Technical Specifications
| Parameter | VOLTRONIC-AXPERT-MAX-E-DUPLEX-11K | AXPERT-MAX-E-DUPLEX-11K |
|---|---|---|
| Electrical Data | ||
| Circulation Current under No Load Condition | Max 2A | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| High Loss Return Frequency | 63±1Hz | |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | |
| Low Loss Voltage | 170Vac±7V (UPS) 90Vac±7V (Appliances) | |
| Max AC Input Current | 60A | |
| Max. Input Current | 27A x 2 (MAX 40A) | |
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| Nominal Input Voltage | 230Vac | |
| PV Array MPPT Voltage Range | 90Vdc 450Vdc | |
| Transfer time in parallel mode | Max 50ms | |
| High DC Cut-off Voltage | 63Vdc | |
| Peak Efficiency | 93% | |
| Charging Current | 150A UPS | |
| Efficiency | >95% ( Rated R load Line Mode | |
| Floating Charging Voltage | 54Vdc | |
| Output Voltage Regulation | 230Vac± 5% | |
| Rated Output Power | 11000W | |
| Rated Power | 11000W Max. PV Array Open Circuit | |
| Safety Certification | CE | |
| Additional Specifications | ||
| High Loss Frequency | 65±1Hz | |
| High Loss Return Voltage | 270Vac±7V | |
| High Loss Voltage | 280Vac±7V | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| Max AC Input Voltage | 300Vac | |
| Max. Charging Current | 150A | |
| Nominal Input Frequency | 50Hz/60Hz (Auto detection) | |
| Output Short Circuit Protection | Line mode: Circuit Breaker (70A) Battery mode: Electronic Circuits | |
| Parallel Kit | YES | |
| Parallel communication | CAN | |
| Power Unbalance Ratio | <5% 100% Load | |
| Max parallel numbers | 6 | |
| DC Offset | ≤100mV | |
| High DC Recovery Voltage | 61Vdc | |
| DC Voltage | DC Offset ≦100mV Power Limitation 55Vdc | |
| Input Voltage Waveform | Sinusoidal (utility or generator) Nominal | |
| Output Frequency | 60Hz or 50Hz Peak | |
| Overload Protection | Surge | |
| Start-up Voltage | 80V +/- 5Vdc Power Limitation PV Current MPPT temperature 75° 80° | |
| Selectable Voltage Range | 170-280 VAC (For Personal Computers) 90-280 VAC (For Home Appliances) | |
| Maxmum Solar Charge Current | 150A | |
| Battery | ||
| Overcharge Protection | 63Vdc Charging Algorithm 3-Step Charging Curve Time | 63 VDC |
| Battery Voltage | 48 VDC | |
| Floating Charge Voltage | 54 VDC | |
| AC Output | ||
| Transfer Time | 10ms typical (UPS); | 10 ms (For Personal Computers), 20 ms (For Home Appliances) |
| AC Voltage Regulation (Batt. Mode) | 230VAC ± 5% | |
| Surge Power | 22000VA | |
| Efficiency (Peak) | 93% | |
| Waveform | Pure sine wave | |
| Solar Charger & AC Charger | ||
| Maximum PV Array Power | 11000W (5500W x 2) | |
| MPPT Range @ Operating Voltage | 90 – 450 VDC | |
| Maximum PV Array Open Circuit Voltage | 500 VDC | |
| Maximum PV Input Current | 27A x 2(MAX 40A) | |
| Maximum Solar Charge Current | 150A | |
| Maximum AC Charge Current | 150A | |
| Maximum Charge Current | 150A | |
| Communication | ||
| Communication Interface | USB/RS232/RS485/WiFi/Dry-contact | |
| Standard | ||
| Compliance Safety | CE | |
| Physical | ||
| Dimension, D x W x H (mm) | 147.4 x 432.5 x 553.6 | |
| Net Weight (kgs) | 18.4 | |
| Operating Environment | ||
| Humidity | 5% to 95% | 5% to 95% Relative Humidity(Non-condensing) |
| Storage Temperature | -15°C~ 60°C | -15°C to 60°C |
| Operating Temperature | -10°C to 50°C | |
| Operating Conditions | ||
| Operating Temperature Range | -10°C to 50°C | |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Sudan
| Market | Sudan |
| Grid authority / regulator | Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum |
| Quotation currency | SDG |
| Support hours timezone | Africa/Khartoum |
| Delivery & installation coverage | Khartoum, Omdurman, Port Sudan, Kassala, Nyala |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Sudan that is Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- Two independent AC power sources: Two independent AC power sources connected and switched automatically
- Adjustable charging current setting for: Adjustable charging current setting for two different power sources via LCD operation and mobile APP
- Status indication with RGB lights: Status indication with RGB lights
- Maximum PV input current increases: Maximum PV input current increases to 27A
- Built-in Wi-Fi for mobile monitoring: Built-in Wi-Fi for mobile monitoring (Android/iOS App is available)
- Supports USB On-the-Go function: Supports USB On-the-Go function
- Replaceable fan design for ease: Replaceable fan design for ease of maintenance
- Battery independent design: Battery independent design
- Configurable AC/PV output usage timer: Configurable AC/PV output usage timer and prioritization
- Selectable input voltage range for: Selectable input voltage range for home appliances and personal computers
- Built-in anti-dust kit: Built-in anti-dust kit
- Parallel operation with 6 units: Parallel operation with 6 units
Frequently Asked Questions
What are the main performance specifications of the Axpert MAX E Duplex 11K?
The Axpert MAX E Duplex 11K offers a peak efficiency of 93% and can handle a surge power of 22000VA. It regulates AC voltage at 230VAC ± 5% in battery mode.
Is the Axpert MAX E Duplex 11K compatible with all battery types?
The inverter is designed for a 48 VDC battery system, making it compatible with most lead-acid and lithium-ion batteries that match this voltage.
What are the physical specifications of the Axpert MAX E Duplex 11K?
Currently, the specific dimensions and weight of the Axpert MAX E Duplex 11K are not provided. Please refer to the product manual or contact Voltronic Power for detailed physical specifications.
What are the installation requirements for the Axpert MAX E Duplex 11K?
Installation should be performed by a qualified technician. Ensure proper ventilation and avoid exposure to direct sunlight or moisture to maintain optimal performance.
What warranty does Voltronic Power offer for the Axpert MAX E Duplex 11K?
Voltronic Power typically offers a standard warranty for their products, but specific terms for the Axpert MAX E Duplex 11K should be confirmed with the retailer or manufacturer.
What certifications does the Axpert MAX E Duplex 11K have?
The Axpert MAX E Duplex 11K is CE certified, ensuring it meets European safety, health, and environmental protection standards.
What are the operating conditions for the Axpert MAX E Duplex 11K?
The inverter is designed to operate efficiently in a range of environmental conditions, but specific temperature and humidity ranges are not detailed in the provided specifications.
What are the key features and benefits of the Axpert MAX E Duplex 11K?
Key features include a pure sine wave output, a high maximum PV array power of 11000W, and a fast transfer time of 10 ms for personal computers, ensuring reliable and efficient power management.