Applications & Use Cases
Typical Applications
- Data centers
- Hospitals and medical facilities
- Banks and financial institutions
- Telecommunications
- Factories and industrial facilities
Regional Installation Notes (Oman)
Climate Suitability: Suitable for Oman's hot climate with reliable performance at high temperatures.
- Ensure adequate ventilation
- Protection from direct sunlight
- Regular maintenance recommended
Frequently Asked Questions
What are the main performance specifications of the Galleon III UPS?
The Galleon III UPS offers a nominal voltage of 208/220/230/240 VAC with a power factor of ≥ 0.99 at full load. It ensures high efficiency with a THDi of less than 4% at 100% load and provides a pure sinewave output in battery mode.
Is the Galleon III compatible with different battery types and solar panels?
The Galleon III is designed to work seamlessly with various battery types and can be integrated into solar panel systems, making it versatile for different power setups.
What are the physical specifications of the Galleon III UPS?
The physical dimensions and weight of the Galleon III UPS are designed for easy installation and integration into existing systems. However, specific dimensions and weight details should be confirmed with the manufacturer.
What are the installation requirements for the Galleon III UPS?
Installation of the Galleon III UPS requires a stable environment with proper ventilation. It should be installed by a qualified technician to ensure optimal performance and safety.
What warranty is provided with the Galleon III UPS?
Voltronic Power offers a standard warranty for the Galleon III UPS, covering manufacturing defects and ensuring reliable performance. Specific warranty terms should be verified with the supplier.
What certifications does the Galleon III UPS have?
The Galleon III UPS is ROHS certified, ensuring compliance with environmental and safety standards.
What are the operating conditions for the Galleon III UPS?
The Galleon III UPS operates efficiently in a wide range of temperatures and humidity levels, ensuring reliable performance in various environmental conditions.
What are the key features and benefits of the Galleon III UPS?
Key features of the Galleon III UPS include zero transfer time, pure sinewave output, and high overload capacity, providing uninterrupted power and protection for sensitive equipment.