Voltronic Otima II

The Otima II UPS by Voltronic Power is engineered to deliver exceptional power backup with voltage options ranging from 110 to 240 VAC. Its precise voltage regulation ensures stability and reliability, making it an ideal choice for safeguarding your critical equipment.

Models Covered: Otima II T 800, Otima II T 1.1K, Otima II T 1.5K, Otima II T 2K, Otima II T 2.5K, Otima II T 3K, Otima II T 5K

Manufacturer: Voltronic Power Technology Corp.

Application: The Otima II is perfect for use in home offices, small businesses, and IT environments where reliable power backup is essential to protect sensitive electronics from power disturbances.

Line Interactive UPS Pure sine wave Output power factor 0.9
Download PDF Datasheet WhatsApp Us

Technical Specifications

Technical Specifications
Parameter Otima II T 800Otima II T 1.1KOtima II T 1.5KOtima II T 2KOtima II T 2.5KOtima II T 3KOtima II T 5K
Input
Voltage 110/115/120/127 VAC or 208/220/230/240 VAC110/115/120/127 VAC or 208/220/230/240 VAC110/115/120/127 VAC or 208/220/230/240 VAC110/115/120/127 VAC or 208/220/230/240 VAC110/115/120/127 VAC or 208/220/230/240 VAC110/115/120/127 VAC or 208/220/230/240 VAC208/220/230/240 VAC
Acceptable Voltage Range 81-152 VAC or 162-290 VAC81-152 VAC or 162-290 VAC81-152 VAC or 162-290 VAC81-152 VAC or 162-290 VAC81-152 VAC or 162-290 VAC81-152 VAC or 162-290 VAC162-290 VAC
Frequency Range 60/50 Hz (Auto sensing)
Output
Output Voltage 110/115/120/127 VAC or 208/220/230/240 VAC110/115/120/127 VAC or 208/220/230/240 VAC110/115/120/127 VAC or 208/220/230/240 VAC110/115/120/127 VAC or 208/220/230/240 VAC110/115/120/127 VAC or 208/220/230/240 VAC110/115/120/127 VAC or 208/220/230/240 VAC208/220/230/240 VAC
Voltage Regulation (Batt. Mode) ±1.5 % (Before battery alarm)
Frequency Range (Batt. Mode) 50 Hz or 60 Hz ± 1 Hz
Current Crest Ratio 3:1
Harmonic Distortion 2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm)
Transfer Time Typical 2-6 ms, 10ms max.
Waveform (Batt. Mode) Pure Sinewave
Efficiency
ECO Mode 97%
Buck & Boost Mode 95%
Battery Mode >= 88%, up to 90% @ nominal battery voltage>= 89%, up to 91% @ nominal battery voltage for 110/115/120/127 VAC>= 91%, up to 92% @ nominal battery voltage for 208/220/230/240 VAC
Battery
Type & Number 12 V/7 Ah x 212 V/9 Ah x 212 V/7 Ah x 212 V/9 Ah x 412 V/9 Ah x 412 V/9 Ah x 612 V/10 Ah x 6
Charging Current (max.) 1.5A
Charging Voltage 27.4 VDC ± 1%54.8 VDC ± 1%82.1 VDC ± 1%
Typical Recharge Time 4 hours recover to 90% capacity
Protection Features
Full Protection Overload, discharge, and overcharge protection
Physical Specifications
Dimension, DxWxH(mm) 397 x 145 x 220455 x 145 x 220421 x 190 x 318
Net Weight (kgs) 11.712.117.219.726.62934.5
Operating Conditions
Humidity 0-90 % RH @ 0- 40°C (Non-condensing)
Noise Level Less than 45dB
Altitude 0~3000m, 10% de-rating for over 1000m
Communication
Smart RS-232/USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser

Note: Specifications are based on the official Voltronic Power datasheet. Values may be subject to change; always verify against the latest manufacturer documentation.

Key Features

Pure sine wave

Output power factor 0.9

Programmable power management outlets

ECO (Efficiency Corrective Optimizer) operation for energy saving

Very high efficiency in battery mode

Boost and Buck AVR for voltage stabilization

Multiple communications available

3-stage smart battery charging control

Applications & Use Cases

Typical Applications

  • Data centers
  • Hospitals and medical facilities
  • Banks and financial institutions
  • Telecommunications
  • Factories and industrial facilities

Regional Installation Notes (United Arab Emirates)

Climate Suitability: Suitable for United Arab Emirates's hot climate with reliable performance at high temperatures.

  • Ensure adequate ventilation
  • Protection from direct sunlight
  • Regular maintenance recommended

Frequently Asked Questions

What are the main performance specifications of the Otima II UPS?

The Otima II UPS offers high efficiency with ECO Mode at 97% and Buck & Boost Mode at 95%. It supports a wide voltage range of 110/115/120/127 VAC or 208/220/230/240 VAC and maintains a voltage regulation of ±1.5% in battery mode.

Is the Otima II UPS compatible with different battery types or solar panels?

The Otima II UPS is designed to work with 12 V/7 Ah batteries. It does not directly support solar panels but can be integrated into a solar setup with appropriate inverters and controllers.

What are the physical specifications of the Otima II UPS?

The Otima II UPS has a compact design, but specific dimensions and weight are not provided in the key specifications. It does not have an IP rating, indicating it should be used in controlled environments.

What are the installation requirements for the Otima II UPS?

Installation of the Otima II UPS requires a stable surface and a connection to the appropriate voltage grid. Ensure proper ventilation and avoid exposure to moisture or extreme temperatures.

What warranty is offered with the Otima II UPS?

Voltronic Power typically offers a standard warranty for their UPS products, but specific warranty details for the Otima II should be confirmed with the retailer or manufacturer.

What certifications and standards does the Otima II UPS meet?

The Otima II UPS complies with standard certifications, ensuring it meets industry safety and performance standards. Specific certifications are not listed in the key specifications.

What are the operating conditions for the Otima II UPS?

The Otima II UPS should be operated in environments with controlled temperature and humidity. Specific operating conditions are not detailed in the key specifications.

What are the key features and benefits of the Otima II UPS?

Key features of the Otima II UPS include a pure sinewave output in battery mode, a fast transfer time of 2-6 ms, and a high current crest ratio of 3:1, making it suitable for sensitive electronics.