Voltronic Giant II 3P/3P

The Voltronic Power Giant II 3P/3P UPS is engineered to deliver robust and reliable power management solutions. With a 6 pulse rectifier and a nominal voltage range of 380VAC to 415VAC, it ensures optimal performance for critical applications.

Models Covered: Giant II 10K, Giant II 15K, Giant II 20K, Giant II 30K, Giant II 40K, Giant II 60K, Giant II 80K, Giant II 100K, Giant II 120K, Giant II 160K

Manufacturer: Voltronic Power Technology Corp.

Application: Ideal for data centers, industrial facilities, and telecommunications, the Giant II 3P/3P UPS provides consistent power protection and efficiency.

Three Phase Online UPS
Download PDF Datasheet WhatsApp Us

Technical Specifications

Technical Specifications
Parameter Giant II 10KGiant II 15KGiant II 20KGiant II 30KGiant II 40KGiant II 60KGiant II 80KGiant II 100KGiant II 120KGiant II 160K
Input
Rectifier Type 6 pulse6 pulse6 pulse6 pulse6 pulse6 pulse12 pulse12 pulse12 pulse12 pulse
Nominal Voltage 380VAC/400VAC/415VAC
Acceptable Voltage Range 304VAC – 456VAC
Frequency 50Hz ± 10%
TVSS 40kA (optional)
Bypass
Nominal Voltage 380VAC/400VAC/415VAC
Input Voltage Range 285VAC – 475VAC
Battery
Battery Voltage 384 VDC (adjustable)
Cold Start Yes
Output
Power Factor 0.9, customized up to 1.0
Nominal Output Voltage 380VAC/400VAC/415VAC
Output Voltage Regulation ±1%
Overload Capability 110% continuous running; 125% for 10 min; >150% for 1 min
Physical
IP Protection IP31 (default), IP42 (optional)
Dimensions (DxWxH) mm 656 x 405 x 817656 x 405 x 941818 x 432 x 1159971 x 554 x 1290971 x 635 x 13261051 x 705 x 1646
Net Weight (Kgs) 120145193278365471573650735790
Operating Conditions
Operating Temperature 0 – 50°C
Storage Temperature -25°C – 55°C
Humidity 0–95% (non-condensing)
Altitude 1000m
Communication
Modbus RS-232/RS-485 Supports Windows® family, Linux and MAC
Dry Contacts 5 outputs and 4 inputs
Optional SNMP Power management from SNMP manager and web browser
Certifications
Safety IEC62040-1:2017

Note: Specifications are based on the official Voltronic Power datasheet. Values may be subject to change; always verify against the latest manufacturer documentation.

Key Features

True online double conversion with DSP control

Output power factor 0.9, customized up to 1.0

Galvanic isolation eliminates common mode noise

Conformal coating ensures operation stability

Standard IP31 protection, optional IP42

Sustains long-term operation for all types of loads

Redundant design for reliability

Temperature compensation to prolong battery life

Applications & Use Cases

Typical Applications

  • Data centers
  • Hospitals and medical facilities
  • Banks and financial institutions
  • Telecommunications
  • Factories and industrial facilities

Regional Installation Notes (United Arab Emirates)

Climate Suitability: Suitable for United Arab Emirates's hot climate with reliable performance at high temperatures.

  • Ensure adequate ventilation
  • Protection from direct sunlight
  • Regular maintenance recommended

Frequently Asked Questions

What are the main performance specifications of the Giant II 3P/3P UPS?

The Giant II 3P/3P UPS features a power factor of 0.9, which can be customized up to 1.0. It operates with a nominal voltage of 380VAC/400VAC/415VAC and maintains output voltage regulation within ±1%.

Is the Giant II 3P/3P UPS compatible with different battery types or solar panels?

The UPS is designed to work with a battery voltage of 384 VDC, which is adjustable. It does not directly support solar panels but can be integrated into systems that include solar power with appropriate converters.

What are the physical specifications of the Giant II 3P/3P UPS?

The dimensions of the UPS are 656 x 405 x 817 mm. It has an IP31 protection rating by default, with an optional upgrade to IP42 for enhanced protection.

What are the installation requirements for the Giant II 3P/3P UPS?

Installation requires a stable environment with an input voltage range of 285VAC to 475VAC. Ensure adequate space for ventilation and maintenance access.

What warranty is offered with the Giant II 3P/3P UPS?

Voltronic Power typically offers a standard warranty period for their UPS products, but specific terms should be confirmed with the retailer or distributor.

What certifications and standards does the Giant II 3P/3P UPS comply with?

The UPS complies with the IEC62040-1:2017 standard, ensuring it meets international safety and performance requirements.

What are the operating conditions for the Giant II 3P/3P UPS?

The UPS is designed to operate efficiently within a frequency range of 50Hz ± 10%. It should be used in environments with controlled temperature and humidity to ensure optimal performance.

What are the key features and benefits of the Giant II 3P/3P UPS?

Key features include a cold start capability and overload capability of 110% continuous running, 125% for 10 minutes, and over 150% for 1 minute. These features ensure reliability and flexibility in power management.