Voltronic VM-II-4000-TWIN-PV-5600 / VOLTRONIC-VM-II-6000-TWIN-PV-8000
Discover the VM II-4000 TWIN-PV 5600 inverter by Voltronic Power with 230 VAC, 8000VA surge power, and auto-sensing frequency for optimal performance.
Technical Specifications
| Parameter | VOLTRONIC-VM-II-4000-TWIN-PV-5600 | VOLTRONIC-VM-II-6000-TWIN-PV-8000 |
|---|---|---|
| Input | ||
| Voltage | 230 VAC | |
| Selectable Voltage Range | 170-280 VAC (For Personal Computers) | 90-280 VAC (For Home Appliances) |
| Frequency Range | 50 Hz/60 Hz (Auto sensing) | |
| Output | ||
| AC Voltage Regulation (Batt. Mode) | 230VAC ± 5% | |
| Efficiency (Peak) | 93% | |
| Transfer Time | 10 ms (For Personal Computers) | 20 ms (For Home Appliances) |
| Waveform | Pure sine wave | |
| Electrical Data | ||
| Surge Power | 8000VA | 12000VA |
| Battery Voltage | 24 VDC | 48 VDC |
| Floating Charge Voltage | 27 VDC | 54 VDC |
| Overcharge Protection | 33 VDC | 63 VDC |
| Maximum PV Array Power | 5600W | 8000W |
| Built-in Charger | ||
| Solar Charger type | MPPT | |
| Maximum PV Array Open Circuit Voltage | 500 VDC | |
| Maximum PV Input Current | 40A | |
| MPP Range @ Operating Voltage | 60-450 VDC | |
| Maximum Solar Charge Current | 120A | |
| Maximum AC Charge Current | 100A | |
| Maximum Charge Current | 120A | |
| Additional Specifications | ||
| Dual Outputs | Yes | |
| Mechanical Data | ||
| Dimension, D x W x H (mm) | 122 x 322.7 x 420.3 | |
| Net Weight (kgs) | 9.5 | 10.5 |
| Communication Interface | USB/RS232/RS485/Wi-Fi | |
| Operating Conditions | ||
| Humidity | 5% to 95% Relative Humidity(Non-condensing) | |
| Operating Temperature | -10°C to 50°C | |
| Storage Temperature | -15°C to 60°C | |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Sudan
| Market | Sudan |
| Grid authority / regulator | Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum |
| Quotation currency | SDG |
| Support hours timezone | Africa/Khartoum |
| Delivery & installation coverage | Khartoum, Omdurman, Port Sudan, Kassala, Nyala |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Sudan that is Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- Increased PV power to 5600W: Increased PV power to 5600W and 8000W based on model
- Maximum PV input current 40A: Maximum PV input current 40A
- Dual outputs, for smart load: Dual outputs, for smart load management
- Built-in WiFi for mobile monitoring: Built-in WiFi for mobile monitoring and OTA firmware upgrade
- Supports USB On-the-Go function: Supports USB On-the-Go function
- Built-in BMS communication port: Built-in BMS communication port
- Built-in meter calibration for optimized: Built-in meter calibration for optimized system operation
- Battery independent design: Battery independent design
- Built-in anti-dust kit: Built-in anti-dust kit
- Increased PV power to 8000W: Increased PV power to 5600W and 8000W based on model
Frequently Asked Questions
What are the main performance specifications of the Axpert VM II TWIN inverter?
The Axpert VM II TWIN inverter offers a peak efficiency of 93%, a surge power of 8000VA, and operates at a voltage of 230 VAC. It provides a pure sine wave output with an AC voltage regulation of 230VAC ± 5% in battery mode.
Is the Axpert VM II TWIN compatible with different battery types and solar panels?
Yes, the inverter is compatible with a 24 VDC battery system and supports solar panels with a maximum PV array power of 5600W. It features an MPPT solar charger with a maximum PV array open circuit voltage of 500 VDC.
What are the physical specifications of the Axpert VM II TWIN?
The physical dimensions and weight of the Axpert VM II TWIN are not specified in the provided details. Please refer to the product manual for exact measurements and weight.
What are the installation requirements for the Axpert VM II TWIN?
Installation requires a 230 VAC connection and a compatible battery system of 24 VDC. Ensure proper ventilation and adherence to safety standards during installation.
What warranty is offered with the Axpert VM II TWIN?
The warranty details for the Axpert VM II TWIN are not specified in the provided information. Please contact Voltronic Power or your distributor for warranty terms and conditions.
What certifications and standards does the Axpert VM II TWIN comply with?
The Axpert VM II TWIN complies with standard certifications, ensuring it meets industry standards for safety and performance. Specific certifications are not listed in the provided information.
What are the operating conditions for the Axpert VM II TWIN?
The specific operating temperature and humidity range are not detailed in the provided specifications. Generally, inverters should be operated in a cool, dry environment for optimal performance.
What are the key features and benefits of the Axpert VM II TWIN?
Key features include a high peak efficiency of 93%, pure sine wave output, and MPPT solar charging. These features ensure reliable performance and efficient energy conversion.