Voltronic Galleon II 3P/3P 10-20KVA, III 3P/3P 30-40KVA
Voltronic Power's Galleon II and III UPS systems are engineered for superior performance with 3P/3P configurations ranging from 10KVA to 40KVA. These systems ensure reliable power with precise voltage regulation and adaptable frequency ranges, making them ideal for critical applications.
Technical Specifications
| Parameter | 10K (L) | 20K (L) | 30K (L) | 40K (L) |
|---|---|---|---|---|
| Input | ||||
| Nominal Voltage | 3 x 400 VAC (3Ph+N) / 230 VAC (1Ph+N) | 3 x 360/380/400/415 VAC (3Ph+N) | ||
| Voltage Range | 110-300 VAC ± 3 % @ 50% load; 176-276 VAC ± 3 % @ 100% load | 305VAC~457VAC | ||
| Frequency Range | 46-54 Hz or 56-64Hz | 40-70 Hz | ||
| Power Factor | > 0.99 @ 100% Load | N/A | ||
| Harmonic Distortion (THDi) | < 4% at full linear load | N/A | ||
| Output | ||||
| AC Voltage Regulation (Batt. Mode) | ± 1% | N/A | ||
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | N/A | ||
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50/60 Hz ± 1% | ||
| Current Crest Ratio | 3:1 (max.) | N/A | ||
| Harmonic Distortion | ≤ 2% THD (Linear Load) ; ≤ 5 % THD (Non-linear Load) | N/A | ||
| Transfer Time | Zero | N/A | ||
| Waveform (Batt. Mode) | Pure Sine wave | N/A | ||
| Overload AC Mode | 100-110% for 60 min, 111-125% for 10 min, 126%-150% for 1 min; >150% immediately shutdown | N/A | ||
| Efficiency | ||||
| AC Mode | 95.5% | N/A | ||
| ECO Mode | 98.5% | N/A | ||
| Battery Mode | 94.5% | N/A | ||
| Battery | ||||
| Battery Type | 12V/9Ah | N/A | ||
| Numbers | (10+10) pcs | (16+16) pcs x 2 | ||
| Standard Model Recharge Time | 9 hours recover to 90% capacity | N/A | ||
| Charging Current (max.) | 1A (Default) | 2A (Default) | ||
| Charging Voltage | +/-136.5 VDC | +/-218 VDC | ||
| Physical | ||||
| Standard Model Dimension, DxWxH (mm) | 630 x 250 x 826 | 815 x 300 x 1000 | ||
| Net Weight (kgs) | 139 | 207 | ||
| Operating Conditions | ||||
| Operation Temperature | 0-40°C | N/A | ||
| Operation Humidity | < 95% and non-condensing | N/A | ||
| Altitude | 0 – 1500m at full load | N/A | ||
| Communication | ||||
| Smart RS-232 / USB | Supports Windows® Family, Linux and MAC | N/A | ||
| Optional SNMP | Power management from SNMP manager and web browser | N/A | ||
Note: Specifications are based on the official Voltronic Power datasheet. Values may be subject to change; always verify against the latest manufacturer documentation.
Key Features
True double-conversion
DSP technology guarantees high performance
Output power factor 1
Active power factor correction in all phases
50Hz/60Hz frequency converter mode
Dual AC inputs
Emergency power off function (EPO)
Generator compatible
Applications & Use Cases
Typical Applications
- Data centers
- Hospitals and medical facilities
- Banks and financial institutions
- Telecommunications
- Factories and industrial facilities
Regional Installation Notes (United Arab Emirates)
Climate Suitability: Suitable for United Arab Emirates's hot climate with reliable performance at high temperatures.
- Ensure adequate ventilation
- Protection from direct sunlight
- Regular maintenance recommended
Frequently Asked Questions
What are the main performance specifications of the Galleon II and III UPS systems?
The Galleon II and III UPS systems offer high efficiency with AC mode at 95.5% and ECO mode at 98.5%. They support a nominal voltage of 3 x 400 VAC and maintain a power factor greater than 0.99 at full load.
Are these UPS systems compatible with different battery types or solar panels?
The Galleon series is designed to be compatible with a wide range of battery types. However, specific compatibility with solar panels should be confirmed with Voltronic Power support.
What are the physical specifications of these UPS systems?
The physical dimensions and weight vary depending on the model. For precise details, please refer to the product manual or contact Voltronic Power.
What are the installation requirements for the Galleon II and III UPS systems?
Installation requires a stable environment with proper ventilation. Ensure the system is connected to a compatible power source and follow the installation guidelines provided in the manual.
What warranty is provided with the Galleon II and III UPS systems?
Voltronic Power typically offers a standard warranty period for their UPS systems. For specific warranty details, please consult the warranty documentation or contact customer support.
What certifications and standards do these UPS systems meet?
The Galleon II and III UPS systems are certified to meet standard industry certifications, ensuring reliable performance and safety.
What are the operating conditions for these UPS systems?
These UPS systems are designed to operate efficiently within a temperature range of 0°C to 40°C and a relative humidity of 0% to 95% non-condensing.
What are the key features and benefits of the Galleon II and III UPS systems?
Key features include zero transfer time, pure sine wave output in battery mode, and robust overload capabilities. These features ensure uninterrupted power supply and protection for sensitive equipment.