Voltronic Power Solutions

Voltronic Power INFINISOLAR-WP-LV-PREMIUM-INFINISOLAR-WP-LV-12KW-PREMIUM

The InfiniSolar WP LV Premium InfiniSolar WP LV 12kw Premium is a hybrid solar inverter rated InfiniSolar WP LV 12kw Premium.

Models Covered: INFINISOLAR-WP-LV-PREMIUM-INFINISOLAR-WP-LV-12KW-PREMIUM

Manufacturer: Voltronic Power

Application: The InfiniSolar WP LV Premium InfiniSolar WP LV 12kw Premium is a hybrid solar inverter rated InfiniSolar WP LV 12kw Premium. Every figure on this page is read from the manufacturer's manual for the InfiniSolar WP LV Premium series.

Technical Specifications

Technical Specifications
Parameter INFINISOLAR-WP-LV-PREMIUM-INFINISOLAR-WP-LV-12KW-PREMIUM
Electrical / AC Output Data
Phase 120V/240V Split phase, 120V/208V Split phase
Rated Apparent Power 10000VA/10000W
Max Conversion Efficiency (DC/AC) 96%
PV String Input Data
Max PV Input Power 12000W
MPP Trackers / Strings per Tracker 2/18A (MAX 30A)
Nominal DC Voltage 40-62 VDC/48 VDC
Battery Data
Max Charge Power 10000W
Additional Specifications
Efficiency (DC to AC) 91%
Maximum Solar Charging Current 200A
Maximum AC Charging Current 200A
Maximum Charging Current 200A
Ground Fault Detection - NEC 690.5 Yes
PV Arc Fault Detection - NEC 690.11 Yes
Protection Features
Safety / EMC Standards UL1741SA, UL1741SB, CSA 22.2.107.1, CEC
Grid Connection Standards IEEE 1547.1:2020; IEEE 1547:2018, California Rule 21, HECO Rule 14H EMC FCC Part 15 Class B
DC Switch Yes
PV Rapid Shutdown Yes
Lightning Protection Yes
Operating Conditions
Operating Temperature -25°C to 60°C (>45°C derating)

Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.

Availability & grid compliance in Netherlands

Market Netherlands
Grid authority / regulator ACM Netherlands
Quotation currency EUR
Support hours timezone Europe/Amsterdam
Delivery & installation coverage Amsterdam, Rotterdam, The Hague, Utrecht

Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Netherlands that is ACM Netherlands. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.