Voltronic +Power E 400V

Discover the +Power E 400V, an advanced Online UPS solution by Voltronic Power. Designed for optimal performance, it supports a nominal voltage of 3 x 380VAC/400VAC/415VAC and features auto-sensing frequency capabilities. Ensure your critical systems are protected with its precise voltage regulation.

Models Covered: +Power E 15U-60, +Power E 15U-90

Manufacturer: Voltronic Power Technology Corp.

Application: Ideal for data centers, telecommunications, and industrial applications where reliable power backup is essential.

Three Phase Online UPS Output power factor 1 Modular design lowers MTTR Adjustable battery numbers Adjustable charging current
Download PDF Datasheet WhatsApp Us

Technical Specifications

Technical Specifications
Parameter +Power E 15U-60+Power E 15U-90
Input
Nominal Voltage 3 x 380VAC/400VAC/415VAC (3Ph+N)3 x 380VAC/400VAC/415VAC (3Ph+N)
Voltage Range 305 - 478 VAC at 70% - 100% load; 208 - 478 VAC for <70% load305 - 478 VAC at 70% - 100% load; 208 - 478 VAC for <70% load
Nominal Frequency 50/60Hz (Auto sensing)50/60Hz (Auto sensing)
Frequency Range 40Hz - 70Hz40Hz - 70Hz
Power Factor > 0.99 at 100% load, > 0.98 at 50% load> 0.99 at 100% load, > 0.98 at 50% load
Harmonic Distortion (THDi) < 3% @ 100% load< 3% @ 100% load
Output
Nominal Voltage 3 x 380VAC/400VAC/415VAC (3Ph+N)3 x 380VAC/400VAC/415VAC (3Ph+N)
Voltage Regulation (Steady state) ≤ ± 1% Typical (balanced load)≤ ± 1% Typical (balanced load)
Nominal Frequency 50Hz50Hz
Frequency Range (Synchronized) 46Hz - 54Hz or 56Hz - 64Hz46Hz - 54Hz or 56Hz - 64Hz
Overload Capability 1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
Harmonic Distortion ≤ 2% THD (Linear load); ≤ 4% THD (Non-linear load)≤ 2% THD (Linear load); ≤ 4% THD (Non-linear load)
Efficiency Up to 94.5%Up to 94.5%
Battery Charging
Nominal Voltage 216V (12V x 36 Pcs)216V (12V x 36 Pcs)
Maximum Voltage +/- 240V (12V x 40 Pcs)+/- 240V (12V x 40 Pcs)
Minimum Voltage +/- 192V (12V x 32 Pcs)+/- 192V (12V x 32 Pcs)
Float Charging Voltage 2.25V/Cell2.25V/Cell
Boost Charging Voltage 2.35V/Cell2.35V/Cell
Temperature Compensation Yes
Maximum Charging Current 6A (User-adjustable)8A (User-adjustable)
Physical
Cabinet Dimension (D x W x H) mm 1000 x 515 x 763
Net Weight (kg) 182183.5
Operating Conditions
Operating Temperature 0 - 40°C
Relative Humidity 0 - 95% non-condensing
Altitude <1000m for Nominal power
IP Protection IP 20
Communication
Smart RS-232 / USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
Certifications
Safety IEC/EN 60950-1; IEC/EN 62040-1
EMC IEC/EN 62040-2 Category C3

Note: Specifications are based on the official Voltronic Power datasheet. Values may be subject to change; always verify against the latest manufacturer documentation.

Key Features

High efficiency online double conversion technology

Output power factor 1

Modular design lowers MTTR

Adjustable battery numbers

Adjustable charging current

Built-in maintenance bypass switch for easy maintenance without interruption

Graphic 5.7” LCD design for easy configuration

Support 1+1 cabinets parallel

Applications & Use Cases

Typical Applications

  • Data centers
  • Hospitals and medical facilities
  • Banks and financial institutions
  • Telecommunications
  • Factories and industrial facilities

Regional Installation Notes (United Arab Emirates)

Climate Suitability: Suitable for United Arab Emirates's hot climate with reliable performance at high temperatures.

  • Ensure adequate ventilation
  • Protection from direct sunlight
  • Regular maintenance recommended

Frequently Asked Questions

What are the main performance specifications of the +Power E 400V?

The +Power E 400V offers a high efficiency of up to 94.5%. It operates at a nominal voltage of 3 x 380VAC/400VAC/415VAC and maintains a power factor greater than 0.99 at full load.

Is the +Power E 400V compatible with different battery types or solar panels?

The +Power E 400V is designed to work with a nominal battery voltage of 216V, consisting of 12V x 36 pieces. It is primarily intended for grid applications and does not directly support solar panels.

What are the physical specifications of the +Power E 400V?

The physical specifications, including dimensions and weight, are not specified in the provided details. Please refer to the product manual or contact Voltronic Power for precise information.

What are the installation requirements for the +Power E 400V?

Installation of the +Power E 400V requires a stable environment with appropriate electrical connections. It should be installed by a qualified technician to ensure safety and compliance with local regulations.

What warranty is provided with the +Power E 400V?

Voltronic Power typically offers a standard warranty for their products. For specific warranty terms for the +Power E 400V, please consult the product documentation or contact the supplier.

What certifications and standards does the +Power E 400V comply with?

The +Power E 400V complies with IEC/EN 60950-1, IEC/EN 62040-1, and IEC/EN 62040-2 Category C3 standards, ensuring safety and performance reliability.

What are the operating conditions for the +Power E 400V?

The +Power E 400V is designed to operate efficiently within a wide frequency range of 40Hz to 70Hz. Specific temperature and humidity conditions are not detailed, so refer to the manual for optimal operating conditions.

What are the key features and benefits of the +Power E 400V?

Key features of the +Power E 400V include high efficiency, low harmonic distortion, and robust overload capability. These features ensure reliable power supply and protection for sensitive equipment.